Permit #2024030692

Permit Details

Status: EXPIRED

Parcel Id: 07-11-31-1090-000C0-0000
Block: 000C0
Subdivision: 1228 - SOUTHWEST QUADRANT
Location Address: 160 CYPRESS POINT PKWY
Type: CIA - COMMERCIAL INTERIOR EXTERIOR ALTERATION
Issue Date: 04/02/2024
NOC: RECORDED
Applicant name: NO CONTRACTOR OF RECORD
Owner: BETHEA PROPERTIES LLC

Address

4662 RIVER POINT RD W

JACKSONVILLE, FL 32207

Lot: 0000
Contracted Stated Job Value: ¤200,000.00
Job Description: UNIT C110 & C111 - (COMBINE UNITS) "CUE NOTE BILLIARD ROOM" 2019050177
Type: CN
Original Permit #: 2019050177

Contractor

NO CONTRACTOR OF RECORD
Status State License Number
CANCEL CGC1111111 (Exp: 05/20/2016)

Sub Contractors

SHAWN MICHAEL HISS
Status Location Address State License Number Phone
ACTIVE

1315 LPGA BLVD

HOLLY HILL, FL 32117

CAC1813585 (Exp: 08/31/2026) (386)672-8688
THOMAS JOSEPH WALL
Status Location Address State License Number Phone
ACTIVE

PO BOX 314

PALAKTKA, FL 32177

CFC037193 (Exp: 08/31/2026) 386-336-9050
DANIEL JOSEPH SCHWARZKOPF
Status Location Address State License Number Phone
ACTIVE

4601 E MOODY BLVD D6

PALM COAST, FL 32164

EC13010351 (Exp: 08/31/2026) 386-313-6211
BERNARD V ELLIOTT III
Status Location Address State License Number Phone Fax
INACTIVE

