I want to search for...

Permit #2024030695

Permit Details

Status: COED

Parcel Id: 07-11-31-7023-00350-0440
CONDITIONED SPACE: 1800 sqft
GARAGE: 434 sqft
OPENED PORCH (WITH ROOF) : 132 sqft
OPENED PORCH (WITH ROOF) : 108 sqft
Total Square Footage: 2474 sqft
Block: 00350
Subdivision: -
Job Phone: 832-726-2202
Location Address: 3 WHITE HAWK PL
Type: BR - BUILDING RESIDENTIAL -SINGLE FAMILY
Issue Date: 04/01/2024
NOC: RECORDED
Applicant name: JONATHON AMBAR
Owner: CASPIAN INVESTMENTS 1 LLC

Address

1802 N ALAFAYA TRAIL

ORLANDO, FL 32826

Address

164

ORLANDO, FL 32826

Lot: 0440
Contracted Stated Job Value: ¤131,500.00
Job Description: SINGLE FAMILY RESIDENCE
Type: CN

Contractor

CASPIAN HOMES, LLC
Status Location Address Mailing Address State License Number Phone
ACTIVE

1802 N ALAFAYA TRAIL

ORLANDO, FL 32826

SUITE 162

ORLANDO, FL 32826

CBC1264918 (Exp: 08/31/2026) 832-726-2202

Sub Contractors

TERRY BRICE DICKERSON
Status Location Address State License Number Phone
ACTIVE

4300 ST JOHN'S PARKWAY

ALPHARETTA, GA 30009

CCC1326209 (Exp: 08/31/2026) 407-548-6733
DAVID SCOTT MORRIS
Status Location Address State License Number Phone
INACTIVE

63 LEIDEL DR

PALM COAST, FL 32137

ER13015750 (Exp: 08/31/2026) 386-569-7262
ROBERT MICHAEL RENNER
Status Location Address State License Number Phone
ACTIVE

531 CODISCO WAY

SANFORD, FL 32771

CAC051477 (Exp: 08/31/2026) 407-333-2665
HEATH EDWARD SANFORD
Status Location Address State License Number Phone
ACTIVE

