Permit #2024081176

Permit Details

Status: COED

Parcel Id: 09-12-31-0000-02030-0020
Total Square Footage: 9468 sqft
Block: 02030
Subdivision: -
Job Phone: 678-697-0613
Location Address: 1 MEMORIAL MEDICAL PKWY
Type: CIA - COMMERCIAL INTERIOR EXTERIOR ALTERATION
Issue Date: 09/26/2024
NOC: RECORDED
Applicant name: BRUCE ROBERT ADAMS
Owner: MEMORIAL HOSPITAL-FLAGLER INC

Address

60 MEMORIAL MEDICAL PKWY

PALM COAST, FL 32164

Lot: 0020
Contracted Stated Job Value: ¤2,500,000.00
Job Description: Level 2 - Oncology suite
Type: CN

Contractor

THE ROBINS & MORTON GROUP
Status Location Address Mailing Address State License Number Phone
ACTIVE

423 S KELLER RD

ORLANDO, FL 32810

#200

ORLANDO, FL 32810

CGC1523017 (Exp: 08/31/2026) 407-916-7235

Sub Contractors

KEITH MICHAEL CAMPBELL
Status Location Address State License Number Phone Fax
ACTIVE

3010 W BEAVER STREET

JACKSONVILLE, FL 32254

CMC1250524 (Exp: 08/31/2026) 904-387-9996 904-387-9068
JAMES BRIAN SEAY
Status Location Address State License Number Phone Fax
ACTIVE

PO BOX 1799

JACKSONVILLE, FL 32201

EC13003061 (Exp: 08/31/2026) 904-388-8000 904-389-8653
KEITH MICHAEL CAMPBELL
Status Location Address State License Number Phone Fax
ACTIVE

