Permit #2024060106

Permit Details

Status: COED

Parcel Id: 09-12-31-0000-02030-0020
Block: 02030
Subdivision: -
Job Phone: 678-697-0613
Location Address: 1 MEMORIAL MEDICAL PKWY
Type: CIA - COMMERCIAL INTERIOR EXTERIOR ALTERATION
Issue Date: 07/01/2024
NOC: RECORDED
Applicant name: BRUCE ROBERT ADAMS
Owner: MEMORIAL HOSPITAL-FLAGLER INC

Address

60 MEMORIAL MEDICAL PKWY

PALM COAST, FL 32164

Lot: 0020
Contracted Stated Job Value: ¤300,000.00
Job Description: ADVENTHEALTH CANCER CENTER Primary Care Suite on Level 1
Type: CN

Contractor

THE ROBINS & MORTON GROUP
Status Location Address Mailing Address State License Number Phone
ACTIVE

423 S KELLER RD

ORLANDO, FL 32810

#200

ORLANDO, FL 32810

CGC1523017 (Exp: 08/31/2026) 407-916-7235

Sub Contractors

MICHAEL W CAMPBELL
Status Location Address State License Number Phone Fax
INACTIVE

1300 FT. NEGLEY BLVD

NASHVILLE, TN 37203

EC0001269 (Exp: 08/31/2026) 615-350-7270 615-350-7242
KEITH MICHAEL CAMPBELL
Status Location Address State License Number Phone Fax
ACTIVE

6225 POWERS AVE

JACKSONVILLE, FL 32217

CFC1426177 (Exp: 08/31/2026) 904-387-9996 904-387-9068
KEITH MICHAEL CAMPBELL
Status Location Address State License Number Phone Fax
ACTIVE