126 EAST END RD

SAN MATEO, FL 32187

CFC1429896 (Exp: 08/31/2026) 386-871-8823

Inspection History

Type Request Date Result Inspector
BLD - BUILDING FINAL 12/31/2024 FINAL APPROVED MKRASKI
BLD - BUILDING FINAL 12/26/2024 Disapproved - NO FEE MKRASKI
Note: 12/26/24 1. Item 3 still not repaired a 45a breaker is installed on AHU FBCR M1303.1 12/23/2024 - PREVIOUS INSPECTION NOTES 12/23/24 1. Whole home surge required to be @ meter main NEC 230.67(B) 2. Seal all exterior penitrations (pep tank) FBC R402.4.1.1 3. AHU breaker undersized per heater sticker, sticker calls for 50a @240v a 45a breaker is installed on AHU for disconnect FBCR M1303.1 12/19/2024 - PREVIOUS INSPECTION NOTES 1. Whole home surge required to be @ meter main NEC 230.67(B) 2. ODU requires 4 hold downs FBC M1401.1 3. Seal all exterior penitrations (pep tank) FBC R402.4.1.1 4. Gutter down spouts must be a min of 12'' off home FBCR 318.5 5. Fridge outlet not working 6. AHU breaker undersized per heater sticker 7. Anchor for garage door opener buck is missing 1 of 2 per plans 8. Seal arond J boxes in garage feeding outside garage lights (exposed romex) 9. ODU required to be a min of 3'' off grade FBCR M1305.1.4.1 10. Front bedroom smoke not interconnected with other smokes FBCR 314 & 315
BLD - BUILDING FINAL 12/23/2024 Disapproved -FEE REQUIRED MKRASKI
Note: 12/23/24 1. Whole home surge required to be @ meter main NEC 230.67(B) 2. Seal all exterior penitrations (pep tank) FBC R402.4.1.1 3. AHU breaker undersized per heater sticker, sticker calls for 50a @240v a 45a breaker is installed on AHU for disconnect FBCR M1303.1 12/19/2024 - PREVIOUS INSPECTION NOTES 1. Whole home surge required to be @ meter main NEC 230.67(B) 2. ODU requires 4 hold downs FBC M1401.1 3. Seal all exterior penitrations (pep tank) FBC R402.4.1.1 4. Gutter down spouts must be a min of 12'' off home FBCR 318.5 5. Fridge outlet not working 6. AHU breaker undersized per heater sticker 7. Anchor for garage door opener buck is missing 1 of 2 per plans 8. Seal arond J boxes in garage feeding outside garage lights (exposed romex) 9. ODU required to be a min of 3'' off grade FBCR M1305.1.4.1 10. Front bedroom smoke not interconnected with other smokes FBCR 314 & 315
BLD - BUILDING FINAL 12/19/2024 Disapproved -FEE REQUIRED MKRASKI
Note: 1. Whole home surge required to be @ meter main NEC 230.67(B) 2. ODU requires 4 hold downs FBC M1401.1 3. Seal all exterior penitrations (RG6 and pep tank) FBC R402.4.1.1 4. Gutter down spouts must be a min of 12'' off home FBCR 318.5 5. Fridge outlet not working 6. AHU breaker undersized per heater sticker 7. Anchor for garage door opener buck is missing 1 of 2 per plans 8. Seal arond J boxes in garage feeding outside garage lights (exposed romex) 9. ODU required to be a min of 3'' off grade FBCR M1305.1.4.1 10. Front bedroom smoke not interconnected with other smokes FBCR 314 & 315
ROW - FINAL APRON (AFTER POUR) 12/17/2024 APPROVED TPOLACEK
Note: PIPE ELEVATION IS GOOD, CUTS ARE MADE, CULVERT CLEAR, HOT PATCH COMPLETE. AT THE TIME OF THE INSPECTION ALL MINIMUM CITY REQUIREMENTS WERE MET. IT IS THE BUILDER'S RESPONSIBILITY TO ENSURE THAT NOTHING CHANGES AFTER THIS INSPECTION IS APPROVED. 10/03/24 TPOLACEK***NOTE*** SPOKE WITH FRED DRIVEWAY APRON SLOPE EXCEEDED 8% HE WILL HAVE CONTRATOR MAKE SURE IT IS BELOW 8% BEFORE THEY POUR
ROW - STORMWATER FINAL 12/17/2024 APPROVED TPOLACEK
Note: AT THE TIME OF THE INSPECTION, ALL MINIMUM CITY REQUIREMENTS WERE MET. NIETHER THE INSPECTOR NOR THE CITY IS RESPONSIBLE IF, FOR WHATEVER REASON, SITE CONDITIONS CHANGE OVER TIME AFTER THE INSPECTION. IT IS THE BUILDER'S RESPONSIBILITY TO ENSURE THAT NOTHING CHANGES AFTER THIS INSPECTION IS APPROVED
U -UTILITY RESIDENTIAL FINAL 12/17/2024 APPROVED - AS NOTED LFITZGERALD
Note: *** NOTES ADDED BY LFITZGERALD 12/17/2024 11:52:11 AM *** re-align(turn sideways) the check valve in water metrr pit so can access pet cock screws/lower sewer clean out at tap so flush with sod Inspector Notes from Inspection 9035 *** NOTES ADDED BY LFITZGERALD 10/23/2024 12:13:26 PM *** no irrigation-no cross connection
ROW- FINAL SURVEY/GRADING CERTIFICATION 12/12/2024 APPROVED TPOLACEK
ROW FIELD SURVEY /GRADING CERTIFICATION 12/12/2024 APPROVED TPOLACEK
Note: UPON WALKING PROPERTY DRAINAGE WILL WORK AS INDICATED ON FINAL SURVEY. AT THE OF THE INSPECTION, ALL MINIMUM CITY REQUIREMENTS WERE MET. IT IS THE BUILDER'S RESPONSIBILITY TO ENSURE THAT NOTHING CHANGES AFTER THIS INSPECTION IS APPROVED.
ELECTRIC - EARLY POWER 11/21/2024 APPROVED - AS NOTED MKRASKI
Note: Emailed FPL @ 1:30am
