Status: CANCEL
| Parcel Id: 34-10-30-5860-00000-00H0 |
| Subdivision: 5860 - |
| Job Phone: 877-906-1113 |
| Location Address: 18 REDBUD RD |
| Type: CE - COMMERCIAL ELECTRIC |
| Issue Date: 02/07/2024 |
| NOC: Unknown |
| Applicant name: JOSEPH HORATIO STRADA JR |
| Owner: TRAILS OF PALM COAST HOMEOWNERS ASSOCIATION INC |
|
Address 2695 DOBBS ROAD ST. AUGUSTINE, FL 32086 |
| Contracted Stated Job Value: ¤1,200.00 |
| Job Description: 200amp irrigation service pedestal. |
| Type: CN |
Contractor
STRADA SERVICES LLC
| Status | Location Address | State License Number | Phone |
| ACTIVE |
3400 ST JOHNS PARKWAY SANFORD, FL 32771 |
EC13003715 (Exp: 08/31/2026) | 877-906-1113 |
Inspection History
| Type | Request Date | Result | Inspector |
| ELECTRIC FINAL | 06/14/2024 | Disapproved -FEE REQUIRED | RMARTIN |
| Note: *** NOTES ADDED BY RMARTIN 6/14/2024 11:20:00 AM *** Pump calls for a max breaker of 30 amps not 40. *** NOTES ADDED BY RMARTIN 6/14/2024 11:19:50 AM *** 6/7/2024 - PREVIOUS INSPECTION NOTES *** NOTES ADDED BY JMUNSON 6/7/2024 9:38:20 AM *** Pump calls for a max breaker of 30 amps not 40. 5/15/2024 - PREVIOUS INSPECTION NOTES 5/15/24 Power release and email sent to FPL @ 10am , once meter is set call in for final 5/13/2024 - PREVIOUS INSPECTION NOTES 5/13/234 Make all repairs before calling in re-inspection 3/27/2024 - PREVIOUS INSPECTION NOTES 3/27/24 1. No approved plans on site FBC 107.3.1 2. Breakers are required to be labeled NEC 210.5 3. Ground wire must be protected NEC 250.64 4. Liquid tight can not be in areas subjust to physical damaage NEC 356.12 5. Connection made for ground wire to ground rods are not approved per manufacturer specs 3/21/2024 - PREVIOUS INSPECTION NOTES NEED TO HAVE SCH. 80 PVC WHERE SUBJECT TO PHYSICAL DAMAGE NEC 300.5, NEED TO UN-COVER GROUND RODS TO BE INSPECTED, NEED TO PROVIDE SITE STICKS FOR SERVICE CONDUIT DEPTH, NEED APPROVED PLANS ON SITE, GROUNDING CONDUCTOR NEEDS TO BE PROTECTED/SLEEVED NEC 250.64 | |||
| ELECTRIC FINAL | 06/07/2024 | Disapproved -FEE REQUIRED | JMUNSON |
| Note: *** NOTES ADDED BY JMUNSON 6/7/2024 9:38:20 AM *** Pump calls for a max breaker of 30 amps not 40. 5/15/2024 - PREVIOUS INSPECTION NOTES 5/15/24 Power release and email sent to FPL @ 10am , once meter is set call in for final 5/13/2024 - PREVIOUS INSPECTION NOTES 5/13/234 Make all repairs before calling in re-inspection 3/27/2024 - PREVIOUS INSPECTION NOTES 3/27/24 1. No approved plans on site FBC 107.3.1 2. Breakers are required to be labeled NEC 210.5 3. Ground wire must be protected NEC 250.64 4. Liquid tight can not be in areas subjust to physical damaage NEC 356.12 5. Connection made for ground wire to ground rods are not approved per manufacturer specs 3/21/2024 - PREVIOUS INSPECTION NOTES NEED TO HAVE SCH. 80 PVC WHERE SUBJECT TO PHYSICAL DAMAGE NEC 300.5, NEED TO UN-COVER GROUND RODS TO BE INSPECTED, NEED TO PROVIDE SITE STICKS FOR SERVICE CONDUIT DEPTH, NEED APPROVED PLANS ON SITE, GROUNDING CONDUCTOR NEEDS TO BE PROTECTED/SLEEVED NEC 250.64 | |||
