Permit Details
Status: FINAL
| Parcel Id: 08-12-31-5835-00000-0020 |
| Block: 00000 |
| Subdivision: 2323 - WILTON AT PAL M COAST |
| Job Phone: 386-322-8700 |
| Location Address: 700 LINWOOD ROW |
| Type: FU - FIRE UNDERGROUND |
| Issue Date: 08/30/2024 |
| NOC: RECORDED |
| Applicant name: CHAD HAZEN |
| Owner: WILTON RESIDENCES LLC |
|
Address 500 OFFICE PARK DRIVE STE 215 BRIMINGHAM, AL 35223 |
| Lot: 0020 |
| Contracted Stated Job Value: ¤40,485.00 |
| Job Description: BLDG 9 - UNDERGROUND FIRE MAIN FROM POINT OF SERVICE TO 1' ABOVE FINISH FLOOR |
| Type: CN |
| Original Permit #: 2023090399 |
Contractor
HAZEN CONSTRUCTION, LLC
| Status | Location Address | State License Number | Phone | Fax |
| ACTIVE |
1599 TIONIA RD NEW SMYRNA BEACH, FL 32168 |
98771000012007 (Exp: 06/30/2026) | 386-322-8700 | 386-756-0000 |
Inspection History
| Type | Request Date | Result | Inspector |
| FIRE FINAL | 01/16/2025 | FINAL APPROVED | LMILLER |
| Note: 3/1/2024 - PREVIOUS INSPECTION NOTES ALL GRADING AND SOD NEEDS TO BE INSTALLED BEFORE FINAL IS SCHEDULED, NEED ALL CAPS AND SIGNAGE ON FDC'S, NEED TO CHECK ALL HIGHTS AS WELL | |||
| FIRE FINAL | 03/01/2024 | Disapproved - NO FEE | RMARTIN |
| Note: ALL GRADING AND SOD NEEDS TO BE INSTALLED BEFORE FINAL IS SCHEDULED, NEED ALL CAPS AND SIGNAGE ON FDC'S, NEED TO CHECK ALL HIGHTS AS WELL | |||
| FIRE SYSTEM FLUSH | 11/22/2023 | APPROVED | RMARTIN |
| FIRE MAIN HYDROSTATIC/BACKFLOW PREVENTOR | 10/24/2023 | APPROVED | RMARTIN |
| FIRE MAIN PLACEMENT /SIZE/THRUST /BLOCKING | 09/29/2023 | APPROVED | JMUNSON |
| Note: 9/27/2023 - PREVIOUS INSPECTION NOTES 9/26/2023 - PREVIOUS INSPECTION NOTES 9-26-2`3 1. Still working to uncover the connections and hardware, still under water and soil. Need to expose for inspection (please be sure the hardware is sufficiently uncovered and cleaned off such that inspection of all threads bolts, bolts, nuts, washers, clamps, and other restraining devices can be inspected for proper coverage of acceptable corrosion-retardant material. NFPA 24 (2016) 10.6.2.5 2. The connections at the zurn riser are not installed per manufacturer specifications (The ears are not to be used as perminant restraint). 9/22/2023 - PREVIOUS INSPECTION NOTES 9-22-23 Work was covered prior to inspection. Need to uncover all connections for inspection. (Need to be able to inspection all connections and hardware). 9/21/2023 - PREVIOUS INSPECTION NOTES | |||
| FIRE MAIN PLACEMENT /SIZE/THRUST /BLOCKING | 09/27/2023 | CANCELLED BY APPLICANT | RMARTIN |
| Note: 9/26/2023 - PREVIOUS INSPECTION NOTES 9-26-2`3 1. Still working to uncover the connections and hardware, still under water and soil. Need to expose for inspection (please be sure the hardware is sufficiently uncovered and cleaned off such that inspection of all threads bolts, bolts, nuts, washers, clamps, and other restraining devices can be inspected for proper coverage of acceptable corrosion-retardant material. NFPA 24 (2016) 10.6.2.5 2. The connections at the zurn riser are not installed per manufacturer specifications (The ears are not to be used as perminant restraint). 9/22/2023 - PREVIOUS INSPECTION NOTES 9-22-23 Work was covered prior to inspection. Need to uncover all connections for inspection. (Need to be able to inspection all connections and hardware). 9/21/2023 - PREVIOUS INSPECTION NOTES | |||
| FIRE MAIN PLACEMENT /SIZE/THRUST /BLOCKING | 09/26/2023 | Disapproved - NO FEE | LMILLER |
| Note: 9-26-2`3 1. Still working to uncover the connections and hardware, still under water and soil. Need to expose for inspection (please be sure the hardware is sufficiently uncovered and cleaned off such that inspection of all threads bolts, bolts, nuts, washers, clamps, and other restraining devices can be inspected for proper coverage of acceptable corrosion-retardant material. NFPA 24 (2016) 10.6.2.5 2. The connections at the zurn riser are not installed per manufacturer specifications (The ears are not to be used as perminant restraint). 9/22/2023 - PREVIOUS INSPECTION NOTES 9-22-23 Work was covered prior to inspection. Need to uncover all connections for inspection. (Need to be able to inspection all connections and hardware). 9/21/2023 - PREVIOUS INSPECTION NOTES | |||
| FIRE MAIN PLACEMENT /SIZE/THRUST /BLOCKING | 09/22/2023 | Disapproved -FEE REQUIRED | LMILLER |
| Note: 9-22-23 Work was covered prior to inspection. Need to uncover all connections for inspection. (Need to be able to inspection all connections and hardware). 9/21/2023 - PREVIOUS INSPECTION NOTES | |||
| FIRE MAIN PLACEMENT /SIZE/THRUST /BLOCKING | 09/21/2023 | CANCELLED BY APPLICANT | RMARTIN |
Review History
| Department | Status | Date In | Date Out |
| FI1 | COMPLETE | 09/20/2023 | 09/20/2023 |
| Note: Released By: LEE MILLER - (386)986-3783 - WMILLER@PALMCOASTGOV.COM | |||
| FI1 | COMPLETE | 09/11/2023 | 09/19/2023 |
| Note: Released By: LEE MILLER - (386)986-3783 - WMILLER@PALMCOASTGOV.COM | |||
| SW1 | COMPLETE | 09/11/2023 | 09/15/2023 |
| Note: Released By: ROBERT GROSS - (386)986-4769 - RGROSS@PALMCOASTGOV.COM | |||
| UD1 | COMPLETE | 09/11/2023 | 09/12/2023 |
| Note: Released By: BRICE WRIGHT - (386)986-2398 - BWRIGHT@PALMCOASTGOV.COM |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| ADJUSTMENT 10% | (¤15.96) | 08/30/2024 |
| ADMINISTRATIVE - COMMERCIAL | ¤75.00 | 08/30/2024 |
| INSPECTION - FIRE COMMERCIAL | ¤84.60 | 08/30/2024 |
| SURCHARGE FS 533.721 | ¤2.00 | 08/30/2024 |
| SURCHARGE - FS 468.631 | ¤2.16 | 08/30/2024 |
| SW ENG - INSPECTION 20 | ¤20.00 | 08/30/2024 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤167.80 |