3010 W BEAVER STREET

JACKSONVILLE, FL 32254

CMC1250524 (Exp: 08/31/2026) 904-387-9996 904-387-9068

Inspection History

Type Request Date Result Inspector
BUILDING FINAL 03/27/2025 FINAL APPROVED FWILLIS
Note: Inspector Notes from Inspection 3470 Electrical -(2) 1/2inch knock out in box Mechanical OK Plumbing OK
FIRE FINAL 03/27/2025 APPROVED RMARTIN
Note: 3/26/2025 - PREVIOUS INSPECTION NOTES 1/10/2025 - PREVIOUS INSPECTION NOTES *** NOTES ADDED BY RMARTIN 1/10/2025 2:29:17 PM *** Pending pharmacy
FIRE FINAL 03/26/2025 CANCELLED BY APPLICANT RMARTIN
Note: 1/10/2025 - PREVIOUS INSPECTION NOTES *** NOTES ADDED BY RMARTIN 1/10/2025 2:29:17 PM *** Pending pharmacy
ELECTRIC FINAL 03/26/2025 APPROVED RMARTIN
Note: 1/13/2025 - PREVIOUS INSPECTION NOTES *** NOTES ADDED BY RMARTIN 1/13/2025 9:09:59 AM *** PENDING PHARMACY, AND CHECKING CORRECT PANEL SCHEDULES ON FINAL 1/10/2025 - PREVIOUS INSPECTION NOTES *** NOTES ADDED BY RMARTIN 1/10/2025 2:34:12 PM *** Need gfci protection in rooms where outlets are within 6' of sink NEC 210.8 Inspector Notes from Inspection 3190 *** NOTES ADDED BY RMARTIN 11/12/2024 2:42:03 PM *** Inside soffit area 2nd floor 9/30/2024 - PREVIOUS INSPECTION NOTES *** NOTES ADDED BY RMARTIN 9/30/2024 2:15:46 PM *** 2nd floor, need to call in rough when rooms 237 and 237a are complete
ABOVE CEILING 03/26/2025 APPROVED - AS NOTED CPISCITELLI
Note: Electrical -(2) 1/2inch knock out in box Mechanical OK Plumbing OK
HVAC FINAL 03/26/2025 FINAL APPROVED CPISCITELLI
Note: 1/10/2025 - PREVIOUS INSPECTION NOTES still need to inspect pharmacy and test and balance report
HVAC ROUGH 03/18/2025 APPROVED CPISCITELLI
Note: 1/29/2025 - PREVIOUS INSPECTION NOTES 1/13/25: Pharmacy area still requires this inspection. 1/2/2025 - PREVIOUS INSPECTION NOTES 11/12/2024 - PREVIOUS INSPECTION NOTES inspected supply duct to be able to wrap
HVAC ROUGH 01/29/2025 PARTIALLY APPROVED RSIMS
Note: *** NOTES ADDED BY RSIMS 1/29/2025 3:56:19 PM *** 1/29/25: Inspected ductwork for pharmacy only so that it could be insulated. Previously installed VAV distribution box that served the pharmacy area has been removed to make room for the new RTU that will independently serve the Pharmacy area. 1/13/25: Pharmacy area still requires this inspection. 1/2/2025 - PREVIOUS INSPECTION NOTES 11/12/2024 - PREVIOUS INSPECTION NOTES inspected supply duct to be able to wrap
U - UTILITY COMMERCIAL FINAL 01/15/2025 FINAL APPROVED LFITZGERALD
BUILDING FINAL 01/13/2025 PARTIALLY APPROVED RSIMS
Note: *** NOTES ADDED BY RSIMS 1/13/2025 3:39:21 PM *** 1/13/25: 2nd floor all areas except for Pharmacy have been inspected. The Pharmacy will still require a full inspection. Also, Utility/Mop Receptor room requires sanitary base molding to protect drywall from potential exposure to water damage and/or wicking of water on floor. Check at 2nd Final. Partial Final Approval to allow for temporary CO. Inspector Notes from Inspection 3470 *** NOTES ADDED BY RMARTIN 1/9/2025 2:13:15 PM *** need to leave a couple tiles out in lobby area for hvac and electric final 1/8/2025 - PREVIOUS INSPECTION NOTES electrical and mechanical have 2 areas that are not ready- Lobby and area in back corner 1/2/2025 - PREVIOUS INSPECTION NOTES *** NOTES ADDED BY RMARTIN 1/2/2025 9:17:15 AM *** 2nd floor rooms only, Robert Sims walked and inspected with me as well
ELECTRIC FINAL 01/13/2025 PARTIALLY APPROVED RMARTIN
Note: *** NOTES ADDED BY RMARTIN 1/13/2025 9:09:59 AM *** PENDING PHARMACY, AND CHECKING CORRECT PANEL SCHEDULES ON FINAL 1/10/2025 - PREVIOUS INSPECTION NOTES *** NOTES ADDED BY RMARTIN 1/10/2025 2:34:12 PM *** Need gfci protection in rooms where outlets are within 6' of sink NEC 210.8 Inspector Notes from Inspection 3190 *** NOTES ADDED BY RMARTIN 11/12/2024 2:42:03 PM *** Inside soffit area 2nd floor 9/30/2024 - PREVIOUS INSPECTION NOTES *** NOTES ADDED BY RMARTIN 9/30/2024 2:15:46 PM *** 2nd floor, need to call in rough when rooms 237 and 237a are complete
