Permit #2024070954
Permit Details
Status: FINAL
| Parcel Id: 08-12-31-5835-00000-0020 |
| Block: 00000 |
| Subdivision: 2323 - WILTON AT PAL M COAST |
| Job Phone: 386-322-8700 |
| Location Address: 300 LINWOOD ROW |
| Type: FU - FIRE UNDERGROUND |
| Issue Date: 08/30/2024 |
| NOC: RECORDED |
| Applicant name: CHAD HAZEN |
| Owner: WILTON RESIDENCES LLC |
|
Address 500 OFFICE PARK DRIVE STE 215 BRIMINGHAM, AL 35223 |
| Lot: 0020 |
| Contracted Stated Job Value: ¤40,485.00 |
| Job Description: BLDG 5 - UNDERGROUND FIRE MAIN FROM POINT OF SERVICE TO 1' ABOVE FINISH FLOOR REF#2023090400 |
| Type: CN |
| Original Permit #: 2023090400 |
Contractor
HAZEN CONSTRUCTION, LLC
| Status | Location Address | State License Number | Phone | Fax |
| ACTIVE |
1599 TIONIA RD NEW SMYRNA BEACH, FL 32168 |
98771000012007 (Exp: 06/30/2026) | 386-322-8700 | 386-756-0000 |
Inspection History
| Type | Request Date | Result | Inspector |
| FIRE FINAL | 01/08/2025 | FINAL APPROVED | RMARTIN |
| Note: 10/1/2024 - PREVIOUS INSPECTION NOTES *** NOTES ADDED BY RMARTIN 10/1/2024 10:21:09 AM *** need to lable fdc connection/connections in front of 300 and check hydrants hight, needs to be 18" from finish grade to centre of lugs not 15" 9/26/2024 - PREVIOUS INSPECTION NOTES *** NOTES ADDED BY RMARTIN 9/26/2024 9:52:54 AM *** need to lable fdc connection/connections in front of 300 and check hydrants hight, needs to be 18" from finish grade to centre of lugs not 15" 3/1/2024 - PREVIOUS INSPECTION NOTES ALL GRADING AND SOD NEEDS TO BE INSTALLED BEFORE FINAL IS SCHEDULED, NEED ALL CAPS AND SIGNAGE ON FDC'S, NEED TO CHECK ALL HIGHTS AS WELL | |||
| FIRE FINAL | 10/01/2024 | Disapproved -FEE REQUIRED | RMARTIN |
| Note: *** NOTES ADDED BY RMARTIN 10/1/2024 10:21:09 AM *** need to lable fdc connection/connections in front of 300 and check hydrants hight, needs to be 18" from finish grade to centre of lugs not 15" 9/26/2024 - PREVIOUS INSPECTION NOTES *** NOTES ADDED BY RMARTIN 9/26/2024 9:52:54 AM *** need to lable fdc connection/connections in front of 300 and check hydrants hight, needs to be 18" from finish grade to centre of lugs not 15" 3/1/2024 - PREVIOUS INSPECTION NOTES ALL GRADING AND SOD NEEDS TO BE INSTALLED BEFORE FINAL IS SCHEDULED, NEED ALL CAPS AND SIGNAGE ON FDC'S, NEED TO CHECK ALL HIGHTS AS WELL | |||
| FIRE FINAL | 09/26/2024 | Disapproved -FEE REQUIRED | RMARTIN |
| Note: *** NOTES ADDED BY RMARTIN 9/26/2024 9:52:54 AM *** need to lable fdc connection/connections in front of 300 and check hydrants hight, needs to be 18" from finish grade to centre of lugs not 15" 3/1/2024 - PREVIOUS INSPECTION NOTES ALL GRADING AND SOD NEEDS TO BE INSTALLED BEFORE FINAL IS SCHEDULED, NEED ALL CAPS AND SIGNAGE ON FDC'S, NEED TO CHECK ALL HIGHTS AS WELL | |||
| FIRE FINAL | 03/01/2024 | Disapproved - NO FEE | RMARTIN |
| Note: ALL GRADING AND SOD NEEDS TO BE INSTALLED BEFORE FINAL IS SCHEDULED, NEED ALL CAPS AND SIGNAGE ON FDC'S, NEED TO CHECK ALL HIGHTS AS WELL | |||
