I want to search for...

Permit #2024090071

Permit Details

Status: INSPECT

Parcel Id: 01-12-30-5550-00030-0030
CONDITIONED SPACE: 2714 sqft
GARAGE: 752 sqft
OPENED PORCH (WITH ROOF) : 534 sqft
Total Square Footage: 4000 sqft
Block: 00030
Subdivision: -
Job Phone: 386-237-5837
Location Address: 4 ETNA WAY
Type: BR - BUILDING RESIDENTIAL -SINGLE FAMILY
Issue Date: 01/07/2025
NOC: RECORDED
Applicant name: MARSEL GILMANSHIN
Owner: LEONID LEVIT AND ELLA CHAGEYEVA

Address

47 EDITH POPE DRIVE

PALM COAST, FL 32164

Lot: 0030
Contracted Stated Job Value: ¤400,000.00
Job Description: Single Family Residence
Type: CN

Contractor

GILMANS DEVELOPMENT CORP
Status Location Address State License Number Phone
ACTIVE

4873 PALM COAST PARKWAY NW #4

PALM COAST, FL 32137

CBC1263180 (Exp: 08/31/2026) 386-237-5837

Sub Contractors

JUAN CARLOS GONZALEZ
Status Location Address State License Number
ACTIVE

1328 COUNTY ROAD 308

CRESCENT CITY, FL 32112

RF11067806 (Exp: 08/31/2027)
MARSEL GILMANSHIN
Status Location Address State License Number Phone
ACTIVE

4873 PALM COAST PARKWAY NW #4

PALM COAST, FL 32137

CBC1263180 (Exp: 08/31/2026) 386-237-5837
WILLIAM TODD SIKES
Status Location Address State License Number Phone
ACTIVE

83 PORT ROYAL DR

ST AUGUSTINE, FL 32084

EC0002726 (Exp: 08/31/2026) 904-762-8762
SCOTT H STILLWELL
Status Location Address State License Number Phone
ACTIVE

