I want to search for...

Permit #2024031123

Permit Details

Status: FINAL

Parcel Id: 07-11-31-7032-00050-0040
Total Square Footage: 2321 sqft
Block: 00050
Subdivision: 7032 -
Job Phone: 904-200-1339
Location Address: 39 ROUND THORN DR
Type: FS - FIRE SPRINKLER WET COMMERCIAL
Issue Date: 06/24/2024
NOC: RECORDED
Applicant name: JOHN CHEEK
Owner: TARIQ MUHAMMAD & CORINNE H&W

Address

60 BAY POINTE DR

ORMOND BEACH, FL 32174

Lot: 0040
Contracted Stated Job Value: ¤10,000.00
Job Description: Add new 13 R sprinkler System to existing Home
Type: CN

Contractor

PYE-BARKER FIRE & SAFETY LLC
Status Location Address State License Number Phone
ACTIVE

8936 WESTERN WAY, SUITE 5

JACKSONVILLE, FL 32256

FPC16-000111 (Exp: 06/30/2026) 904-634-7100

Inspection History

Type Request Date Result Inspector
FIRE SPRINKLER FINAL 08/01/2024 FINAL APPROVED RMARTIN
Note: 7/31/2024 - PREVIOUS INSPECTION NOTES *** NOTES ADDED BY RMARTIN 7/31/2024 2:20:58 PM *** ALARM NOT WORKING WITH FLOW TEST
FIRE SPRINKLER FINAL 07/31/2024 Disapproved - NO FEE RMARTIN
Note: *** NOTES ADDED BY RMARTIN 7/31/2024 2:20:58 PM *** ALARM NOT WORKING WITH FLOW TEST
FIRE SPRINKLER 1ST ROUGH 07/30/2024 APPROVED RMARTIN
FIRE SPRINKLER HYDROSTATIC TEST 07/30/2024 APPROVED RMARTIN

Review History

Department Status Date In Date Out
BADMIN INFORMATION 06/28/2024 06/28/2024
Note: Marked INFORMATION By: SCOTT THOMAS - (386)986-3780 - STHOMAS@PALMCOASTGOV.COM 1. RENAME TO NOC.PDF 2. DO NOT SCAN DL. ONLY RECORDED NOC
BADMIN INFORMATION 06/26/2024 06/26/2024
Note: Marked INFORMATION By: NICOLE DIMATTINA - - NDIMATTINA@PALMCOASTGOV.COM The wrong owner is listed on the NOC
FI1 COMPLETE 06/13/2024 06/21/2024
Note: Released By: LEE MILLER - (386)986-3783 - WMILLER@PALMCOASTGOV.COM Held By: LEE MILLER - (386)986-3783 - WMILLER@PALMCOASTGOV.COM Please provide a written response to each comment below in a response letter and provide clouded response changes on plan sheets and add page locations for each response. All comments below per the: Per the FBC 8th edition (2023) and or the FFPC 8th edition (2023) 1. FFPC 8th edition (2023) Florida Fire Prevention Code with the Florida specific NFPA (2021) 1 and 101 to the plans for review 2. NFPA 13R, (2019) edition, Standard for the Installation of Sprinkler Systems in Low-Rise Residential Occupancies to the plans for review 3. Please provide type and location of Bell alarm per NFPA 13-R 8.1.7 (14) 4. Please provide pressure gauges with shutoff on supply and system side and show in riser diagram per NFPA 13-R 6.12.1 and 6.12.2 5. Please provide pressure gauges with shutoff on supply and system side and show in riser diagram per NFPA 13-R 6.12.1 and 6.12.2
FI1 HOLD 05/21/2024 05/30/2024
Note: Held By: LEE MILLER - (386)986-3783 - WMILLER@PALMCOASTGOV.COM Please provide a written response to each comment below in a response letter and provide clouded response changes on plan sheets and add page locations for each response. All comments below per the: Per the FBC 8th edition (2023) and or the FFPC 8th edition (2023) 1. FFPC 8th edition (2023) Florida Fire Prevention Code with the Florida specific NFPA (2021) 1 and 101 to the plans for review 2. NFPA 13R, (2019) edition, Standard for the Installation of Sprinkler Systems in Low-Rise Residential Occupancies to the plans for review 3. Please provide type and location of Bell alarm per NFPA 13-R 8.1.7 (14) 4. Please provide pressure gauges with shutoff on supply and system side and show in riser diagram per NFPA 13-R 6.12.1 and 6.12.2 5. Please provide pressure gauges with shutoff on supply and system side and show in riser diagram per NFPA 13-R 6.12.1 and 6.12.2
FI1 HOLD 05/07/2024 05/20/2024
Note: Held By: LEE MILLER - (386)986-3783 - WMILLER@PALMCOASTGOV.COM Prior remarks from fire review were not resolved still need... Please upload the required system design along with the material specs. (you did not submit any documents for the system) (There is still no floor plan or system layout)
FI1 HOLD 04/18/2024 05/01/2024
Note: Held By: LEE MILLER - (386)986-3783 - WMILLER@PALMCOASTGOV.COM Prior remarks from fire review were not resolved still need... Please upload the required system design along with the material specs. (you did not submit any documents for the system)
FI1 HOLD 03/25/2024 04/02/2024
Note: Held By: LEE MILLER - (386)986-3783 - WMILLER@PALMCOASTGOV.COM Please upload the required system design along with the material specs. (you did not submit any documents for the system)
UD1 COMPLETE 03/25/2024 03/27/2024
Note: Released By: GREG DEGLER - - GDEGLER@PALMCOASTGOV.COM

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
ADJUSTMENT 50% (¤128.00) 06/24/2024
ADMINISTRATIVE - COMMERCIAL ¤75.00 06/24/2024
INSPECTION - FIRE COMMERCIAL ¤66.00 06/24/2024
PLAN REVIEW - COMMERCIAL ¤115.00 06/24/2024
SURCHARGE FS 533.721 ¤2.00 06/24/2024
SURCHARGE - FS 468.631 ¤2.00 06/24/2024
Fees Total Due: ¤0.00 Total Paid: ¤132.00