4533 SUNBEAM ROAD # 493

JACKSONVILLE, FL 32257

CAC057663 (Exp: 08/31/2024) 904-662-2792 904-221-5560

Inspection History

Type Request Date Result Inspector
FIREWALL NAILING 08/07/2023 APPROVED FWILLIS
Note: 4/28/2023 - PREVIOUS INSPECTION NOTES ***dorlock calulking in the kitchen and fire caulk in kitchen also. Call John when on the way 386-503-2902 8/7/23 - FIREWALL IN KITCHEN AREA ONLY.
FIREWALL NAILING 04/28/2023 CANCELLED BY APPLICANT FWILLIS
U-GREASE INTERCEPTOR FLOW/DYE TESTED 04/11/2023 CANCELLED BY APPLICANT WEB
U-GREASE INTERCEPTOR FLOW/DYE TESTED 04/11/2023 APPROVED - AS NOTED LFITZGERALD
Note: please call /contact me(386)286-2041 lfitzgerald@palmcoastgov.com, when 2nd mop sink/basin is connected to the original to ensure it goes to the grease trap as well
FRAMING 07/26/2022 PARTIALLY APPROVED FWILLIS
Note: THIS IS A REINSPECTION THIS IS A REINSPECTION NOT READY FOR FRAMING INSPECTION. A FULL SET OF APPROVED DRAWINGS AND DOCUMENTS MUST BE KEPT ON SITE 107.3,1. ACCESS IS NEEDED WHEN INSPECTION IS SCHEDULED. 7/19/22 - SCHEDULE ELECTRICAL AND PLUMBING BEFORE THE FRAME. 7/26/22 - Partial framing Kitchen area Only.
PLUMBING 1ST ROUGH 07/25/2022 PARTIALLY APPROVED MGIBSON
Note: THIS IS A REINSPECTION THIS IS A REINSPECTION THIS WAS FOR THE REST OF THE FIRST ROUGH, WHICH INCLUDED ADDITIONAL WORK DONE ON THE EXISTING PART OF PROJECT, ALSO THE REVISION WAS SUBMITTED TO BUILDING AND PLANNING DEPARTMENT UPON APPROVAL BY PLAN EXAMINER MUST HAVE BY BUILDING FIN AL Partial inspectionon only, all condensate rain lines need to be rerouted to exterior of building per land development code,all AAV need to be open to grill covers
ELECTRIC 2ND ROUGH 07/25/2022 PARTIALLY APPROVED RMARTIN
Note: THIS IS A REINSPECTION THIS IS A REINSPECTION THIS IS A REINSPECTION THIS IS A REINSPECTION 9/3/20 need a few nail plates on kick plates in bar area, straps on existing wiring in walls 3/4/21 marked on print, bar area, north side exterior walls 7/20/22 all doors locked, looked in windows could not see anyone, called the number given no answer, need access for inspection, also need to have addresses on doors 7/25/22 KITCHEN WALLS, MARKED ON PRINT
ELECTRIC 2ND ROUGH 07/20/2022 Disapproved -FEE REQUIRED RMARTIN
Note: THIS IS A REINSPECTION THIS IS A REINSPECTION THIS IS A REINSPECTION 9/3/20 need a few nail plates on kick plates in bar area, straps on existing wiring in walls 3/4/21 marked on print, bar area, north side exterior walls 7/20/22 all doors locked, looked in windows could not see anyone, called the number given no answer, need access for inspection, also need to have addresses on doors
PLUMBING 1ST ROUGH 07/20/2022 CANCELLED BY APPLICANT JWALKER
Note: THIS IS A REINSPECTION THIS WAS FOR THE REST OF THE FIRST ROUGH, WHICH INCLUDED ADDITIONAL WORK DONE ON THE EXISTING PART OF PROJECT, ALSO THE REVISION WAS SUBMITTED TO BUILDING AND PLANNING DEPARTMENT UPON APPROVAL BY PLAN EXAMINER MUST HAVE BY BUILDING FIN AL
FRAMING 07/19/2022 Disapproved - NO FEE FWILLIS
Note: THIS IS A REINSPECTION NOT READY FOR FRAMING INSPECTION. A FULL SET OF APPROVED DRAWINGS AND DOCUMENTS MUST BE KEPT ON SITE 107.3,1. ACCESS IS NEEDED WHEN INSPECTION IS SCHEDULED. 7/19/22 - SCHEDULE ELECTRICAL AND PLUMBING BEFORE THE FRAME.
FRAMING 03/21/2022 Disapproved - NO FEE FWILLIS
Note: NOT READY FOR FRAMING INSPECTION. A FULL SET OF APPROVED DRAWINGS AND DOCUMENTS MUST BE KEPT ON SITE 107.3,1. ACCESS IS NEEDED WHEN INSPECTION IS SCHEDULED.
INSULATION 03/21/2022 PARTIALLY APPROVED FWILLIS
Note: PARTIAL 3/21/22 - FRONT WALL AND REAR WALL ONLY.
ELECTRIC 2ND ROUGH 03/04/2021 PARTIALLY APPROVED RMARTIN
Note: THIS IS A REINSPECTION THIS IS A REINSPECTION 9/3/20 need a few nail plates on kick plates in bar area, straps on existing wiring in walls 3/4/21 marked on print, bar area, north side exterior walls
ELECTRIC 2ND ROUGH 09/03/2020 PARTIALLY APPROVED RMARTIN
Note: THIS IS A REINSPECTION 9/3/20 need a few nail plates on kick plates in bar area, straps on existing wiring in walls
PLUMBING 1ST ROUGH 06/09/2020 PARTIALLY APPROVED JGIBSON
Note: THIS WAS FOR THE REST OF THE FIRST ROUGH, WHICH INCLUDED ADDITIONAL WORK DONE ON THE EXISTING PART OF PROJECT, ALSO THE REVISION WAS SUBMITTED TO BUILDING AND PLANNING DEPARTMENT UPON APPROVAL BY PLAN EXAMINER MUST HAVE BY BUILDING FINAL
PLUMBING 2ND ROUGH 03/17/2020 APPROVED JGIBSON
PLUMBING 1ST ROUGH 10/07/2019 APPROVED - AS NOTED JGIBSON
Note: THIS IS A REINSPECTION THIS WAS APPROVED BASED ON LETTER VARIFICATION OF RISER SUBMITTED FROM ENGINEER
MONOLITHIC SLAB 10/04/2019 APPROVED MWILLIAMS
PLUMBING 1ST ROUGH 10/01/2019 Disapproved - NO FEE JGIBSON
Note: DISCREPANCY ON PLAN PAGES P-001 AND P-100 ON SIZE OF WASTE LINES FOR GREASE , FIXTURE SCHEDUAL IS CALLING FOR 3'' WASTE FOR FLOOR DRAINS AND FLOOR SINKS, NEED CLARIFICATION. NEED TO CHANGE 3'' 90 TO 3'' LONG SWEEP OR 2-- 3'' 45 PER TABLE 706.3
ELECTRIC 2ND ROUGH 10/01/2019 PARTIALLY APPROVED RMARTIN
Note: UNDERGROUND GOOD, CALL BACK IN WHEN WALLS ARE ROUGHED IN
HVAC ROUGH 10/01/2019 PARTIALLY APPROVED CPISCITELLI
Note: Inspected copper lines in the ground and going up to ceiling only.
HVAC ROUGH
Note: THIS IS A REINSPECTION
HVAC FINAL
ELECTRIC 2ND ROUGH
Note: THIS IS A REINSPECTION THIS IS A REINSPECTION THIS IS A REINSPECTION THIS IS A REINSPECTION THIS IS A REINSPECTION 9/3/20 need a few nail plates on kick plates in bar area, straps on existing wiring in walls 3/4/21 marked on print, bar area, north side exterior walls 7/20/22 all doors locked, looked in windows could not see anyone, called the number given no answer, need access for inspection, also need to have addresses on doors 7/25/22 KITCHEN WALLS, MARKED ON PRINT
ELECTRIC FINAL
PLUMBING FINAL
PLUMBING 1ST ROUGH
Note: THIS IS A REINSPECTION THIS IS A REINSPECTION THIS IS A REINSPECTION THIS WAS FOR THE REST OF THE FIRST ROUGH, WHICH INCLUDED ADDITIONAL WORK DONE ON THE EXISTING PART OF PROJECT, ALSO THE REVISION WAS SUBMITTED TO BUILDING AND PLANNING DEPARTMENT UPON APPROVAL BY PLAN EXAMINER MUST HAVE BY BUILDING FIN AL Partial inspectionon only, all condensate rain lines need to be rerouted to exterior of building per land development code,all AAV need to be open to grill covers
FRAMING
Note: THIS IS A REINSPECTION THIS IS A REINSPECTION THIS IS A REINSPECTION NOT READY FOR FRAMING INSPECTION. A FULL SET OF APPROVED DRAWINGS AND DOCUMENTS MUST BE KEPT ON SITE 107.3,1. ACCESS IS NEEDED WHEN INSPECTION IS SCHEDULED. 7/19/22 - SCHEDULE ELECTRICAL AND PLUMBING BEFORE THE FRAME. 7/26/22 - Partial framing Kitchen area Only.
ABOVE CEILING
INSULATION
Note: THIS IS A REINSPECTION PARTIAL 3/21/22 - FRONT WALL AND REAR WALL ONLY.
BUILDING FINAL
FIRE FINAL
U - UTILITY COMMERCIAL FINAL