4500 US 1 UNIT 206

BUNNELL, FL 32110

CAC1819433 (Exp: 08/31/2026) 386-864-4404

Inspection History

Type Request Date Result Inspector
GRAVITY SEWER TEST 03/25/2026 APPROVED HCAMACHO
SEWER TIE IN 03/25/2026 APPROVED HCAMACHO
U-CROSS CONNECTION 03/25/2026 APPROVED - AS NOTED BHAINES
Note: No CC, No IRR
ROW- PRE-APRON (PRE-POUR) 01/08/2026 PARTIALLY APPROVED FSLADISH
Note: 1/8/26 REVISED SITE PLAN NOW SHOWS UPPER DRIVEWAY AT RESIDENCE MEETING THE COPC PREPOUR STAND WIDTH. I AM PARTIALLY APPROVING YOU TO POUR DRIVEWAY AT STRUCTURE. YOU ARE REQUIRED TO CALL IN A SECONDARY PREPOUR INSPECTION FOR YOUR DRIVEWAY ENTRANCE APRON AT ROAD EDGE AND MITERED END SECTIONS ON YOUR CULVERT PIPE CROSSING INDICATED. BUILDER REFER TO CONCRETE (FRC) DRAWING 300,E RESIDENTIAL CULVERT DETAIL BEFORE POURING. . IF FIBERGLASS OPTION IS USED, BUILDER REQUIRED TO USE 3000 PSI CONCRETE REINFORCED WITH WWF 6X6.W1.4 MESH OR FIBERGLASS REINFORCED DOCUMENTATION OF THE ( FRC) CONTAINING THE FIBERGLASS MUST BE ATTACHED TO THE PERMIT PRIOR TO REQUESTING AN AFTER-POUR INSPECTION. 8.b. IF MESH OPTION IS USED, IT SHALL BE IN PLACE AT THE TIME OF THE PRE-POUR AT THE TIME OF THE INSPECTION READY TO POUR, IF RAIN PLEASE, BUILDER SHOULD DOUBLE CHECK SITE FOR ANY STANDING WATER. NO EXPANSION JOINTS ALLOWED, AT THE TIME OF THIS INSPECTION ALL MINIMUM COPC REQUIREMENTS ARE MET. BUILDER TO BE HELD RESPONSIBLE IF, FOR WHATEVER REASON, SITE CONDITIONS CHANGE OVER TIME AFTER THE INSPECTION. IT IS THE BUILDER'S RESPONSIBILITY TO ENSURE THAT NOTHING CHANGES AFTER THIS INSPECTION IS APPROVED 12/17/2025 - PREVIOUS INSPECTION NOTES 12/17/25 CONTACTED MARCEL CM AND LET HIM KNOW A NEW SITE PLAN NEEDS TO BE SUBMITTED FOR REVIEW AND APPROVAL BEFORE A PREPOUR INSPECTION CAN TAKE PLACE. 12/11/2025 - PREVIOUS INSPECTION NOTES 12/11/25 We will be meeting with builder to discuss how to move forward with this site. disapproving no fee
ROW- PRE-APRON (PRE-POUR) 12/17/2025 CANCELLED BY APPLICANT FSLADISH
Note: 12/17/25 CONTACTED MARCEL CM AND LET HIM KNOW A NEW SITE PLAN NEEDS TO BE SUBMITTED FOR REVIEW AND APPROVAL BEFORE A PREPOUR INSPECTION CAN TAKE PLACE. 12/11/2025 - PREVIOUS INSPECTION NOTES 12/11/25 We will be meeting with builder to discuss how to move forward with this site. disapproving no fee
ROW- PRE-APRON (PRE-POUR) 12/11/2025 Disapproved - NO FEE FSLADISH
Note: 12/11/25 We will be meeting with builder to discuss how to move forward with this site. disapproving no fee
ELECTRIC - EARLY POWER 11/06/2025 APPROVED CVANSTRAHLEN
Note: Email to FPL
ELECTRIC - EARLY POWER 11/04/2025 Disapproved -FEE REQUIRED CVANSTRAHLEN
Note: Please fix items before next inspection #1- NEC 110.27-SAFE OFF ALL WIRING ( several gang boxes with electrical wire need to have wire safe off . kitchen area , AH unit wire , exterior left side , garage right side #2- ground wire need to be expose or have a opening near electrical main panel
PEP TANK INSTALLATION REQUEST 10/08/2025 APPROVED CBOWERMASTER
INSULATION 08/27/2025 APPROVED - AS NOTED MCONTRYMAN
Note: 8/27/25 The following needs to be completed by final 1. Need whole home sure protection on meter/main only NEC 230.67 (electrician installing at early power) 2. Need approved revision of energy calcs to show all doors and windows installed FBC(A) 107.4 (waiting on approval) 3. Energy calcs need to also show spray foam insulation and corect R-value for ceiling and walls 8/26/2025 - PREVIOUS INSPECTION NOTES 8/26/25 Previous notes not rectified 4. Need whole home sure protection on meter/main only NEC 230.67 (electrician installing at early power) 5. Need approved revision of energy calcs to show all doors and windows installed FBC(A) 107.4 (waiting on approval) In addition: 1. Energy calcs need to also show spray foam insulation and corect R-value for ceiling and walls 2. Water heater lines are protruding out of the wall in the utility/laundry room 3. No spray foam certificate on site Inspector Notes from Inspection 2420 8/20/25 Will check at insulation 2. No 5' Head test FBCR P2503.7 4. Need whole home sure protection on meter/main only NEC 230.67 (electrician installing at early power) 5. Need approved revision of energy calcs and product approvals to show all doors and windows installed FBC(A) 107.4 (waiting on approval) 6. Need approved plan revision to show placement of AH, wash sink, and water heater as built FBC(A) 107.4 (waiting on approval) Inspector Notes from Inspection 2320 Please fix previous inspections items Inspector Notes from Inspection 2420 7/29/25 Approved to keep job moving 1. Need nail plate on stud in back hall outside of master bedroom (labeled NP) NEC 300.4 2. No 5' Head test FBCR P2503.7 3. No water pressure on lines FBCR P2503.5 4. Need whole home sure protection on meter/main only NEC 230.67 5. Need approved revision of energy calcs and product approvals to show all doors and windows installed FBC(A) 107.4 6. Need approved plan revision to show placement of AH, wash sink, and water heater as built FBC(A) 107.4 --Notating that the surrounding wall behind the wood burning fireplace in the family room needs to be heat shielded and per fire code-- 7/16/2025 - PREVIOUS INSPECTION NOTES 7/16/25 Job not ready 1. No windows or doors installed. Upon arriving, they were sitting out front 2. Site still not cleaned up. All garbage and debris is just piled up to the side. Site needs to be cleaned at all times FBC 3302.2 --Will need all new inspection-- Inspector Notes from Inspection 2460 4/25/25 3. Dump trailer on site. Site needs to be cleaned up FBC 3302.2 (must be done by next inspection) Notes: -No water pressure -Need 5' head test 4/17/2025 - PREVIOUS INSPECTION NOTES 4/17/25 1. No Permit pack on site FBC(A) 105.7 2. No plans on site FBC(A) 107.3.1 3. Need dumpster on site and site cleaned up FBC 3302.2 (must be done by next inspection) Inspector Notes from Inspection 2340 3/31/25 Will check at next inspection 1. Window sill by kitchen sink is not mortared in. Changing windows size (3040SH, 35 1/2"x"x47 1/2" on plans). If size changes, will need engineered letter of approval Inspector Notes from Inspection 2340 3/31/25 Will check at next inspection 1. Window sill by kitchen sink is not mortared in. Changing windows size (3040SH, 35 1/2"x"x47 1/2" on plans). If size changes, will need engineered letter of approval