| ELECTRIC FINAL | 05/15/2024 | PARTIALLY APPROVED | MKRASKI |
| Note: 5/15/24 Power release and email sent to FPL @ 10am , once meter is set call in for final 5/13/2024 - PREVIOUS INSPECTION NOTES 5/13/234 Make all repairs before calling in re-inspection 3/27/2024 - PREVIOUS INSPECTION NOTES 3/27/24 1. No approved plans on site FBC 107.3.1 2. Breakers are required to be labeled NEC 210.5 3. Ground wire must be protected NEC 250.64 4. Liquid tight can not be in areas subjust to physical damaage NEC 356.12 5. Connection made for ground wire to ground rods are not approved per manufacturer specs 3/21/2024 - PREVIOUS INSPECTION NOTES NEED TO HAVE SCH. 80 PVC WHERE SUBJECT TO PHYSICAL DAMAGE NEC 300.5, NEED TO UN-COVER GROUND RODS TO BE INSPECTED, NEED TO PROVIDE SITE STICKS FOR SERVICE CONDUIT DEPTH, NEED APPROVED PLANS ON SITE, GROUNDING CONDUCTOR NEEDS TO BE PROTECTED/SLEEVED NEC 250.64 | |||
| ELECTRIC FINAL | 05/13/2024 | CANCELLED BY APPLICANT | WEB |
| Note: 3/27/2024 - PREVIOUS INSPECTION NOTES 3/27/24 1. No approved plans on site FBC 107.3.1 2. Breakers are required to be labeled NEC 210.5 3. Ground wire must be protected NEC 250.64 4. Liquid tight can not be in areas subjust to physical damaage NEC 356.12 5. Connection made for ground wire to ground rods are not approved per manufacturer specs 3/21/2024 - PREVIOUS INSPECTION NOTES NEED TO HAVE SCH. 80 PVC WHERE SUBJECT TO PHYSICAL DAMAGE NEC 300.5, NEED TO UN-COVER GROUND RODS TO BE INSPECTED, NEED TO PROVIDE SITE STICKS FOR SERVICE CONDUIT DEPTH, NEED APPROVED PLANS ON SITE, GROUNDING CONDUCTOR NEEDS TO BE PROTECTED/SLEEVED NEC 250.64 | |||
| ELECTRIC FINAL | 05/13/2024 | Disapproved -FEE REQUIRED | MKRASKI |
| Note: 5/13/234 Make all repairs before calling in re-inspection 3/27/2024 - PREVIOUS INSPECTION NOTES 3/27/24 1. No approved plans on site FBC 107.3.1 2. Breakers are required to be labeled NEC 210.5 3. Ground wire must be protected NEC 250.64 4. Liquid tight can not be in areas subjust to physical damaage NEC 356.12 5. Connection made for ground wire to ground rods are not approved per manufacturer specs 3/21/2024 - PREVIOUS INSPECTION NOTES NEED TO HAVE SCH. 80 PVC WHERE SUBJECT TO PHYSICAL DAMAGE NEC 300.5, NEED TO UN-COVER GROUND RODS TO BE INSPECTED, NEED TO PROVIDE SITE STICKS FOR SERVICE CONDUIT DEPTH, NEED APPROVED PLANS ON SITE, GROUNDING CONDUCTOR NEEDS TO BE PROTECTED/SLEEVED NEC 250.64 | |||
| ELECTRIC FINAL | 03/27/2024 | Disapproved -FEE REQUIRED | MKRASKI |
| Note: 3/27/24 1. No approved plans on site FBC 107.3.1 2. Breakers are required to be labeled NEC 210.5 3. Ground wire must be protected NEC 250.64 4. Liquid tight can not be in areas subjust to physical damaage NEC 356.12 5. Connection made for ground wire to ground rods are not approved per manufacturer specs 3/21/2024 - PREVIOUS INSPECTION NOTES NEED TO HAVE SCH. 80 PVC WHERE SUBJECT TO PHYSICAL DAMAGE NEC 300.5, NEED TO UN-COVER GROUND RODS TO BE INSPECTED, NEED TO PROVIDE SITE STICKS FOR SERVICE CONDUIT DEPTH, NEED APPROVED PLANS ON SITE, GROUNDING CONDUCTOR NEEDS TO BE PROTECTED/SLEEVED NEC 250.64 | |||