| U -UTILITY RESIDENTIAL FINAL | 03/01/2024 | CANCELLED BY APPLICANT | JHARDING |
| Note: Not ready | |||
| FIRE SYSTEM FLUSH | 11/22/2023 | APPROVED | RMARTIN |
| FIRE MAIN HYDROSTATIC/BACKFLOW PREVENTOR | 10/20/2023 | APPROVED | RMARTIN |
| FIRE MAIN PLACEMENT /SIZE/THRUST /BLOCKING | 09/29/2023 | APPROVED | JMUNSON |
| Note: 9/27/2023 - PREVIOUS INSPECTION NOTES 9/26/2023 - PREVIOUS INSPECTION NOTES Still working to uncover the connections and hardware, still under water and soil. Need to expose for inspection (please be sure the hardware is sufficiently uncovered and cleand off such that inspection of all threads bolts, bolts, nuts, washers, clamps, and other restraining devices can be inspected for proper coverage of acceptable corrosion-retardant material. NFPA 24 (2016) 10.6.2.5 | |||
| FIRE MAIN PLACEMENT /SIZE/THRUST /BLOCKING | 09/27/2023 | CANCELLED BY APPLICANT | RMARTIN |
| Note: 9/26/2023 - PREVIOUS INSPECTION NOTES Still working to uncover the connections and hardware, still under water and soil. Need to expose for inspection (please be sure the hardware is sufficiently uncovered and cleand off such that inspection of all threads bolts, bolts, nuts, washers, clamps, and other restraining devices can be inspected for proper coverage of acceptable corrosion-retardant material. NFPA 24 (2016) 10.6.2.5 | |||
| FIRE MAIN PLACEMENT /SIZE/THRUST /BLOCKING | 09/26/2023 | Disapproved - NO FEE | LMILLER |
| Note: 1. Still working to uncover the connections and hardware, still under water and soil. Need to expose for inspection (please be sure the hardware is sufficiently uncovered and cleand off such that inspection of all threads bolts, bolts, nuts, washers, clamps, and other restraining devices can be inspected for proper coverage of acceptable corrosion-retardant material. NFPA 24 (2016) 10.6.2.5 2. The connections at the zurn riser are not installed per manufacturer specifications (the ears are not to be used as perminant restraint. |
Review History
| Department | Status | Date In | Date Out |
| FI1 | COMPLETE | 09/20/2023 | 09/20/2023 |
| Note: Released By: LEE MILLER - (386)986-3783 - WMILLER@PALMCOASTGOV.COM | |||
| FI1 | COMPLETE | 09/11/2023 | 09/19/2023 |
| Note: Released By: LEE MILLER - (386)986-3783 - WMILLER@PALMCOASTGOV.COM | |||
| SW1 | COMPLETE | 09/11/2023 | 09/15/2023 |
| Note: Released By: ROBERT GROSS - (386)986-4769 - RGROSS@PALMCOASTGOV.COM | |||
| UD1 | COMPLETE | 09/11/2023 | 09/12/2023 |
| Note: Released By: BRICE WRIGHT - (386)986-2398 - BWRIGHT@PALMCOASTGOV.COM |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| REINSPECTION - COMMERCIAL | ¤60.00 | 01/06/2025 |
| REINSPECTION - COMMERCIAL | ¤60.00 | 09/30/2024 |
| ADJUSTMENT 10% | (¤15.96) | 08/30/2024 |
| ADMINISTRATIVE - COMMERCIAL | ¤75.00 | 08/30/2024 |
| INSPECTION - FIRE COMMERCIAL | ¤84.60 | 08/30/2024 |
| SURCHARGE FS 533.721 | ¤2.00 | 08/30/2024 |
| SURCHARGE - FS 468.631 | ¤2.16 | 08/30/2024 |
| SW ENG - INSPECTION 20 | ¤20.00 | 08/30/2024 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤287.80 |