INSULATION 08/26/2025 Disapproved -FEE REQUIRED MCONTRYMAN
Note: 8/26/25 Previous notes not rectified 4. Need whole home sure protection on meter/main only NEC 230.67 (electrician installing at early power) 5. Need approved revision of energy calcs to show all doors and windows installed FBC(A) 107.4 (waiting on approval) In addition: 1. Energy calcs need to also show spray foam insulation and corect R-value for ceiling and walls 2. Water heater lines are protruding out of the wall in the utility/laundry room 3. No spray foam certificate on site Inspector Notes from Inspection 2420 8/20/25 Will check at insulation 2. No 5' Head test FBCR P2503.7 4. Need whole home sure protection on meter/main only NEC 230.67 (electrician installing at early power) 5. Need approved revision of energy calcs and product approvals to show all doors and windows installed FBC(A) 107.4 (waiting on approval) 6. Need approved plan revision to show placement of AH, wash sink, and water heater as built FBC(A) 107.4 (waiting on approval) Inspector Notes from Inspection 2320 Please fix previous inspections items Inspector Notes from Inspection 2420 7/29/25 Approved to keep job moving 1. Need nail plate on stud in back hall outside of master bedroom (labeled NP) NEC 300.4 2. No 5' Head test FBCR P2503.7 3. No water pressure on lines FBCR P2503.5 4. Need whole home sure protection on meter/main only NEC 230.67 5. Need approved revision of energy calcs and product approvals to show all doors and windows installed FBC(A) 107.4 6. Need approved plan revision to show placement of AH, wash sink, and water heater as built FBC(A) 107.4 --Notating that the surrounding wall behind the wood burning fireplace in the family room needs to be heat shielded and per fire code-- 7/16/2025 - PREVIOUS INSPECTION NOTES 7/16/25 Job not ready 1. No windows or doors installed. Upon arriving, they were sitting out front 2. Site still not cleaned up. All garbage and debris is just piled up to the side. Site needs to be cleaned at all times FBC 3302.2 --Will need all new inspection-- Inspector Notes from Inspection 2460 4/25/25 3. Dump trailer on site. Site needs to be cleaned up FBC 3302.2 (must be done by next inspection) Notes: -No water pressure -Need 5' head test 4/17/2025 - PREVIOUS INSPECTION NOTES 4/17/25 1. No Permit pack on site FBC(A) 105.7 2. No plans on site FBC(A) 107.3.1 3. Need dumpster on site and site cleaned up FBC 3302.2 (must be done by next inspection) Inspector Notes from Inspection 2340 3/31/25 Will check at next inspection 1. Window sill by kitchen sink is not mortared in. Changing windows size (3040SH, 35 1/2"x"x47 1/2" on plans). If size changes, will need engineered letter of approval Inspector Notes from Inspection 2340 3/31/25 Will check at next inspection 1. Window sill by kitchen sink is not mortared in. Changing windows size (3040SH, 35 1/2"x"x47 1/2" on plans). If size changes, will need engineered letter of approval
ALL ROUGH 08/20/2025 APPROVED - AS NOTED MCONTRYMAN
Note: 8/20/25 Will check at insulation 2. No 5' Head test FBCR P2503.7 4. Need whole home sure protection on meter/main only NEC 230.67 (electrician installing at early power) 5. Need approved revision of energy calcs and product approvals to show all doors and windows installed FBC(A) 107.4 (waiting on approval) 6. Need approved plan revision to show placement of AH, wash sink, and water heater as built FBC(A) 107.4 (waiting on approval) Inspector Notes from Inspection 2320 Please fix previous inspections items Inspector Notes from Inspection 2420 7/29/25 Approved to keep job moving 1. Need nail plate on stud in back hall outside of master bedroom (labeled NP) NEC 300.4 2. No 5' Head test FBCR P2503.7 3. No water pressure on lines FBCR P2503.5 4. Need whole home sure protection on meter/main only NEC 230.67 5. Need approved revision of energy calcs and product approvals to show all doors and windows installed FBC(A) 107.4 6. Need approved plan revision to show placement of AH, wash sink, and water heater as built FBC(A) 107.4 --Notating that the surrounding wall behind the wood burning fireplace in the family room needs to be heat shielded and per fire code-- 7/16/2025 - PREVIOUS INSPECTION NOTES 7/16/25 Job not ready 1. No windows or doors installed. Upon arriving, they were sitting out front 2. Site still not cleaned up. All garbage and debris is just piled up to the side. Site needs to be cleaned at all times FBC 3302.2 --Will need all new inspection-- Inspector Notes from Inspection 2460 4/25/25 3. Dump trailer on site. Site needs to be cleaned up FBC 3302.2 (must be done by next inspection) Notes: -No water pressure -Need 5' head test 4/17/2025 - PREVIOUS INSPECTION NOTES 4/17/25 1. No Permit pack on site FBC(A) 105.7 2. No plans on site FBC(A) 107.3.1 3. Need dumpster on site and site cleaned up FBC 3302.2 (must be done by next inspection) Inspector Notes from Inspection 2340 3/31/25 Will check at next inspection 1. Window sill by kitchen sink is not mortared in. Changing windows size (3040SH, 35 1/2"x"x47 1/2" on plans). If size changes, will need engineered letter of approval Inspector Notes from Inspection 2340 3/31/25 Will check at next inspection 1. Window sill by kitchen sink is not mortared in. Changing windows size (3040SH, 35 1/2"x"x47 1/2" on plans). If size changes, will need engineered letter of approval