ELECTRIC - EARLY POWER 11/20/2024 Disapproved -FEE REQUIRED MKRASKI
Note: Door locked need access for inspection FBC[A] 110.5
SEWER TIE IN 10/23/2024 APPROVED MGIBSON
Note: New inspection due to canceled inspection 5/9/2024 - PREVIOUS INSPECTION NOTES pep tqnk area
GRAVITY SEWER TEST 10/23/2024 APPROVED MGIBSON
Note: New inspection due to canceled inspection 5/9/2024 - PREVIOUS INSPECTION NOTES sewer not ran
U-CROSS CONNECTION 10/23/2024 APPROVED - AS NOTED LFITZGERALD
Note: *** NOTES ADDED BY LFITZGERALD 10/23/2024 12:13:26 PM *** no irrigation-no cross connection
ROW- PRE-APRON (PRE-POUR) 10/03/2024 APPROVED TPOLACEK
Note: AT THE TIME OF THE INSPECTION CULVERT PIPE IS GOOD IS READY TO POUR, IF RAIN PLEASE, BUILDER SHOULD DOUBLE CHECK CULVERT ELEVATIONS MAKE SURE IS 3000 PSI CONCRETE REINFORCED WITH WWF 6X6.W1.4 MESH OR FIBERGLASS REINFORCED CONCRETE (FRC) DRAWING 300,E RESIDENTIAL CULVERT DETAIL BEFORE POURING. TICKET OF CONCRETE MIX DESIGN SHALL BE UPLOADED INTO PERMIT PORTAL. 8.a. IF FIBERGLASS OPTION IS USED, DOCUMENTATION OF THE ( FRC) CONTAINING THE FIBERGLASS MUST BE ATTACHED TO THE PERMIT PRIOR TO REQUESTING AN AFTER-POUR INSPECTION. 8.b. IF MESH OPTION IS USED, IT SHALL BE IN PLACE AT THE TIME OF THE PRE-POUR 10/1/2024 - PREVIOUS INSPECTION NOTES 10/01/24 TPOLACEK** RECEIVED TEXT FROM FRED ASKING TO CANCEL INSPECTION FOR TODAY.
ROW- PRE-APRON (PRE-POUR) 10/01/2024 CANCELLED BY APPLICANT TPOLACEK
Note: 10/01/24 TPOLACEK** RECEIVED TEXT FROM FRED ASKING TO CANCEL INSPECTION FOR TODAY.
GRAVITY SEWER TEST 08/30/2024 CANCELLED BY APPLICANT WEB
Note: 5/9/2024 - PREVIOUS INSPECTION NOTES sewer not ran
SEWER TIE IN 08/30/2024 CANCELLED BY APPLICANT WEB
Note: 5/9/2024 - PREVIOUS INSPECTION NOTES pep tqnk area
ELECTRIC-TUG 08/29/2024 APPROVED AGAETANO
Note: 7/18/2024 - PREVIOUS INSPECTION NOTES 7-18-24 1. Protection pipe for SER is not glued.
PEP TANK INSTALLATION REQUEST 07/26/2024 APPROVED CBOWERMASTER
INSULATION 07/18/2024 APPROVED BTAYLOR
Note: Inspector Notes from Inspection 2420 7/12/24: Approved as noted to keep project moving. ALL MUST BE COMPLETE PRIOR TO NEXT INSPECTION. Check at next inspection. 1). Bedroom 3 window is missing an anchor left side bottom.
ELECTRIC-TUG 07/18/2024 Disapproved - NO FEE BTAYLOR
Note: 7-18-24 1. Protection pipe for SER is not glued.
ALL ROUGH 07/12/2024 APPROVED - AS NOTED RSIMS
Note: 7/12/24: Approved as noted to keep project moving. ALL MUST BE COMPLETE PRIOR TO NEXT INSPECTION. Check at next inspection. 1). Bedroom 3 window is missing an anchor left side bottom.
LATH/BRICK/ WATER BARRIER 07/10/2024 APPROVED FWILLIS
Note: Inspector Notes from Inspection 2467 Inspector Notes from Inspection 2460 1. Leger detail on A-5 requires (2) 2x8 legger boards (bedroom) Check on next inspection 06-24-2024 Above issue has not been resolved. Ledger detail on A-5 requires (2) 2x8 ledger boards and 1/2" CDX plywood. Installper plans or submit a revision to the building department and have on site. Check at next inspection. 1/2" CDX not installed.
ROOF VALLEY & METAL 06/24/2024 APPROVED - AS NOTED AGAETANO
Note: Inspector Notes from Inspection 2460 1. Leger detail on A-5 requires (2) 2x8 legger boards (bedroom) Check on next inspection 06-24-2024 Above issue has not been resolved. Ledger detail on A-5 requires (2) 2x8 ledger boards and 1/2" CDX plywood. Installper plans or submit a revision to the building department and have on site. Check at next inspection. 1/2" CDX not installed.
ROOF SHEATHING / BRACES/TIES/DOWN CELL 06/20/2024 APPROVED - AS NOTED MKRASKI
Note: 1. Leger detail on A-5 requires (2) 2x8 legger boards (bedroom) Check on next inspection
WALL SHEATHING 06/13/2024 APPROVED MKRASKI
ROOF SHEATHING / BRACES/TIES/DOWN CELL 06/13/2024 Disapproved - NO FEE MKRASKI
Note: 1. Leger detail on A-5 requires (2) 2x8 legger boards (bedroom) 2. Leger board missing anchors per detail on A-5 (bedroom) 3. Lead bearing openings require CS-16 42'' long Roof sheathing good to dry in
TIE BEAM / LINTEL 05/31/2024 APPROVED MKRASKI
FOUND SURVEY APPROVED (OFFICE) 05/31/2024 APPROVED AMOBLEY
TIE BEAM / LINTEL 05/29/2024 Disapproved - NO FEE MKRASKI
Note: Window sill bed joints exceed 3/8''Per FBC 606.3. Check all marked on print
MONOLITHIC SLAB 05/16/2024 APPROVED MKRASKI
PLUMBING 1ST ROUGH UNDERGROUND 05/09/2024 APPROVED MGIBSON
GRAVITY SEWER TEST 05/09/2024 Disapproved - NO FEE MGIBSON
Note: sewer not ran
SEWER TIE IN 05/09/2024 Disapproved - NO FEE MGIBSON
Note: pep tqnk area
GEOTECHNICAL REPORT APPROVAL (OFFICE USE) 05/08/2024 APPROVED JMUNSON
WATER METER INSTALLATION REQUEST 04/30/2024 APPROVED CBOWERMASTER