6225 POWERS AVE

JACKSONVILLE, FL 32217

CFC1426177 (Exp: 08/31/2026) 904-387-9996 904-387-9068

Inspection History

Type Request Date Result Inspector
PLUMBING FINAL 01/09/2025 APPROVED - AS NOTED MGIBSON
Note: Inspector Notes from Inspection 3080 10/21/2024 - PREVIOUS INSPECTION NOTES 9/30/2024 - PREVIOUS INSPECTION NOTES Inspector Notes from Inspection 3070 THIS WAS TO CLEAN UP THE PERMIT, SPOKE TO JAVIER ZAMORA 7/25/2024 - PREVIOUS INSPECTION NOTES NOTE THAT WAS APPROVED AS NOTED 7/2/24 HAS NOT BEEN COMPLETED, NO CONCRETE TO BE PLACED IN AREA THAT NEEDS REVISION CONCRETE TO BE POURED UNTIL REVISION IS APPROVED. This was for the firts rough plumbing in Southwest corner of building. Per request of Building Official Patrick Buckley and our email That we had we will allow job to proceed with the requeste ''rfi'' or revisions thst need to made at plumbing final. NEED TEST ON WASTE ANDVENT AND WATER DISTRIBUTION THIS WAS FOR INSULATION ON ALL WATER DISTRIBUTION LINES SUPPLY RETURN O RESIRC HAVE ALL ARRATORS ON BY BUILDING FINAL
HVAC FINAL 01/09/2025 FINAL APPROVED CPISCITELLI
Note: 1/6/2025 - PREVIOUS INSPECTION NOTES 1/6/25: Partial approval - waiting on submission of Balancing Report. Also, Staff Restroom C117 does not have a supply register/feed. Only exhaust. PM stated he would check with the Architectural Engineer to see if it is required. Everything else is approved.
BUILDING FINAL 01/09/2025 FINAL APPROVED FWILLIS
Note: PRIME CARE 1ST FLOOR. Inspector Notes from Inspection 3470 *** NOTES ADDED BY RMARTIN 12/18/2024 10:42:24 AM *** M.E.P met on site 12/16/2024 - PREVIOUS INSPECTION NOTES *** NOTES ADDED BY RMARTIN 12/16/2024 9:09:24 PM *** exterior exam rooms, need to leave a tile out in every room to re-check hvac and fire alarm
FIRE FINAL 01/08/2025 APPROVED RMARTIN
U - UTILITY COMMERCIAL FINAL 01/08/2025 FINAL APPROVED LFITZGERALD
ELECTRIC FINAL 01/08/2025 APPROVED RMARTIN
HVAC FINAL 01/06/2025 PARTIALLY APPROVED RSIMS
Note: *** NOTES ADDED BY RSIMS 1/6/2025 10:25:12 AM *** 1/6/25: Partial approval - waiting on submission of Balancing Report. Also, Staff Restroom C117 does not have a supply register/feed. Only exhaust. PM stated he would check with the Architectural Engineer to see if it is required. Everything else is approved.
PLUMBING 2ND ROUGH 01/06/2025 APPROVED - AS NOTED MGIBSON
Note: 10/21/2024 - PREVIOUS INSPECTION NOTES 9/30/2024 - PREVIOUS INSPECTION NOTES Inspector Notes from Inspection 3070 THIS WAS TO CLEAN UP THE PERMIT, SPOKE TO JAVIER ZAMORA 7/25/2024 - PREVIOUS INSPECTION NOTES NOTE THAT WAS APPROVED AS NOTED 7/2/24 HAS NOT BEEN COMPLETED, NO CONCRETE TO BE PLACED IN AREA THAT NEEDS REVISION CONCRETE TO BE POURED UNTIL REVISION IS APPROVED. This was for the firts rough plumbing in Southwest corner of building. Per request of Building Official Patrick Buckley and our email That we had we will allow job to proceed with the requeste ''rfi'' or revisions thst need to made at plumbing final. NEED TEST ON WASTE ANDVENT AND WATER DISTRIBUTION THIS WAS FOR INSULATION ON ALL WATER DISTRIBUTION LINES SUPPLY RETURN O RESIRC
HVAC ROUGH 12/18/2024 APPROVED CPISCITELLI
Note: 10/21/2024 - PREVIOUS INSPECTION NOTES Inspected seams to be able to wrap. Missing exhaust duct in bathrooms
ABOVE CEILING 12/18/2024 APPROVED - AS NOTED RMARTIN
Note: *** NOTES ADDED BY RMARTIN 12/18/2024 10:42:24 AM *** M.E.P met on site 12/16/2024 - PREVIOUS INSPECTION NOTES *** NOTES ADDED BY RMARTIN 12/16/2024 9:09:24 PM *** exterior exam rooms, need to leave a tile out in every room to re-check hvac and fire alarm
ABOVE CEILING 12/16/2024 PARTIALLY APPROVED RMARTIN
Note: *** NOTES ADDED BY RMARTIN 12/16/2024 9:09:24 PM *** exterior exam rooms, need to leave a tile out in every room to re-check hvac and fire alarm
HVAC ROUGH 10/21/2024 PARTIALLY APPROVED CPISCITELLI
Note: Inspected seams to be able to wrap. Missing exhaust duct in bathrooms
PLUMBING 2ND ROUGH 10/21/2024 PARTIALLY APPROVED MGIBSON
Note: 9/30/2024 - PREVIOUS INSPECTION NOTES Inspector Notes from Inspection 3070 7/25/2024 - PREVIOUS INSPECTION NOTES NOTE THAT WAS APPROVED AS NOTED 7/2/24 HAS NOT BEEN COMPLETED, NO CONCRETE TO BE PLACED IN AREA THAT NEEDS REVISION CONCRETE TO BE POURED UNTIL REVISION IS APPROVED. This was for the firts rough plumbing in Southwest corner of building. Per request of Building Official Patrick Buckley and our email That we had we will allow job to proceed with the requeste ''rfi'' or revisions thst need to made at plumbing final. NEED TEST ON WASTE ANDVENT AND WATER DISTRIBUTION THIS WAS FOR INSULATION ON ALL WATER DISTRIBUTION LINES SUPPLY RETURN O RESIRC
PLUMBING PRESSURE TEST 10/14/2024 APPROVED MGIBSON
Note: 10/4/2024 - PREVIOUS INSPECTION NOTES WASTE AND VENT ONLY, WATER DISTRIBUTION LINES NOT TESTED YET
PLUMBING PRESSURE TEST 10/04/2024 PARTIALLY APPROVED MGIBSON
Note: WASTE AND VENT ONLY, WATER DISTRIBUTION LINES NOT TESTED YET
ELECTRIC 2ND ROUGH 10/01/2024 APPROVED RMARTIN
PLUMBING 2ND ROUGH 09/30/2024 PARTIALLY APPROVED MGIBSON
Note: Inspector Notes from Inspection 3070 7/25/2024 - PREVIOUS INSPECTION NOTES NOTE THAT WAS APPROVED AS NOTED 7/2/24 HAS NOT BEEN COMPLETED, NO CONCRETE TO BE PLACED IN AREA THAT NEEDS REVISION CONCRETE TO BE POURED UNTIL REVISION IS APPROVED. This was for the firts rough plumbing in Southwest corner of building. Per request of Building Official Patrick Buckley and our email That we had we will allow job to proceed with the requeste ''rfi'' or revisions thst need to made at plumbing final. NEED TEST ON WASTE ANDVENT AND WATER DISTRIBUTION
INSULATION 09/13/2024 APPROVED FWILLIS
Note: TOPS ONLY
FRAMING 09/06/2024 APPROVED FWILLIS
PLUMBING 1ST ROUGH 07/31/2024 APPROVED - AS NOTED MGIBSON
Note: 7/25/2024 - PREVIOUS INSPECTION NOTES NOTE THAT WAS APPROVED AS NOTED 7/2/24 HAS NOT BEEN COMPLETED, NO CONCRETE TO BE PLACED IN AREA THAT NEEDS REVISION CONCRETE TO BE POURED UNTIL REVISION IS APPROVED. This was for the firts rough plumbing in Southwest corner of building. Per request of Building Official Patrick Buckley and our email That we had we will allow job to proceed with the requeste ''rfi'' or revisions thst need to made at plumbing final
MONOLITHIC SLAB 07/31/2024 APPROVED LMILLER
Note: *** NOTES ADDED BY LMILLER 7/31/2024 3:50:53 PM *** Mono slab in southwest corner of first floor matches the un-approved RFI that was shown to me durring the inspection. The RFI must be approved prior to the finalinspecction 7/25/2024 - PREVIOUS INSPECTION NOTES *** NOTES ADDED BY LMILLER 7/25/2024 2:42:27 PM *** Notes said this was for south east corner however, the work was in the southwest corner. also there are no details for the method of repairs on site or in the system. Need Revision for detail for Mono Slab Repair on site for inspection. FBC 107
MONOLITHIC SLAB 07/25/2024 Disapproved - NO FEE LMILLER
Note: *** NOTES ADDED BY LMILLER 7/25/2024 2:42:27 PM *** Notes said this was for south east corner however, the work was in the southwest corner. also there are no details for the method of repairs on site or in the system. Need Revision for detail for Mono Slab Repair on site for inspection. FBC 107
PLUMBING 1ST ROUGH 07/25/2024 Disapproved - NO FEE MGIBSON
Note: NOTE THAT WAS APPROVED AS NOTED 7/2/24 HAS NOT BEEN COMPLETED, NO CONCRETE TO BE PLACED IN AREA THAT NEEDS REVISION CONCRETE TO BE POURED UNTIL REVISION IS APPROVED