LATH/BRICK/ WATER BARRIER 08/04/2025 APPROVED - AS NOTED CVANSTRAHLEN
Note: Please fix previous inspections items Inspector Notes from Inspection 2420 7/29/25 Approved to keep job moving 1. Need nail plate on stud in back hall outside of master bedroom (labeled NP) NEC 300.4 2. No 5' Head test FBCR P2503.7 3. No water pressure on lines FBCR P2503.5 4. Need whole home sure protection on meter/main only NEC 230.67 5. Need approved revision of energy calcs and product approvals to show all doors and windows installed FBC(A) 107.4 6. Need approved plan revision to show placement of AH, wash sink, and water heater as built FBC(A) 107.4 --Notating that the surrounding wall behind the wood burning fireplace in the family room needs to be heat shielded and per fire code-- 7/16/2025 - PREVIOUS INSPECTION NOTES 7/16/25 Job not ready 1. No windows or doors installed. Upon arriving, they were sitting out front 2. Site still not cleaned up. All garbage and debris is just piled up to the side. Site needs to be cleaned at all times FBC 3302.2 --Will need all new inspection-- Inspector Notes from Inspection 2460 4/25/25 3. Dump trailer on site. Site needs to be cleaned up FBC 3302.2 (must be done by next inspection) Notes: -No water pressure -Need 5' head test 4/17/2025 - PREVIOUS INSPECTION NOTES 4/17/25 1. No Permit pack on site FBC(A) 105.7 2. No plans on site FBC(A) 107.3.1 3. Need dumpster on site and site cleaned up FBC 3302.2 (must be done by next inspection) Inspector Notes from Inspection 2340 3/31/25 Will check at next inspection 1. Window sill by kitchen sink is not mortared in. Changing windows size (3040SH, 35 1/2"x"x47 1/2" on plans). If size changes, will need engineered letter of approval Inspector Notes from Inspection 2340 3/31/25 Will check at next inspection 1. Window sill by kitchen sink is not mortared in. Changing windows size (3040SH, 35 1/2"x"x47 1/2" on plans). If size changes, will need engineered letter of approval
ALL ROUGH 07/29/2025 APPROVED - AS NOTED MCONTRYMAN
Note: 7/29/25 Approved to keep job moving 1. Need nail plate on stud in back hall outside of master bedroom (labeled NP) NEC 300.4 2. No 5' Head test FBCR P2503.7 3. No water pressure on lines FBCR P2503.5 4. Need whole home sure protection on meter/main only NEC 230.67 5. Need approved revision of energy calcs and product approvals to show all doors and windows installed FBC(A) 107.4 6. Need approved plan revision to show placement of AH, wash sink, and water heater as built FBC(A) 107.4 --Notating that the surrounding wall behind the wood burning fireplace in the family room needs to be heat shielded and per fire code-- 7/16/2025 - PREVIOUS INSPECTION NOTES 7/16/25 Job not ready 1. No windows or doors installed. Upon arriving, they were sitting out front 2. Site still not cleaned up. All garbage and debris is just piled up to the side. Site needs to be cleaned at all times FBC 3302.2 --Will need all new inspection-- Inspector Notes from Inspection 2460 4/25/25 3. Dump trailer on site. Site needs to be cleaned up FBC 3302.2 (must be done by next inspection) Notes: -No water pressure -Need 5' head test 4/17/2025 - PREVIOUS INSPECTION NOTES 4/17/25 1. No Permit pack on site FBC(A) 105.7 2. No plans on site FBC(A) 107.3.1 3. Need dumpster on site and site cleaned up FBC 3302.2 (must be done by next inspection) Inspector Notes from Inspection 2340 3/31/25 Will check at next inspection 1. Window sill by kitchen sink is not mortared in. Changing windows size (3040SH, 35 1/2"x"x47 1/2" on plans). If size changes, will need engineered letter of approval Inspector Notes from Inspection 2340 3/31/25 Will check at next inspection 1. Window sill by kitchen sink is not mortared in. Changing windows size (3040SH, 35 1/2"x"x47 1/2" on plans). If size changes, will need engineered letter of approval
ALL ROUGH 07/16/2025 Disapproved -FEE REQUIRED MCONTRYMAN
Note: 7/16/25 Job not ready 1. No windows or doors installed. Upon arriving, they were sitting out front 2. Site still not cleaned up. All garbage and debris is just piled up to the side. Site needs to be cleaned at all times FBC 3302.2 --Will need all new inspection-- Inspector Notes from Inspection 2460 4/25/25 3. Dump trailer on site. Site needs to be cleaned up FBC 3302.2 (must be done by next inspection) Notes: -No water pressure -Need 5' head test 4/17/2025 - PREVIOUS INSPECTION NOTES 4/17/25 1. No Permit pack on site FBC(A) 105.7 2. No plans on site FBC(A) 107.3.1 3. Need dumpster on site and site cleaned up FBC 3302.2 (must be done by next inspection) Inspector Notes from Inspection 2340 3/31/25 Will check at next inspection 1. Window sill by kitchen sink is not mortared in. Changing windows size (3040SH, 35 1/2"x"x47 1/2" on plans). If size changes, will need engineered letter of approval Inspector Notes from Inspection 2340 3/31/25 Will check at next inspection 1. Window sill by kitchen sink is not mortared in. Changing windows size (3040SH, 35 1/2"x"x47 1/2" on plans). If size changes, will need engineered letter of approval
ELECTRIC-TUG 05/01/2025 APPROVED CVANSTRAHLEN
ROOF SHEATHING / BRACES/TIES/DOWN CELL 04/28/2025 APPROVED - AS NOTED MCONTRYMAN