Review History

Department Status Date In Date Out
ENGIN1 COMPLETE 05/30/2024 05/31/2024
Note: Released By: TIM BAKER - (386)986-4726 - TBAKER@PALMCOASTGOV.COM
ZON COMPLETE 05/30/2024 05/31/2024
Note: Released By: ALISHA MOBLEY - (386)986-3751 - AMOBLEY@PALMCOASTGOV.COM
BLD COMPLETE 05/07/2024 05/08/2024
Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM
BLD HOLD 05/02/2024 05/06/2024
Note: Held By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM Letter must be accompanied by a signed and sealed inspection and certification letter by the geotechnical engineer of record. Engineer’s letter to confirm the following: Site clearing / over excavation was completed and inspected by engineer prior to the placement of fill and engineer confirms clearing and over excavation work is acceptable. Engineer to confirm fill materials were suitable and within specifications. Engineer to confirm the required number and location of field density tests were completed. Engineer to include certification statement in accordance with Florida Administrative Code 61G15-18.011 (4) Field dentisty Test Must be digiutally signed and sealed.
SW1 COMPLETE 04/24/2024 04/24/2024
Note: Released By: TIM BAKER - (386)986-4726 - TBAKER@PALMCOASTGOV.COM
ZON COMPLETE 04/24/2024 04/24/2024
Note: Released By: ALISHA MOBLEY - (386)986-3751 - AMOBLEY@PALMCOASTGOV.COM
ENGIN1 COMPLETE 04/24/2024 04/24/2024
Note: Released By: TIM BAKER - (386)986-4726 - TBAKER@PALMCOASTGOV.COM
BLD COMPLETE 04/09/2024 04/14/2024
Note: Released By: JIM WALKER - (386)529-4112 - JWALKER@PALMCOASTGOV.COM
ELEC COMPLETE 04/09/2024 04/15/2024
Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM
ZON COMPLETE 03/28/2024 03/28/2024
Note: Released By: CINDY CHIRI-GONCALVES - (386)986-4737 - CGONCALVES@PALMCOASTGOV.COM
ZON HOLD 03/25/2024 03/25/2024
Note: Held By: CINDY CHIRI-GONCALVES - (386)986-4737 - CGONCALVES@PALMCOASTGOV.COM No landscape submitted to address the comment Held By: MICHELLE RAMOS - (386)986-3780 - MRAMOS@PALMCOASTGOV.COM Repeat comment. Landscape plan missing trees. One tree for every 2500 square feet.
BLD COMPLETE 03/25/2024 03/27/2024
Note: Released By: JPI
ELEC COMPLETE 03/25/2024 03/26/2024
Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM
ZON HOLD 03/18/2024 03/18/2024
Note: Held By: MICHELLE RAMOS - (386)986-3780 - MRAMOS@PALMCOASTGOV.COM Repeat comment. Landscape plan missing trees. One tree for every 2500 square feet.
SWALE COMPLETE 03/18/2024 05/22/2024
Note: Released By: TIM BAKER - (386)986-4726 - TBAKER@PALMCOASTGOV.COM
BADMIN COMPLETE 03/15/2024 03/21/2024
Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM
BLD HOLD 03/15/2024 03/19/2024
Note: Held By: JPI 1. Per City Truss Submittal Requirements dated April 15, 2023, provide the truss plan packet signed and sealed by a licensed design professional including a completed shop drawing approval stamp on the truss cover sheet.
CUSVC COMPLETE 03/15/2024 03/18/2024
Note: Released By: CYNTHIA SCHWEERS - - CSCHWEERS@PALMCOASSTGOV.COM
ELEC HOLD 03/15/2024 03/21/2024
Note: Held By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM Electrical riser diagram needs to include the surge protector. NEC 2020 230.67
ENGIN1 COMPLETE 03/15/2024 03/18/2024
Note: Released By: TIM BAKER - (386)986-4726 - TBAKER@PALMCOASTGOV.COM
GAS CANCEL 03/15/2024 03/20/2024
LOCATE COMPLETE 03/15/2024 03/19/2024
Note: Released By: CANDACE BOWERMASTER - - CBOWERMASTER@PALMCOASTGOV.COM
MECH COMPLETE 03/15/2024 03/20/2024
Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM
SW1 COMPLETE 03/15/2024 03/18/2024
Note: Released By: TIM BAKER - (386)986-4726 - TBAKER@PALMCOASTGOV.COM
ZON HOLD 03/15/2024 03/15/2024
Note: Held By: MICHELLE RAMOS - (386)986-3780 - MRAMOS@PALMCOASTGOV.COM Landscape plan missing trees. One tree for every 2500 square feet

