I want to search for...
Permit #2024030906
Permit Details
Status: FINAL
| Parcel Id: 07-11-31-7026-00640-0300 |
| Block: 00640 |
| Subdivision: 7026 - |
| Job Phone: 904-610-4499 |
| Location Address: 21 PINELL LN |
| Type: GEN - GENERATOR |
| Issue Date: 04/08/2024 |
| NOC: RECORDED |
| Applicant name: ANTHONY MODESTO SCHREIBER |
| Owner: KUGELMANN DEBORAH |
|
Address 21 PINELL LANE PALM COAST, FL 32164 |
| Lot: 0300 |
| Contracted Stated Job Value: ¤18,619.00 |
| Job Description: GENERATOR AND 250 GALLON UG LP TANK |
| Type: CN |
Contractor
AA SERVICE AND REPAIR NORTH FLORIDA AC
| Status | Location Address | State License Number | Phone | Fax |
| INACTIVE |
PO BOX 57896 JACKSONVILLE, FL 32258 |
CMC1249701 (Exp: 08/31/2026) | 904-610-4499 | 904-288-8164 |
Sub Contractors
ANTHONY MODESTO SCHREIBER
| Status | Location Address | State License Number | Phone | Fax |
| ACTIVE |
PO BOX 57896 JACKSONVILLE, FL 32258 |
CFC1427665 (Exp: 08/31/2026) | 904-626-8199 | 904-288-8164 |
Inspection History
| Type | Request Date | Result | Inspector |
| ELECTRIC FINAL | 04/17/2024 | FINAL APPROVED | RSIMS |
| GAS FINAL | 04/17/2024 | FINAL APPROVED | RSIMS |
| Note: Inspector Notes from Inspection 2225 4/11/2024 - PREVIOUS INSPECTION NOTES. REPAIR DANAGED LINE AT TANK BEFORE GAS FINAL INSPECTION. GAS LINE IS KINKED NEAR GAS GUAGE Inspector Notes from Inspection 2225 4/11/2024 - PREVIOUS INSPECTION NOTES. REPAIR DANAGED LINE AT TANK BEFORE GAS FINAL INSPECTION. GAS LINE IS KINKED NEAR GAS GUAGE | |||
| GAS ROUGH | 04/15/2024 | APPROVED - AS NOTED | MGIBSON |
| Note: 4/11/2024 - PREVIOUS INSPECTION NOTES. REPAIR DANAGED LINE AT TANK BEFORE GAS FINAL INSPECTION. GAS LINE IS KINKED NEAR GAS GUAGE | |||
| GAS ROUGH | 04/11/2024 | CANCELLED BY APPLICANT | MGIBSON |
Review History
| Department | Status | Date In | Date Out |
| ZON | COMPLETE | 04/11/2024 | 04/11/2024 |
| Note: Released By: ALISHA MOBLEY - (386)986-3751 - AMOBLEY@PALMCOASTGOV.COM | |||
| GAS | COMPLETE | 04/05/2024 | 04/08/2024 |
| Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM | |||
| ZON | COMPLETE | 04/05/2024 | 04/05/2024 |
| Note: Released By: ALISHA MOBLEY - (386)986-3751 - AMOBLEY@PALMCOASTGOV.COM | |||
| GAS | HOLD | 04/02/2024 | 04/05/2024 |
| Note: Held By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM Show 10Ft minimum generator exhaust from any opening into the building per FBC Residential 2023 8Th edition M1905.2.5. If using the exception, show note for 5 foot and a carbon monoxides. Carbon monoxide detectors will be inspected on generator final. (Third Request) | |||
| ZON | COMPLETE | 04/02/2024 | 04/02/2024 |
| Note: Released By: TRACEY DOAK - (386)986-3751 - TDOAK@PALMCOASTGOV.COM | |||
| BADMIN | INFORMATION | 04/02/2024 | 04/02/2024 |
| Note: Marked INFORMATION By: SCOTT THOMAS - (386)986-3780 - STHOMAS@PALMCOASTGOV.COM 1. RENAME TO SITE PLAN.PDF, MANU SPECS.PDF | |||
| ELEC | COMPLETE | 03/26/2024 | 04/01/2024 |
| Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM | |||
| GAS | HOLD | 03/26/2024 | 03/26/2024 |
| Note: Held By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM Show 10Ft minimum generator exhaust from any opening into the building per FBC Residential 2023 8Th edition M1905.2.5. If using the exception, show note for 5 foot and a carbon monoxides. Carbon monoxide detectors will be inspected on generator final. (Second Request) | |||
| ZON | HOLD | 03/26/2024 | 03/26/2024 |
| Note: Held By: CINDY CHIRI-GONCALVES - (386)986-4737 - CGONCALVES@PALMCOASTGOV.COM repeat comment Please submit a readable site plan as all setbacks are legible please know that the tanks can not be in the easement. | |||
| ELEC | HOLD | 03/20/2024 | 03/25/2024 |
| Note: Held By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM 1. Need to show wire sizes. | |||
| ZON | HOLD | 03/20/2024 | 03/21/2024 |
| Note: Held By: CINDY CHIRI-GONCALVES - (386)986-4737 - CGONCALVES@PALMCOASTGOV.COM Please submit a readable site plan as all setbacks are legible please know that the tanks can not be in the easement. | |||
| GAS | HOLD | 03/20/2024 | 03/25/2024 |
| Note: Held By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM Show 10Ft minimum generator exhaust from any opening into the building per FBC Residential 2023 8Th edition M1905.2.5. If using the exception, show note for 5 foot and a carbon monoxides. Carbon monoxide detectors will be inspected on generator final. |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| ADJUSTMENT 50% | (¤61.25) | 04/08/2024 |
| ADMINISTRATIVE RESIDENTIAL | ¤30.00 | 04/08/2024 |
| INSPECTION - RESIDENTIAL | ¤60.00 | 04/08/2024 |
| PLAN REVIEW - MISC 32.50 | ¤32.50 | 04/08/2024 |
| SURCHARGE FS 533.721 | ¤2.00 | 04/08/2024 |
| SURCHARGE - FS 468.631 | ¤2.00 | 04/08/2024 |
| SITE PLAN 15 | ¤15.00 | 04/08/2024 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤80.25 |