Note: 4/25/25 3. Dump trailer on site. Site needs to be cleaned up FBC 3302.2 (must be done by next inspection) Notes: -No water pressure -Need 5' head test 4/17/2025 - PREVIOUS INSPECTION NOTES 4/17/25 1. No Permit pack on site FBC(A) 105.7 2. No plans on site FBC(A) 107.3.1 3. Need dumpster on site and site cleaned up FBC 3302.2 (must be done by next inspection) Inspector Notes from Inspection 2340 3/31/25 Will check at next inspection 1. Window sill by kitchen sink is not mortared in. Changing windows size (3040SH, 35 1/2"x"x47 1/2" on plans). If size changes, will need engineered letter of approval Inspector Notes from Inspection 2340 3/31/25 Will check at next inspection 1. Window sill by kitchen sink is not mortared in. Changing windows size (3040SH, 35 1/2"x"x47 1/2" on plans). If size changes, will need engineered letter of approval
ROOF VALLEY & METAL 04/17/2025 APPROVED MCONTRYMAN
Note: Inspector Notes from Inspection 2340 3/31/25 Will check at next inspection 1. Window sill by kitchen sink is not mortared in. Changing windows size (3040SH, 35 1/2"x"x47 1/2" on plans). If size changes, will need engineered letter of approval Inspector Notes from Inspection 2340 3/31/25 Will check at next inspection 1. Window sill by kitchen sink is not mortared in. Changing windows size (3040SH, 35 1/2"x"x47 1/2" on plans). If size changes, will need engineered letter of approval Inspector Notes from Inspection 2340 3/31/25 Will check at next inspection 1. Window sill by kitchen sink is not mortared in. Changing windows size (3040SH, 35 1/2"x"x47 1/2" on plans). If size changes, will need engineered letter of approval
WALL SHEATHING 04/17/2025 APPROVED MCONTRYMAN
Note: Inspector Notes from Inspection 2340 3/31/25 Will check at next inspection 1. Window sill by kitchen sink is not mortared in. Changing windows size (3040SH, 35 1/2"x"x47 1/2" on plans). If size changes, will need engineered letter of approval Inspector Notes from Inspection 2340 3/31/25 Will check at next inspection 1. Window sill by kitchen sink is not mortared in. Changing windows size (3040SH, 35 1/2"x"x47 1/2" on plans). If size changes, will need engineered letter of approval
ROOF SHEATHING / BRACES/TIES/DOWN CELL 04/17/2025 Disapproved -FEE REQUIRED MCONTRYMAN
Note: 4/17/25 1. No Permit pack on site FBC(A) 105.7 2. No plans on site FBC(A) 107.3.1 3. Need dumpster on site and site cleaned up FBC 3302.2 (must be done by next inspection) Inspector Notes from Inspection 2340 3/31/25 Will check at next inspection 1. Window sill by kitchen sink is not mortared in. Changing windows size (3040SH, 35 1/2"x"x47 1/2" on plans). If size changes, will need engineered letter of approval Inspector Notes from Inspection 2340 3/31/25 Will check at next inspection 1. Window sill by kitchen sink is not mortared in. Changing windows size (3040SH, 35 1/2"x"x47 1/2" on plans). If size changes, will need engineered letter of approval
PLUMBING 1ST ROUGH UNDERGROUND 04/16/2025 APPROVED MGIBSON
Note: 2/21/2025 - PREVIOUS INSPECTION NOTES WATER SERVICE NOT RAN YET
FOUND SURVEY APPROVED (OFFICE) 04/15/2025 APPROVED RRICKS
FOUND SURVEY APPROVED (OFFICE) 04/15/2025 APPROVED RRICKS
TIE BEAM / LINTEL 03/31/2025 APPROVED - AS NOTED MCONTRYMAN
Note: 3/31/25 Will check at next inspection 1. Window sill by kitchen sink is not mortared in. Changing windows size (3040SH, 35 1/2"x"x47 1/2" on plans). If size changes, will need engineered letter of approval
MONOLITHIC SLAB 03/05/2025 APPROVED MCONTRYMAN
Note: 3/4/2025 - PREVIOUS INSPECTION NOTES 3/4/25: 1). No Plans in box or on site. 2). 6mil plastic is blowing off in numerous areas. 3). Trash/debris in footers along with minor dirt cave in at left side (of garage?).
WATER METER INSTALLATION REQUEST 03/05/2025 APPROVED CBOWERMASTER
MONOLITHIC SLAB 03/04/2025 Disapproved - NO FEE RSIMS
Note: *** NOTES ADDED BY RSIMS 3/4/2025 2:30:00 PM *** 3/4/25: 1). No Plans in box or on site. 2). 6mil plastic is blowing off in numerous areas. 3). Trash/debris in footers along with minor dirt cave in at left side (of garage?).
PLUMBING 1ST ROUGH UNDERGROUND 02/21/2025 PARTIALLY APPROVED MGIBSON
Note: WATER SERVICE NOT RAN YET
GEOTECHNICAL REPORT APPROVAL (OFFICE USE) 02/20/2025 APPROVED PKNAPIK
BLD - BUILDING FINAL
ROW- PRE-APRON (PRE-POUR)
Note: 1/8/2026 - PREVIOUS INSPECTION NOTES 1/8/26 REVISED SITE PLAN NOW SHOWS UPPER DRIVEWAY AT RESIDENCE MEETING THE COPC PREPOUR STAND WIDTH. I AM PARTIALLY APPROVING YOU TO POUR DRIVEWAY AT STRUCTURE. YOU ARE REQUIRED TO CALL IN A SECONDARY PREPOUR INSPECTION FOR YOUR DRIVEWAY ENTRANCE APRON AT ROAD EDGE AND MITERED END SECTIONS ON YOUR CULVERT PIPE CROSSING INDICATED. BUILDER REFER TO CONCRETE (FRC) DRAWING 300,E RESIDENTIAL CULVERT DETAIL BEFORE POURING. . IF FIBERGLASS OPTION IS USED, BUILDER REQUIRED TO USE 3000 PSI CONCRETE REINFORCED WITH WWF 6X6.W1.4 MESH OR FIBERGLASS REINFORCED DOCUMENTATION OF THE ( FRC) CONTAINING THE FIBERGLASS MUST BE ATTACHED TO THE PERMIT PRIOR TO REQUESTING AN AFTER-POUR INSPECTION. 8.b. IF MESH OPTION IS USED, IT SHALL BE IN PLACE AT THE TIME OF THE PRE-POUR AT THE TIME OF THE INSPECTION READY TO POUR, IF RAIN PLEASE, BUILDER SHOULD DOUBLE CHECK SITE FOR ANY STANDING WATER. NO EXPANSION JOINTS ALLOWED, AT THE TIME OF THIS INSPECTION ALL MINIMUM COPC REQUIREMENTS ARE MET. BUILDER TO BE HELD RESPONSIBLE IF, FOR WHATEVER REASON, SITE CONDITIONS CHANGE OVER TIME AFTER THE INSPECTION. IT IS THE BUILDER'S RESPONSIBILITY TO ENSURE THAT NOTHING CHANGES AFTER THIS INSPECTION IS APPROVED 12/17/2025 - PREVIOUS INSPECTION NOTES 12/17/25 CONTACTED MARCEL CM AND LET HIM KNOW A NEW SITE PLAN NEEDS TO BE SUBMITTED FOR REVIEW AND APPROVAL BEFORE A PREPOUR INSPECTION CAN TAKE PLACE. 12/11/2025 - PREVIOUS INSPECTION NOTES 12/11/25 We will be meeting with builder to discuss how to move forward with this site. disapproving no fee
ROW - FINAL APRON (AFTER POUR)
ROW- FINAL SURVEY/GRADING CERTIFICATION
ROW FIELD SURVEY /GRADING CERTIFICATION
ROW - STORMWATER FINAL
U -UTILITY RESIDENTIAL FINAL

