I want to search for...
Permit #2024040603
Permit Details
Status: FINAL
| Parcel Id: 33-11-31-3065-00000-0500 |
| Block: 00000 |
| Subdivision: 3065 - |
| Job Phone: 904-610-4499 |
| Location Address: 61 GRAHAM WOODS PL |
| Type: GEN - GENERATOR |
| Issue Date: 04/30/2024 |
| NOC: RECORDED |
| Applicant name: ANTHONY MODESTO SCHREIBER |
| Owner: CROVO DANIEL AUGUSTUS & DIANE CATHERINE H&W |
|
Address PO BOX 354083 PALM COAST, FL 32135 |
| Lot: 0500 |
| Contracted Stated Job Value: ¤16,779.00 |
| Job Description: 24KW GENERATOR WITH ATS AND 2-120 AG LP TANKS |
| Type: CN |
Contractor
AA SERVICE AND REPAIR NORTH FLORIDA AC
| Status | Location Address | State License Number | Phone | Fax |
| INACTIVE |
PO BOX 57896 JACKSONVILLE, FL 32258 |
CMC1249701 (Exp: 08/31/2026) | 904-610-4499 | 904-288-8164 |
Sub Contractors
ANTHONY MODESTO SCHREIBER
| Status | Location Address | State License Number | Phone | Fax |
| ACTIVE |
PO BOX 57896 JACKSONVILLE, FL 32258 |
CFC1427665 (Exp: 08/31/2026) | 904-626-8199 | 904-288-8164 |
Inspection History
| Type | Request Date | Result | Inspector |
| ELECTRIC FINAL | 06/10/2024 | FINAL APPROVED | BTAYLOR |
| GAS FINAL | 05/29/2024 | FINAL APPROVED | MGIBSON |
| GAS ROUGH | 05/15/2024 | APPROVED | MGIBSON |
Review History
| Department | Status | Date In | Date Out |
| GAS | COMPLETE | 04/24/2024 | 04/26/2024 |
| Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM | |||
| ZON | COMPLETE | 04/22/2024 | 04/23/2024 |
| Note: Released By: ALISHA MOBLEY - (386)986-3751 - AMOBLEY@PALMCOASTGOV.COM | |||
| GAS | HOLD | 04/22/2024 | 04/23/2024 |
| Note: Held By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM 1. Provide gas riser diagram Third Request | |||
| GAS | HOLD | 04/18/2024 | 04/19/2024 |
| Note: Held By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM 1. Provide gas riser diagram 2. Provide note on plan that Generator exhaust must be minumum 10ft from any opening into the building per FBC Residential 2023 8Th edition M1905.2.5. If using the exception to 5ft, carbon monoxide detectors will be inspected on generator final. (Second Request) | |||
| ELEC | COMPLETE | 04/18/2024 | 04/22/2024 |
| Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM | |||
| ELEC | HOLD | 04/16/2024 | 04/18/2024 |
| Note: Held By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM 1. Need to show wire size going to generator. | |||
| ELEC | HOLD | 04/10/2024 | 04/15/2024 |
| Note: Held By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM 1. Submit electrical riser diagram. | |||
| ZON | HOLD | 04/10/2024 | 04/10/2024 |
| Note: Held By: ALISHA MOBLEY - (386)986-3751 - AMOBLEY@PALMCOASTGOV.COM Please use final survey to Show the location of tanks and generator with setbacks for review I am emailing you a copy of the survey | |||
| GAS | HOLD | 04/10/2024 | 04/15/2024 |
| Note: Held By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM 1. Provide gas riser diagram 2. Provide note on plan that Generator exhaust must be minumum 10ft from any opening into the building per FBC Residential 2023 8Th edition M1905.2.5. If using the exception to 5ft, carbon monoxide detectors will be inspected on generator final. |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| ADJUSTMENT 50% | (¤61.25) | 04/30/2024 |
| ADMINISTRATIVE RESIDENTIAL | ¤30.00 | 04/30/2024 |
| INSPECTION - RESIDENTIAL | ¤60.00 | 04/30/2024 |
| PLAN REVIEW - MISC 32.50 | ¤32.50 | 04/30/2024 |
| SURCHARGE FS 533.721 | ¤2.00 | 04/30/2024 |
| SURCHARGE - FS 468.631 | ¤2.00 | 04/30/2024 |
| SITE PLAN 15 | ¤15.00 | 04/30/2024 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤80.25 |