Permit #2024040762

Permit Details

Status: FINAL

Parcel Id: 07-11-31-7065-00110-0010
Block: 00110
Subdivision: 7065 -
Job Phone: 386-479-7149
Location Address: 1 KANSAS PATH
Type: EL - ELECTRICAL
Issue Date: 04/15/2024
NOC: Unknown
Applicant name: TIMOTHY RYAN GODFREY
Owner: SHAFFER MICHAEL ALEXANDER & JENNIFER DEAN H&W

Address

1 KANSAS PATH

PALM COAST, FL 32164

Lot: 0010
Contracted Stated Job Value: ¤1,550.00
Job Description: EV Charger install
Type: CN

Contractor

POWERFULL RECHARGE, LLC
Status Location Address State License Number Phone
INACTIVE

255 MARGARITAVILLE AVE

DAYTONA BEACH, FL 32124

EC13012049 (Exp: 08/31/2026) 386-479-7149

Inspection History

Type Request Date Result Inspector
ELECTRIC FINAL 05/10/2024 FINAL APPROVED RSIMS
Note: 4/26/2024 - PREVIOUS INSPECTION NOTES 4/26/24: 1). Need a revision for the plans to match the field install. Plan submitted shows 50AMP with #6AWG wire and the EVSE installed directly adjacent to the panel. Installed is 100AMP with #3AWG wire in conduit into & through the attic to the exterior location of the EVSE and a 100AMP disconnect. 2). New 2024 code requires that the breaker be GFCI type per Article 210.8 in the code changes. 3). Hole drilled through the drywall and breaker box framing at the right side will need to be sealed with the approved material per FBC-R302.11.1/ FBC 302.6. Also, cardboard at the ceiling conduit penetration will need to be removed so that proper sealing with the approved material can be confirmed. 4). Hole in the soffit above disconnect for pipe penetration needs to be sealed as required. (1203.2.1/FBCEC R402.4)
ELECTRIC FINAL 04/26/2024 Disapproved - NO FEE RSIMS
Note: 4/26/24: 1). Need a revision for the plans to match the field install. Plan submitted shows 50AMP with #6AWG wire and the EVSE installed directly adjacent to the panel. Installed is 100AMP with #3AWG wire in conduit into & through the attic to the exterior location of the EVSE and a 100AMP disconnect. 2). New 2024 code requires that the breaker be GFCI type per Article 210.8 in the code changes. 3). Hole drilled through the drywall and breaker box framing at the right side will need to be sealed with the approved material per FBC-R302.11.1/ FBC 302.6. Also, cardboard at the ceiling conduit penetration will need to be removed so that proper sealing with the approved material can be confirmed. 4). Hole in the soffit above disconnect for pipe penetration needs to be sealed as required. (1203.2.1/FBCEC R402.4)
ELECTRIC FINAL 04/16/2024 CANCELLED BY APPLICANT WEB

Review History

Department Status Date In Date Out
ELEC COMPLETE 05/02/2024 05/03/2024
Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM
ELEC COMPLETE 04/12/2024 04/15/2024
Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
ADJUSTMENT 50% (¤61.25) 04/15/2024
ADMINISTRATIVE RESIDENTIAL ¤30.00 04/15/2024
INSPECTION- ELECTRICAL ¤60.00 04/15/2024
PLAN REVIEW - MISC 32.50 ¤32.50 04/15/2024
SURCHARGE FS 533.721 ¤2.00 04/15/2024
SURCHARGE - FS 468.631 ¤2.00 04/15/2024
Fees Total Due: ¤0.00 Total Paid: ¤65.25