Review History

Department Status Date In Date Out
SW1 COMPLETE 12/31/2025 01/07/2026
Note: Released By: RODNEY RICKS - (386)986-4726 - RRICKS@PALMCOASTGOV.COM
ZON COMPLETE 12/18/2025 12/18/2025
Note: Released By: CINDY CHIRI-GONCALVES - (386)986-4737 - CGONCALVES@PALMCOASTGOV.COM
SW1 HOLD 12/18/2025 12/29/2025
Note: Held By: RODNEY RICKS - (386)986-4726 - RRICKS@PALMCOASTGOV.COM Please depict a grading plan depicting how the water is moving.
ENGIN1 COMPLETE 12/18/2025 12/29/2025
Note: Released By: RODNEY RICKS - (386)986-4726 - RRICKS@PALMCOASTGOV.COM After conversations with Engineering, no culvert will be required at the end of the driveway.
ZON HOLD 12/04/2025 12/04/2025
Note: Held By: CINDY CHIRI-GONCALVES - (386)986-4737 - CGONCALVES@PALMCOASTGOV.COM circular drives can't exceed 18' wide pleaseadjust plan accordingly
ENGIN1 HOLD 12/04/2025 12/11/2025
Note: Held By: RODNEY RICKS - (386)986-4726 - RRICKS@PALMCOASTGOV.COM No grading information on revised grading plan.
SW1 HOLD 12/04/2025 12/11/2025
Note: Held By: RODNEY RICKS - (386)986-4726 - RRICKS@PALMCOASTGOV.COM There is no grading information on the revised site plan. Please revise.
BLD COMPLETE 08/26/2025 08/29/2025
Note: Released By: PETER KNAPIK - (386)986-3783 - PKNAPIK@PALMCOASTGOV.COM
BLD HOLD 08/19/2025 08/22/2025
Note: Held By: PETER KNAPIK - (386)986-3783 - PKNAPIK@PALMCOASTGOV.COM Product Approval FL# 42251 not a sliding glass door FL# 243.3 not a single hung window FL# 239.1 not a fixed window
ELEC COMPLETE 08/19/2025 08/22/2025
Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM
MECH COMPLETE 06/30/2025 07/01/2025
Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM
ZON COMPLETE 04/15/2025 04/15/2025
Note: Released By: TRACEY DOAK - (386)986-3751 - TDOAK@PALMCOASTGOV.COM
ENGIN1 COMPLETE 04/15/2025 04/15/2025
Note: Released By: RODNEY RICKS - - RRICKS@PALMCOASTGOV.COM
ENGIN1 COMPLETE 04/15/2025 04/15/2025
Note: Released By: RODNEY RICKS - - RRICKS@PALMCOASTGOV.COM
BLD COMPLETE 02/20/2025 02/20/2025
Note: Released By: PETER KNAPIK - (386)986-3783 - PKNAPIK@PALMCOASTGOV.COM
BLD HOLD 02/18/2025 02/20/2025
Note: Held By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM 1. Need to upload certification letter.
ZON COMPLETE 12/30/2024 12/30/2024
Note: Released By: ALISHA MOBLEY - (386)986-3751 - AMOBLEY@PALMCOASTGOV.COM
ENGIN1 COMPLETE 12/30/2024 12/31/2024
Note: Released By: LEVI SALYERDS - (386)986-2326 - LSALYERDS@PALMCOASTGOV.COM
SW1 COMPLETE 12/30/2024 01/06/2025
Note: Released By: TIM BAKER - (386)986-4726 - TBAKER@PALMCOASTGOV.COM
ZON HOLD 12/26/2024 12/26/2024
Note: Held By: ALISHA MOBLEY - (386)986-3751 - AMOBLEY@PALMCOASTGOV.COM REPEAT COMMENT: Held By: SCOTT THOMAS - (386)986-3780 - STHOMAS@PALMCOASTGOV.COM ***REPEAT COMMENT** 1. CORRECT SITE PLAN/LANDSCAPE PLAN. SITE PLAN/LANDSCAPE PLANS USING 2 DIFFERENT TYPES MATERIAL FOR DRIVEWAY 2. SHOW TREES ON SITE PLAN SURROUNDING HOME. MUST HAVE SHADE TREES. MAKE SURE YOU SPECIFY TREES TYPES SO WE CAN VERIFY YOU HAVE THE REQUIRED AMOUNT OF SHADE AND UNDER STORY TREES 3. NEED A MINIMUM OF 16 PLANTINGS W/8 ALONG FRONT AND 4 ALONG EACH SIDE WRAPPING FRONT CORNERS 4. NEED SEPARATION BETWEEN FRONT ENTRY & DRIVE WAY FOR PLANTINGS HAVE NOT UPDATED THE SITE PLAN TO SHOW THIS 5. NEED ANOTHER FORM OF ARTICULATION ON ELEVATION
MECH COMPLETE 12/26/2024 12/26/2024
Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM
PLENV COMPLETE 12/26/2024 12/30/2024
Note: Released By: DYLAN RODRIGUEZ - - DRODRIGUEZ@PALMCOASTGOV.COM After action report was submitted and accepted by FWC meeting the requirements for 10.04.01 of the LDC. Staff suggests placing silt fence as soon as possible to prevent gopher tortoises from moving into the lot. If any gopher tortoises are located in the future further coordination may be necessary. In future submittals, acceptance email for after action report is required to be submitted.
CUSVC COMPLETE 12/17/2024 12/17/2024
Note: Released By: HALEIGH HAND - - HHAND@PALMCOASTGOV.COM Fees at this time are only for water
PLENV HOLD 12/03/2024 12/05/2024
Note: Held By: DYLAN RODRIGUEZ - - DRODRIGUEZ@PALMCOASTGOV.COM Staff conduced a site visit on 9/11/24 and found potentially Gopher Tortoise habitat. Please either provide a Gopher Tortoise survey by a QEP that shows no burrows are within 25ft of construction activities or a gopher tortoise survey and letter from a QEP stating there are no gopher tortoises on site. Gopher Tortoise relocation permit is attached and was reviewed. The after-action report will need to be submitted prior to hold release.
ZON HOLD 11/27/2024 12/03/2024
Note: Held By: SCOTT THOMAS - (386)986-3780 - STHOMAS@PALMCOASTGOV.COM ***REPEAT COMMENT** 1. CORRECT SITE PLAN/LANDSCAPE PLAN. SITE PLAN/LANDSCAPE PLANS USING 2 DIFFERENT TYPES MATERIAL 2. SHOW TREES ON SITE PLAN SURROUNDING HOME. STATE ON PLANS TREES ARE IN AREAS NOT BEING CLEARED 3. NEED A MINUMUM OF 6 PLANTINF W/8 ALONG FRONT AND 4 ALONG EACH SIDE WRAPPING CORNERS 4. NEED SEPARATION BETWEEN FRONT ENTRY & DRIVE WAY FOR PLANTINGS 5. NEED ANOTHER FORM OF ARTICULATION