Review History

Department Status Date In Date Out
BLD COMPLETE 06/04/2024 06/17/2024
Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM
DSD COMPLETE 06/04/2024 06/10/2024
Note: Released By: JACQUELINE GONZALEZ - (386)986-3751 - JGONZALEZ@PALMCOASTGOV.COM
ELEC COMPLETE 06/04/2024 06/17/2024
Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM
FI1 COMPLETE 06/04/2024 06/17/2024
Note: Released By: LEE MILLER - (386)986-3783 - WMILLER@PALMCOASTGOV.COM
MECH COMPLETE 06/04/2024 06/17/2024
Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM
PLUM COMPLETE 06/04/2024 06/18/2024
Note: Released By: PATRICK BUCKLEY - (386)986-3786 - PBUCKLEY@PALMCOASTGOV.COM
UD1 COMPLETE 06/04/2024 06/06/2024
Note: Released By: GREG DEGLER - (386)986-2384 - GDEGLER@PALMCOASTGOV.COM

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
ADJUSTMENT 10% (¤252.00) 07/01/2024
ADMINISTRATIVE - COMMERCIAL ¤75.00 07/01/2024
INSPECTION COMMERCIAL ¤2,100.00 07/01/2024
PLAN REVIEW - COMMERCIAL ¤345.00 07/01/2024
SURCHARGE FS 533.721 ¤22.68 07/01/2024
SURCHARGE - FS 468.631 ¤34.02 07/01/2024
SITE PLAN 30 ¤30.00 07/01/2024
Fees Total Due: ¤0.00 Total Paid: ¤2,354.70