Review History

Department Status Date In Date Out
BADMIN COMPLETE 05/11/2021 05/11/2021
Note: Released By: MARGA DEFREITAS - - MDEFREITAS@PALMCOASTGOV.COM
BADMIN HOLD 05/04/2021 05/04/2021
Note: Held By: BARBIE BEMBRY - (386)986-3780 - BUILDINGDIVISION@PALMCOASTGOV.COM Please provide authorization from the property owner relieving your responsibility from this permit.
BLD COMPLETE 03/03/2020 03/16/2020
Note: Released By: FREODICA Revision #2 - Sheet A-1- interior wall relocation.
PLUM COMPLETE 10/03/2019 10/17/2019
Note: Released By: MGARRETT
ZON COMPLETE 07/29/2019 07/29/2019
Note: Released By: JGONZALEZ
ZON HOLD 07/12/2019 07/16/2019
Note: Held By: JGONZALEZ Provide an application license for extendsion of licensed premises or amended sketch of license premise ABT 6029 form.
BLD COMPLETE 07/12/2019 07/26/2019
Note: Released By: JHINDMAN
MECH COMPLETE 07/12/2019 07/23/2019
Note: Released By: MGARRETT
PLUM COMPLETE 07/12/2019 07/23/2019
Note: Released By: MGARRETT
BLD HOLD 05/06/2019 05/20/2019
Note: Held By: JHINDMAN 1. Provide an accessible ramp to the stage 6th ed. FBC Accessibility code 303.4. 2. remove Future phase two area's from drawing.
ELEC COMPLETE 05/06/2019 05/20/2019
Note: Released By: JHINDMAN
FI1 COMPLETE 05/06/2019 05/20/2019
Note: Released By: JHINDMAN
MECH HOLD 05/06/2019 05/20/2019
Note: Held By: RLEE Remove future mechanical systems, adn future floor plan area.
PLUM HOLD 05/06/2019 05/20/2019
Note: Held By: RLEE provide floor plan for thgree compartment sink and bar equipment
UD1 COMPLETE 05/06/2019 05/08/2019
Note: Released By: CJOHNSON
ZON HOLD 05/06/2019 05/06/2019
Note: Held By: JGONZALEZ Provide Form ABT6029 to amended sketch for alcohol permit.

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
ADJUSTMENT 50% (¤737.50) 04/02/2024
ADMINISTRATIVE - COMMERCIAL ¤75.00 04/02/2024
INSPECTION COMMERCIAL ¤1,400.00 04/02/2024
SURCHARGE FS 533.721 ¤7.38 04/02/2024
SURCHARGE - FS 468.631 ¤11.06 04/02/2024
CONTRACTOR CHANGE ¤20.00
Fees Total Due: ¤20.00 Total Paid: ¤755.94