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
REINSPECTION RESIDENTIAL ¤40.00 09/05/2025
CONNECTION FEES ¤1,187.26 04/01/2024
FC IMPACT FEE EMS ¤62.00 04/01/2024
IMPACT FEE FIRE ¤428.09 04/01/2024
FC IMPACT FEE LAW ENFORCEMENT ¤218.00 04/01/2024
FC IMPACT FEE LIBRARY ¤268.00 04/01/2024
IMPACT FEE PARKS ¤1,800.99 04/01/2024
IMPACT FEE SCHOOL ¤5,450.00 04/01/2024
IMPACT FEE TRANSPORTATION ¤1,862.00 04/01/2024
WATER -IRRIGATION INSPECTION ¤25.00 04/01/2024
SURCHARGE FS 533.721 ¤6.19 04/01/2024
SURCHARGE - FS 468.631 ¤9.28 04/01/2024
SW ENG - FOUNDATION SURVEY ¤20.00 04/01/2024
SW ENG INSPECTION 80 ¤80.00 04/01/2024
SW ENG PRE APRON ¤30.00 04/01/2024
SW ENG - REVIEW 20 ¤20.00 04/01/2024
SW ENG RES REVIEW 200 ¤200.00 04/01/2024
SEWER CREDIT (¤1,466.00) 04/01/2024
SEWER INSPECTION ¤25.00 04/01/2024
SEWER CAPITAL FACILITY ¤5,441.03 04/01/2024
WATER CAPITAL FACILITY FEE ¤3,994.51 04/01/2024
SITE PLAN 30 ¤30.00 04/01/2024
WATER- TURN ON ¤25.00 04/01/2024
ADJUSTMENT 50% (¤618.63) 04/01/2024
ADMINISTRATIVE RESIDENTIAL ¤30.00 04/01/2024
INSPECTION - RESIDENTIAL ¤940.50 04/01/2024
PLAN REVIEW - RESIDENTIAL ¤266.76 04/01/2024
Fees Total Due: ¤0.00 Total Paid: ¤20,374.98