MECH HOLD 11/27/2024 12/05/2024
Note: Held By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM duct layout needs to be signed by listed subcontractor
BLD COMPLETE 11/27/2024 12/06/2024
Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM
BADMIN COMPLETE 11/27/2024 12/06/2024
Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM
PLENV HOLD 11/27/2024 12/02/2024
Note: Held By: DYLAN RODRIGUEZ - - DRODRIGUEZ@PALMCOASTGOV.COM Staff conduced a site visit on 9/11/24 and found potentially Gopher Tortoise habitat. Please either provide a Gopher Tortoise survey by a QEP that shows no burrows are within 25ft of construction activities or a gopher tortoise survey and letter from a QEP stating there are no gopher tortoises on site. Gopher Tortoise relocation permit is attached and was reviewed. The after-action report will need to be submitted prior to hold release.
CUSVC HOLD 11/27/2024 12/10/2024
Note: Held By: HALEIGH HAND - - HHAND@PALMCOASTGOV.COM Sewer has not yet been approved for installation. Please contact Stephen Flanagan at 386-986-2354 or sflanagan@palmcoastgov.com and Rebecca Teixeira at 386-986-2355 or rteixeira@palmcoastgov.com.
BADMIN HOLD 09/04/2024 09/09/2024
Note: Held By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM 1. Provide geotechnical investigation report in accordance with Section 1803.2. Report to be conducted per Sections 1803.3 through 1803.5. Completed report shall comply with Section 1803.6. Report shall be signed and sealed by a Florida licensed professional engineer in accordance with F.S. 471.025 and Florida Administrative Code Sections 61G15-30.001 and 61G15-23.001 through .005. If report determines unsuitable sub-surface conditions or unsuitable soil conditions, then engineer shall provide a soils mitigation plan in order to ensure soils are suitable to receive the building's foundation. Report to include fill and compaction specifications and engineering inspection requirements. At conclusion of any soils mitigation work, engineer will be required to certify work was performed according to plans. Be advised, if the geotechnical report reveals any unsuitable soils and / or subsurface conditions, the first inspection for this permit (1st Rough / Underground Plumbing) will be HELD until such time as a report by the geotechnical engineer is submitted to the Building Division documenting that the soil mitigation work has been completed according to the engineer's plans and is now suitable for construction. Report must also include a record of all required compaction testing.
BLD HOLD 09/04/2024 09/07/2024
Note: Held By: JPI 1. Based on an internet inquiry, the following product approval number appears to have recently expired, please cure. FL 17676 (Windows - Single Hung non impact +35/-50)
CUSVC HOLD 09/04/2024 09/11/2024
Note: Held By: HALEIGH HAND - - HHAND@PALMCOASTGOV.COM Pending utility agreement for sewer connection
ELEC COMPLETE 09/04/2024 09/06/2024
Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM
ENGIN1 COMPLETE 09/04/2024 09/04/2024
Note: Released By: TIM BAKER - (386)986-4726 - TBAKER@PALMCOASTGOV.COM
GAS CANCEL 09/04/2024 09/05/2024
LOCATE COMPLETE 09/04/2024 09/11/2024
Note: Released By: CANDACE BOWERMASTER - - CBOWERMASTER@PALMCOASTGOV.COM
MECH HOLD 09/04/2024 09/06/2024
Note: Held By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM 1. Direction house faces on Energy Calcs does not match the site plan. Revise to match per R405.4.2.1 FBC Energy Conservation 2023 8Th Edition 2. Energy Calcs need to be signed by the owner/ owner agent below the preparer per R103.1.1.2 FBC Energy Conservation 2023 8Th edition
SW1 COMPLETE 09/04/2024 09/30/2024
Note: Released By: CARMELO MORALES - (386)986-4758 - CMORALES@PALMCOASTGOV.COM
ZON HOLD 09/04/2024 09/04/2024
Note: Held By: SCOTT THOMAS - (386)986-3780 - STHOMAS@PALMCOASTGOV.COM 1. CORRECT SITE PLAN/LANDSCAPE PLAN. SITE PLAN/LANDSCAPE PLANS USING 2 DIFFERENT TYPES MATERIAL 2. SHOW TREES ON SITE PLAN SURROUNDING HOME. STATE ON PLANS TREES ARE IN AREAS NOT BEING CLEARED 3. NEED A MINUMUM OF 6 PLANTINF W/8 ALONG FRONT AND 4 ALONG EACH SIDE WRAPPING CORNERS 4. NEED SEPARATION BETWEEN FRONT ENTRY & DRIVE WAY FOR PLANTINGS 5. NEED ANOTHER FORM OF ARTICULATION
SWALE COMPLETE 09/04/2024 12/09/2024
Note: Released By: TIM BAKER - (386)986-4726 - TBAKER@PALMCOASTGOV.COM
UTL COMPLETE 09/04/2024 09/09/2024
Note: Released By: LARRY FITZGERALD - (386)286-2041 - LFITZGERALD@PALMCOASTGOV.COM
PLENV HOLD 09/04/2024 09/11/2024
Note: Held By: DYLAN RODRIGUEZ - - DRODRIGUEZ@PALMCOASTGOV.COM Staff conduced a site visit on 9/11/24 and found potentially Gopher Tortoise habitat. Please either provide a Gopher Tortoise survey by a QEP that shows no burrows are within 25ft of construction activities or a gopher tortoise survey and letter from a QEP stating there are no gopher tortoises on site.