ELECTRIC FINAL 01/10/2025 Disapproved - NO FEE RMARTIN
Note: *** NOTES ADDED BY RMARTIN 1/10/2025 2:34:12 PM *** Need gfci protection in rooms where outlets are within 6' of sink NEC 210.8 Inspector Notes from Inspection 3190 *** NOTES ADDED BY RMARTIN 11/12/2024 2:42:03 PM *** Inside soffit area 2nd floor 9/30/2024 - PREVIOUS INSPECTION NOTES *** NOTES ADDED BY RMARTIN 9/30/2024 2:15:46 PM *** 2nd floor, need to call in rough when rooms 237 and 237a are complete
HVAC FINAL 01/10/2025 PARTIALLY APPROVED CPISCITELLI
Note: still need to inspect pharmacy and test and balance report
PLUMBING FINAL 01/10/2025 APPROVED MGIBSON
Note: Inspector Notes from Inspection 3080 9/30/2024 - PREVIOUS INSPECTION NOTES WASTE AND VENT NEED TEST ON AND WATER DISTRIBUTION THIS WAS A FOR SECOND FLOOR
FIRE FINAL 01/10/2025 PARTIALLY APPROVED RMARTIN
Note: *** NOTES ADDED BY RMARTIN 1/10/2025 2:29:17 PM *** Pending pharmacy
ABOVE CEILING 01/09/2025 APPROVED - AS NOTED RMARTIN
Note: *** NOTES ADDED BY RMARTIN 1/9/2025 2:13:15 PM *** need to leave a couple tiles out in lobby area for hvac and electric final 1/8/2025 - PREVIOUS INSPECTION NOTES electrical and mechanical have 2 areas that are not ready- Lobby and area in back corner 1/2/2025 - PREVIOUS INSPECTION NOTES *** NOTES ADDED BY RMARTIN 1/2/2025 9:17:15 AM *** 2nd floor rooms only, Robert Sims walked and inspected with me as well
ABOVE CEILING 01/08/2025 PARTIALLY APPROVED CPISCITELLI
Note: electrical and mechanical have 2 areas that are not ready- Lobby and area in back corner 1/2/2025 - PREVIOUS INSPECTION NOTES *** NOTES ADDED BY RMARTIN 1/2/2025 9:17:15 AM *** 2nd floor rooms only, Robert Sims walked and inspected with me as well
FIREWALL PENETRATIONS 01/06/2025 APPROVED RSIMS
Note: *** NOTES ADDED BY RSIMS 1/6/2025 10:27:10 AM ***
ABOVE CEILING 01/02/2025 PARTIALLY APPROVED RMARTIN
Note: *** NOTES ADDED BY RMARTIN 1/2/2025 9:17:15 AM *** 2nd floor rooms only, Robert Sims walked and inspected with me as well
HVAC ROUGH 01/02/2025 PARTIALLY APPROVED RSIMS
Note: *** NOTES ADDED BY RSIMS 1/2/2025 9:25:38 AM *** 1/2/25: Partial Inspection for rooms and corridors > Infusuion area, Pharmacy and Lobby are still in progress and not ready for inspection yet. Partial approval is also contingent on Revisions Uploaded/Accepted on 11/19/24 being Approved. Informed PM that drywall edges at penetrations (at a minimum) will need to be sealed due to conditioned returm plenum. 11/12/2024 - PREVIOUS INSPECTION NOTES inspected supply duct to be able to wrap
PLUMBING PRESSURE TEST 11/12/2024 APPROVED - AS NOTED MGIBSON
Note: 10/4/2024 - PREVIOUS INSPECTION NOTES NOT READY. WILL RESCHEDUAL WHEN READY. THIS WAS FOR SECOND FLOOR
HVAC ROUGH 11/12/2024 PARTIALLY APPROVED CPISCITELLI
Note: inspected supply duct to be able to wrap
PLUMBING 2ND ROUGH 11/12/2024 APPROVED - AS NOTED MGIBSON
Note: 9/30/2024 - PREVIOUS INSPECTION NOTES WASTE AND VENT NEED TEST ON AND WATER DISTRIBUTION THIS WAS A FOR SECOND FLOOR
ELECTRIC 2ND ROUGH 11/12/2024 APPROVED - AS NOTED RMARTIN
Note: *** NOTES ADDED BY RMARTIN 11/12/2024 2:42:03 PM *** Inside soffit area 2nd floor 9/30/2024 - PREVIOUS INSPECTION NOTES *** NOTES ADDED BY RMARTIN 9/30/2024 2:15:46 PM *** 2nd floor, need to call in rough when rooms 237 and 237a are complete
PLUMBING PRESSURE TEST 10/04/2024 Disapproved - NO FEE MGIBSON
Note: NOT READY. WILL RESCHEDUAL WHEN READY
PLUMBING 2ND ROUGH 09/30/2024 PARTIALLY APPROVED MGIBSON
Note: WASTE AND VENT NEED TEST ON AND WATER DISTRIBUTION
ELECTRIC 2ND ROUGH 09/30/2024 PARTIALLY APPROVED RMARTIN
Note: *** NOTES ADDED BY RMARTIN 9/30/2024 2:15:46 PM *** 2nd floor, need to call in rough when rooms 237 and 237a are complete
PLUMBING 1ST ROUGH 09/27/2024 APPROVED - AS NOTED MGIBSON
Note: PLUMBERS WERE FILLING UP WASTE WILL CHECK HEAD TEST ON 9/30/24 WHEN SECOND ROUGH PLUMBING IS SCHEDUALED
FRAMING 09/27/2024 APPROVED FWILLIS
Note: LEVEL #2 ONCOLOGY