| ELECTRIC FINAL | 03/21/2024 | Disapproved - NO FEE | RMARTIN |
| Note: NEED TO HAVE SCH. 80 PVC WHERE SUBJECT TO PHYSICAL DAMAGE NEC 300.5, NEED TO UN-COVER GROUND RODS TO BE INSPECTED, NEED TO PROVIDE SITE STICKS FOR SERVICE CONDUIT DEPTH, NEED APPROVED PLANS ON SITE, GROUNDING CONDUCTOR NEEDS TO BE PROTECTED/SLEEVED NEC 250.64 | |||
| ELECTRIC FINAL | |||
| Note: 6/14/2024 - PREVIOUS INSPECTION NOTES *** NOTES ADDED BY RMARTIN 6/14/2024 11:20:00 AM *** Pump calls for a max breaker of 30 amps not 40. *** NOTES ADDED BY RMARTIN 6/14/2024 11:19:50 AM *** 6/7/2024 - PREVIOUS INSPECTION NOTES *** NOTES ADDED BY JMUNSON 6/7/2024 9:38:20 AM *** Pump calls for a max breaker of 30 amps not 40. 5/15/2024 - PREVIOUS INSPECTION NOTES 5/15/24 Power release and email sent to FPL @ 10am , once meter is set call in for final 5/13/2024 - PREVIOUS INSPECTION NOTES 5/13/234 Make all repairs before calling in re-inspection 3/27/2024 - PREVIOUS INSPECTION NOTES 3/27/24 1. No approved plans on site FBC 107.3.1 2. Breakers are required to be labeled NEC 210.5 3. Ground wire must be protected NEC 250.64 4. Liquid tight can not be in areas subjust to physical damaage NEC 356.12 5. Connection made for ground wire to ground rods are not approved per manufacturer specs 3/21/2024 - PREVIOUS INSPECTION NOTES NEED TO HAVE SCH. 80 PVC WHERE SUBJECT TO PHYSICAL DAMAGE NEC 300.5, NEED TO UN-COVER GROUND RODS TO BE INSPECTED, NEED TO PROVIDE SITE STICKS FOR SERVICE CONDUIT DEPTH, NEED APPROVED PLANS ON SITE, GROUNDING CONDUCTOR NEEDS TO BE PROTECTED/SLEEVED NEC 250.64 |
Review History
| Department | Status | Date In | Date Out |
| ELEC | COMPLETE | 02/02/2024 | 02/05/2024 |
| Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM | |||
| ELEC | HOLD | 02/01/2024 | 02/01/2024 |
| Note: Held By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM 1. Need to apply for a commercial electrical permit. 2. You always need to submit a electrical riser diagram that includes all wire sizes, breaker sizes and GFCI protection. |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| REINSPECTION - COMMERCIAL | ¤60.00 | 06/18/2024 |
| REINSPECTION - COMMERCIAL | ¤60.00 | 06/11/2024 |
| REINSPECTION - COMMERCIAL | ¤60.00 | 05/13/2024 |
| REINSPECTION - COMMERCIAL | ¤60.00 | 03/29/2024 |
| SURCHARGE FS 533.721 | ¤2.00 | 02/07/2024 |
| SURCHARGE - FS 468.631 | ¤2.00 | 02/07/2024 |
| ADJUSTMENT 50% | (¤83.75) | 02/07/2024 |
| ADMINISTRATIVE - COMMERCIAL | ¤75.00 | 02/07/2024 |
| INSPECTION- ELECTRICAL | ¤60.00 | 02/07/2024 |
| PLAN REVIEW - MISC 32.50 | ¤32.50 | 02/07/2024 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤327.75 |