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
REINSPECTION RESIDENTIAL ¤40.00 06/27/2025
PEP TANK INSTALL ¤756.74 06/27/2025
WASTEWATER MAIN EXTENSION IMPA ¤2,385.00 06/27/2025
SEWER CAPITAL FACILITY ¤4,415.00 06/27/2025
WATER CAPITAL FACILITY FEE ¤4,351.14 01/07/2025
SITE PLAN 30 ¤30.00 01/07/2025
CONNECTION FEES ¤1,187.26 01/07/2025
SURCHARGE FS 533.721 ¤17.20 01/07/2025
SURCHARGE - FS 468.631 ¤25.81 01/07/2025
SW ENG - FOUNDATION SURVEY ¤20.00 01/07/2025
SW ENG INSPECTION 80 ¤80.00 01/07/2025
SW ENG PRE APRON ¤30.00 01/07/2025
SW ENG - REVIEW 20 ¤20.00 01/07/2025
SW ENG RES REVIEW 200 ¤200.00 01/07/2025
WATER- TURN ON ¤25.00 01/07/2025
ADJUSTMENT 10% (¤191.15) 01/07/2025
ADMINISTRATIVE RESIDENTIAL ¤30.00 01/07/2025
INSPECTION - RESIDENTIAL ¤1,465.75 01/07/2025
PLAN REVIEW - RESIDENTIAL ¤415.74 01/07/2025
FC IMPACT FEE EMS ¤62.00 01/07/2025
IMPACT FEE FIRE ¤434.51 01/07/2025
FC IMPACT FEE LAW ENFORCEMENT ¤218.00 01/07/2025
FC IMPACT FEE LIBRARY ¤268.00 01/07/2025
IMPACT FEE PARKS ¤1,828.01 01/07/2025
IMPACT FEE SCHOOL ¤5,450.00 01/07/2025
IMPACT FEE TRANSPORTATION ¤1,862.00 01/07/2025
WATER -IRRIGATION INSPECTION ¤25.00 01/07/2025
REINSPECTION RESIDENTIAL ¤40.00
REINSPECTION RESIDENTIAL ¤40.00
REINSPECTION RESIDENTIAL ¤40.00
CONTRACTOR CHANGE ¤20.00
CONTRACTOR CHANGE ¤20.00
Fees Total Due: ¤160.00 Total Paid: ¤25,451.01