Review History

Department Status Date In Date Out
ELEC COMPLETE 01/02/2025 01/03/2025
Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM
BLD COMPLETE 01/02/2025 01/03/2025
Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM
BLD COMPLETE 11/19/2024 12/05/2024
Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM
ELEC HOLD 11/19/2024 11/19/2024
Note: Held By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM 1. Submit engineer response letter for changes.
MECH COMPLETE 11/19/2024 12/02/2024
Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM
PLUM COMPLETE 11/19/2024 12/05/2024
Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM
BLD COMPLETE 09/24/2024 09/25/2024
Note: Released By: ALPHANETTE WATERS - (386)986-2624 - AWATERS@PALMCOASTGOV.COM
BLD HOLD 09/23/2024 09/24/2024
Note: Held By: ALPHANETTE WATERS - (386)986-2624 - AWATERS@PALMCOASTGOV.COM PLEASE LOAD NEW APPLICATION FOR PROJECT ADDRESS 1 MEMORIAL MEDICAL PARKWAY INSTEAD OF 60 MEMORIAL MEDICAL PARKWAY SO WE CAN CHANE THE ADDRESS ON THE PERMIT. ALL DRAWING REVISIONS ARE APPROVED.
BLD HOLD 08/28/2024 09/10/2024
Note: Held By: ALPHANETTE WATERS - (386)986-2624 - AWATERS@PALMCOASTGOV.COM 1. Incorrect address on the plans. AHJ 2. Use noncombustible materails per FBCB 602.2 or fire-retardant-treated wood per FBCB 603
DSD COMPLETE 08/28/2024 08/29/2024
Note: Released By: JACQUELINE GONZALEZ - (386)986-3751 - JGONZALEZ@PALMCOASTGOV.COM
ELEC COMPLETE 08/28/2024 09/09/2024
Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM
FI1 COMPLETE 08/28/2024 09/10/2024
Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM
MECH COMPLETE 08/28/2024 09/11/2024
Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM
PLUM COMPLETE 08/28/2024 09/10/2024
Note: Released By: ALPHANETTE WATERS - (386)986-2624 - AWATERS@PALMCOASTGOV.COM
UD1 COMPLETE 08/28/2024 09/06/2024
Note: Released By: GREG DEGLER - (386)986-2384 - GDEGLER@PALMCOASTGOV.COM

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
ADJUSTMENT 10% (¤2,045.00) 09/26/2024
ADMINISTRATIVE - COMMERCIAL ¤75.00 09/26/2024
INSPECTION COMMERCIAL ¤17,500.00 09/26/2024
PLAN REVIEW - COMMERCIAL ¤2,875.00 09/26/2024
CONTRACTOR CHANGE ¤20.00 09/26/2024
SURCHARGE FS 533.721 ¤184.05 09/26/2024
SURCHARGE - FS 468.631 ¤276.08 09/26/2024
SITE PLAN 30 ¤30.00 09/26/2024
Fees Total Due: ¤0.00 Total Paid: ¤18,915.13