I want to search for...
Permit #2024071399
Permit Details
Status: FINAL
| Parcel Id: 15-11-31-2971-00000-0550 |
| Block: 00000 |
| Subdivision: - |
| Job Phone: 386-566-9114 |
| Location Address: 15 LAKESIDE WAY |
| Type: GEN - GENERATOR |
| Issue Date: 08/26/2024 |
| NOC: RECORDED |
| Applicant name: ROBERT J CATES |
| Owner: CRAIG ALAN J & BARBARA J H&W |
|
Address 15 LAKESIDE WAY PALM COAST, FL 32137 |
| Lot: 0550 |
| Contracted Stated Job Value: ¤19,467.00 |
| Job Description: GENERATOR,(1)200 AMP ATS,&(1) 120 GAL. AG TANK |
| Type: CN |
Contractor
TOTAL COMFORT HEATING AND AIR CONDITIONING
| Status | Location Address | State License Number | Phone |
| INACTIVE |
400 NORTH US HIGHWAY 1 ORMOND BEACH, FL 32174 |
EC13003957 (Exp: 08/31/2026) | 386-672-8494 |
Sub Contractors
KEN DEPRINZIO
| Status | Location Address | State License Number | Phone | Fax |
| ACTIVE |
325 WALKER STREET HOLLY HILL, FL 32117 |
11351 (Exp: 08/31/2026) | 386-672-8494 | 386-673-7856 |
Inspection History
| Type | Request Date | Result | Inspector |
| ELECTRIC FINAL | 10/02/2024 | APPROVED | PKNAPIK |
| GAS FINAL | 09/26/2024 | APPROVED - AS NOTED | MGIBSON |
| Note: THIS WAS ALSO APPROVED ON 9/24/24 WITH GAS ROUGH INSPECTION, GAS WAS HOOKED UP | |||
| GAS ROUGH | 09/24/2024 | APPROVED | MGIBSON |
Review History
| Department | Status | Date In | Date Out |
| BADMIN | INFORMATION | 08/06/2024 | 08/06/2024 |
| Note: Marked INFORMATION By: CINDY CHIRI-GONCALVES - (386)986-4737 - CGONCALVES@PALMCOASTGOV.COM Description and file name should match. Please label the site plan correctly | |||
| GAS | HOLD | 08/01/2024 | 08/05/2024 |
| Note: Held By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM Provide note on plans that generator exhaust must be minimum 10ft from any opening into the building per FBC Residential 2023 8Th edition M1905.2.5. If using the exception to 5ft, carbon monoxide detectors will be inspected on generator final. (Second Request) | |||
| ZON | COMPLETE | 08/01/2024 | 08/01/2024 |
| Note: Released By: ALISHA MOBLEY - (386)986-3751 - AMOBLEY@PALMCOASTGOV.COM | |||
| ELEC | COMPLETE | 07/29/2024 | 08/01/2024 |
| Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM | |||
| ZON | HOLD | 07/29/2024 | 07/30/2024 |
| Note: Held By: ALISHA MOBLEY - (386)986-3751 - AMOBLEY@PALMCOASTGOV.COM Please provide on site plan the setbacks from the generator and tank to side property line | |||
| GAS | HOLD | 07/29/2024 | 08/01/2024 |
| Note: Held By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM Provide note on plans that generator exhaust must be minimum 10ft from any opening into the building per FBC Residential 2023 8Th edition M1905.2.5. If using the exception to 5ft, carbon monoxide detectors will be inspected on generator final. | |||
| GAS | COMPLETE | 07/03/2024 | 08/07/2024 |
| Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| ADJUSTMENT 10% | (¤12.25) | 08/26/2024 |
| ADMINISTRATIVE RESIDENTIAL | ¤30.00 | 08/26/2024 |
| INSPECTION - RESIDENTIAL | ¤60.00 | 08/26/2024 |
| PLAN REVIEW - MISC 32.50 | ¤32.50 | 08/26/2024 |
| SURCHARGE FS 533.721 | ¤2.00 | 08/26/2024 |
| SURCHARGE - FS 468.631 | ¤2.00 | 08/26/2024 |
| SITE PLAN 15 | ¤15.00 | 08/26/2024 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤129.25 |