Permit #2024040848

Permit Details

Status: FINAL

Parcel Id: 07-11-31-7063-00030-0010
Block: 00030
Subdivision: 7063 -
Job Phone: 386-338-7335
Location Address: 32 ZOELLER CT
Type: ME - MECHANICAL
Issue Date: 04/16/2024
NOC: Unknown
Applicant name: SERGEY SERGEYEVICH KRUGLYAK
Owner: YEMELYANOV ALEXANDER M

Address

208 HOOKS MILL ROAD

AMERICUS, GA 31709

Lot: 0010
Contracted Stated Job Value: ¤4,560.00
Job Description: HVAC Like For Like Tonnage.
Type: CN

Contractor

FLAGLER AIR CONDITIONING, INC
Status Location Address State License Number Phone
ACTIVE

50 PINE CREST LN

PALM COAST, FL 32164

CAC1818004 (Exp: 08/31/2026) 386-338-7335

Inspection History

Type Request Date Result Inspector
HVAC FINAL 04/22/2024 FINAL APPROVED RSIMS
Note: 4/18/2024 - PREVIOUS INSPECTION NOTES 4/18/24: 1). All 3 locking port caps are off and laying on the AC pad. ** M1411.8 - Locking access port caps. Refrigerant circuit access ports located outdoors shall be fitted with locking-type tamper-resistant caps or shall be otherwise secured to prevent unauthorized access. Exception: No locking-type tamper-resistant caps are 2). Condensate drain needs to terminate 6" above finished grade as required. E406.1.1 Condensate drains. Condensate drains shall connect to air outside the building perimeter at a height of at least 6 inches (172 mm) above the finished grade ground level. 3). Exterior metal chase for lineset needs to be sealed at the bottom and top with the approved material as required - FBC- M1203.2.1 4). Male adapter at condensate pan is loose and pvc pipe is not glued at fittings as required.
HVAC FINAL 04/18/2024 Disapproved -FEE REQUIRED RSIMS
Note: 4/18/24: 1). All 3 locking port caps are off and laying on the AC pad. ** M1411.8 - Locking access port caps. Refrigerant circuit access ports located outdoors shall be fitted with locking-type tamper-resistant caps or shall be otherwise secured to prevent unauthorized access. Exception: No locking-type tamper-resistant caps are 2). Condensate drain needs to terminate 6" above finished grade as required. E406.1.1 Condensate drains. Condensate drains shall connect to air outside the building perimeter at a height of at least 6 inches (172 mm) above the finished grade ground level. 3). Exterior metal chase for lineset needs to be sealed at the bottom and top with the approved material as required - FBC- M1203.2.1 4). Male adapter at condensate pan is loose and pvc pipe is not glued at fittings as required.

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
REINSPECTION RESIDENTIAL ¤40.00 04/19/2024
SURCHARGE FS 533.721 ¤2.00 04/16/2024
SURCHARGE - FS 468.631 ¤2.00 04/16/2024
ADJUSTMENT 50% (¤45.00) 04/16/2024
ADMINISTRATIVE RESIDENTIAL ¤30.00 04/16/2024
INSPECTION - MECHANICAL ¤60.00 04/16/2024
Fees Total Due: ¤0.00 Total Paid: ¤89.00