Permit #2024050859

Permit Details

Status: CANCEL

Parcel Id: 48-11-31-1710-00000-0370
Block: 00000
Subdivision: 1710 -
Job Phone: 904-610-4499
Location Address: 22 SCARLET OAK CIR
Type: GEN - GENERATOR
Issue Date: 06/05/2024
NOC: RECORDED
Applicant name: ANTHONY MODESTO SCHREIBER
Owner: FRANER PAUL T & DIANNE R H&W

Address

6312 LUCENA WAY

MASON, OH 45040

Lot: 0370
Contracted Stated Job Value: ¤17,529.00
Job Description: GENERATOR WITH ATS
Type: CN

Contractor

AA SERVICE AND REPAIR NORTH FLORIDA AC
Status Location Address State License Number Phone Fax
INACTIVE

PO BOX 57896

JACKSONVILLE, FL 32258

CMC1249701 (Exp: 08/31/2026) 904-610-4499 904-288-8164

Sub Contractors

ANTHONY MODESTO SCHREIBER
Status Location Address State License Number Phone Fax
ACTIVE

PO BOX 57896

JACKSONVILLE, FL 32258

CFC1427665 (Exp: 08/31/2026) 904-626-8199 904-288-8164

Inspection History

Type Request Date Result Inspector
ELECTRIC FINAL 12/17/2024 Disapproved - NO FEE MKRASKI
Note: 12/17/24 No repairs made, not ready 8/9/2024 - PREVIOUS INSPECTION NOTES New inspection due to canceled inspection 6/27/2024 - PREVIOUS INSPECTION NOTES *** NOTES ADDED BY RMARTIN 6/27/2024 1:38:32 PM *** STARTUP WAS DONE, NEED TO RELOCATE EXHAUST/GENERATOR 10' AWAY FROM OPENING OR PROVIDE CARBON MONOXIDE DETECTOR TO AREA CLOSEST TO GENERATOR AND IN RESPECT TO M1905.2.5
ELECTRIC FINAL 08/09/2024 CANCELLED BY APPLICANT BTAYLOR
Note: New inspection due to canceled inspection 6/27/2024 - PREVIOUS INSPECTION NOTES *** NOTES ADDED BY RMARTIN 6/27/2024 1:38:32 PM *** STARTUP WAS DONE, NEED TO RELOCATE EXHAUST/GENERATOR 10' AWAY FROM OPENING OR PROVIDE CARBON MONOXIDE DETECTOR TO AREA CLOSEST TO GENERATOR AND IN RESPECT TO M1905.2.5
ELECTRIC FINAL 07/31/2024 CANCELLED BY APPLICANT WEB
Note: 6/27/2024 - PREVIOUS INSPECTION NOTES *** NOTES ADDED BY RMARTIN 6/27/2024 1:38:32 PM *** STARTUP WAS DONE, NEED TO RELOCATE EXHAUST/GENERATOR 10' AWAY FROM OPENING OR PROVIDE CARBON MONOXIDE DETECTOR TO AREA CLOSEST TO GENERATOR AND IN RESPECT TO M1905.2.5
ELECTRIC FINAL 06/27/2024 Disapproved - NO FEE RMARTIN
Note: *** NOTES ADDED BY RMARTIN 6/27/2024 1:38:32 PM *** STARTUP WAS DONE, NEED TO RELOCATE EXHAUST/GENERATOR 10' AWAY FROM OPENING OR PROVIDE CARBON MONOXIDE DETECTOR TO AREA CLOSEST TO GENERATOR AND IN RESPECT TO M1905.2.5
GAS FINAL 06/27/2024 APPROVED - AS NOTED MGIBSON
Note: GAS FINAL IS APPROVED BUT NEED TO COMPLY WITH M1905.2.5 CARBONMONOXIDE DETECTOR
GAS ROUGH 06/25/2024 APPROVED MGIBSON
ELECTRIC FINAL
Note: 12/17/2024 - PREVIOUS INSPECTION NOTES 12/17/24 No repairs made, not ready 8/9/2024 - PREVIOUS INSPECTION NOTES New inspection due to canceled inspection 6/27/2024 - PREVIOUS INSPECTION NOTES *** NOTES ADDED BY RMARTIN 6/27/2024 1:38:32 PM *** STARTUP WAS DONE, NEED TO RELOCATE EXHAUST/GENERATOR 10' AWAY FROM OPENING OR PROVIDE CARBON MONOXIDE DETECTOR TO AREA CLOSEST TO GENERATOR AND IN RESPECT TO M1905.2.5

Review History

Department Status Date In Date Out
GAS COMPLETE 05/30/2024 06/04/2024
Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM
ELEC COMPLETE 05/22/2024 05/28/2024
Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM
GAS HOLD 05/22/2024 05/24/2024
Note: Held By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM Put note on site plan. Generator exhaust must be minumum 10ft from any opening into the building per FBC Residential 2023 8Th edition M1905.2.5. If using the exception to 5ft, carbon monoxide detectors will be inspected on generator final.
BADMIN INFORMATION 05/22/2024 05/22/2024
Note: Marked INFORMATION By: CINDY CHIRI-GONCALVES - (386)986-4737 - CGONCALVES@PALMCOASTGOV.COM please specify the permit and what is being revised on the revision sheet
ELEC HOLD 05/16/2024 05/22/2024
Note: Held By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM 1. Show wire size going to the generator
ZON COMPLETE 05/16/2024 05/16/2024
Note: Released By: TRACEY DOAK - (386)986-3751 - TDOAK@PALMCOASTGOV.COM
GAS HOLD 05/16/2024 05/22/2024
Note: Held By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM Put note on site plan. Generator exhaust must be minumum 10ft from any opening into the building per FBC Residential 2023 8Th edition M1905.2.5. If using the exception to 5ft, carbon monoxide detectors will be inspected on generator final.

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
ADJUSTMENT 10% (¤12.25) 06/05/2024
ADMINISTRATIVE RESIDENTIAL ¤30.00 06/05/2024
INSPECTION - RESIDENTIAL ¤60.00 06/05/2024
PLAN REVIEW - MISC 32.50 ¤32.50 06/05/2024
SURCHARGE FS 533.721 ¤2.00 06/05/2024
SURCHARGE - FS 468.631 ¤2.00 06/05/2024
SITE PLAN 15 ¤15.00 06/05/2024
Fees Total Due: ¤0.00 Total Paid: ¤129.25