Permit #2024090281

Permit Details

Status: COED

Total Square Footage: 30027 sqft
Block: 00000
Subdivision: 2334 - EVOLVE PALM COAST - SANDLAKE SUBDIVISION LOT 4
Job Phone: 304-694-7694
Location Address: 41 EVOLVE PKWY
Type: BM - BUILDING MULTI - APARTMENT
Issue Date: 09/26/2024
NOC: RECORDED
Applicant name: MATTHEW ADAM ROGERS
Owner: EVOLVE PALM COAST LLC

Address

2918-A MARTINVILLE ROAD

GREENSBORO, NC 27408

Lot: 0040
Contracted Stated Job Value: ¤1,650,000.00
Job Description: BLDG 700 - TYPE I - 41 EVOLVE PARKWAY (22 UNITS)
Type: CN
Original Permit #: 2024030358

Contractor

EVOLVE CONSTRUCTION OF FL LLC
Status Location Address State License Number Phone
INACTIVE

2018A MARTINSVILLE RD

GREENSBORO, NC 27408

CGC1532932 (Exp: 08/31/2026) 304-694-7694

Sub Contractors

PAUL LEONARD RICHARDS
Status Location Address State License Number Phone Fax
ACTIVE

671 BUSINESS PARK BLVD

WINTER GARDEN, FL 34787

CAC057235 (Exp: 08/31/2026) 407-877-8090 407-877-8479
TRACEY LYNN HYMAN-MONTEE
Status Location Address State License Number Phone Fax
ACTIVE

75 STUMPFIELD ROAD

PENSACOLA, FL 32503

CFC1430978 (Exp: 08/31/2026) 850-477-0388 850-477-0381
MARK ASSELIN
Status Location Address State License Number Phone
ACTIVE

3508 LENOX AVE

JACKSONVILLE, FL 32254

EC13009251 (Exp: 08/31/2026) 904-726-7966

Inspection History

Type Request Date Result Inspector
U - UTILITY COMMERCIAL FINAL 11/05/2025 FINAL APPROVED BWRIGHT
FIRE FINAL 11/04/2025 APPROVED RMARTIN
Note: New inspection due to canceled inspection 10/30/2025 - PREVIOUS INSPECTION NOTES 10/30/25 Plans call for 10 lb abc fire extinguishers on every floor, need to have lables at fire extinguisher cabinets, need to have extra heads and tool in fire riser room, need to mount FDC sign up off the ground at FDC 10/6/2025 - PREVIOUS INSPECTION NOTES 10/6/25 Need to have Fire Sprinkler and Fire Alarm finaled prior to Fire Final and additional inspections on building permit approved. 10/2/2025 - PREVIOUS INSPECTION NOTES Need to have fire sprinkler final, fire alarm final, and fire underground final complete prior to fire final.
EXTERIOR ARCHITECTURAL FEATURES 11/04/2025 APPROVED RPICATAGI
FIRE FINAL 11/03/2025 CANCELLED BY APPLICANT WEB
Note: 10/30/2025 - PREVIOUS INSPECTION NOTES 10/30/25 Plans call for 10 lb abc fire extinguishers on every floor, need to have lables at fire extinguisher cabinets, need to have extra heads and tool in fire riser room, need to mount FDC sign up off the ground at FDC 10/6/2025 - PREVIOUS INSPECTION NOTES 10/6/25 Need to have Fire Sprinkler and Fire Alarm finaled prior to Fire Final and additional inspections on building permit approved. 10/2/2025 - PREVIOUS INSPECTION NOTES Need to have fire sprinkler final, fire alarm final, and fire underground final complete prior to fire final.
FIRE FINAL 10/30/2025 Disapproved - NO FEE RMARTIN
Note: 10/30/25 Plans call for 10 lb abc fire extinguishers on every floor, need to have lables at fire extinguisher cabinets, need to have extra heads and tool in fire riser room, need to mount FDC sign up off the ground at FDC 10/6/2025 - PREVIOUS INSPECTION NOTES 10/6/25 Need to have Fire Sprinkler and Fire Alarm finaled prior to Fire Final and additional inspections on building permit approved. 10/2/2025 - PREVIOUS INSPECTION NOTES Need to have fire sprinkler final, fire alarm final, and fire underground final complete prior to fire final.
BUILDING FINAL 10/30/2025 FINAL APPROVED FWILLIS
U -UTILITY RESIDENTIAL FINAL 10/29/2025 FINAL APPROVED BWRIGHT
Note: Inspector Notes from Inspection 9035 Using Construction hydrant meter with backflow to irrigate, will soon switch to irrigating from the pond no cross connection was found
HORIZONTAL ASSEMB FINAL 10/20/2025 APPROVED FWILLIS
FRAMING 10/14/2025 APPROVED FWILLIS
Note: 3/17/2025 - PREVIOUS INSPECTION NOTES
FIRE FINAL 10/06/2025 Disapproved - NO FEE RMARTIN
Note: 10/6/25 Need to have Fire Sprinkler and Fire Alarm finaled prior to Fire Final and additional inspections on building permit approved. 10/2/2025 - PREVIOUS INSPECTION NOTES Need to have fire sprinkler final, fire alarm final, and fire underground final complete prior to fire final.
FIRE FINAL 10/02/2025 Disapproved - NO FEE RMARTIN
Note: Need to have fire sprinkler final, fire alarm final, and fire underground final complete prior to fire final.
ROOF SHEATHING / BRACE / TIE DOWN 10/01/2025 APPROVED FWILLIS
HORIZONTAL ASSEMB PENETRATIONS 10/01/2025 APPROVED FWILLIS
STOREFRONT 10/01/2025 CANCELLED BY INSPECTOR FWILLIS
U-CROSS CONNECTION 09/25/2025 APPROVED - AS NOTED BWRIGHT
Note: Using Construction hydrant meter with backflow to irrigate, will soon switch to irrigating from the pond no cross connection was found
U - SEWER TIE IN 09/25/2025 APPROVED MGIBSON
Note: New inspection due to canceled inspection Inspector Notes from Inspection 3080 5/7/2025 - PREVIOUS INSPECTION NOTES VENTS NOT TIED IN ON HUB DRAINS AT ALL UNITS ON TOP FLOOR IN MECHANICAL ROOMS , MULTIPLE LEAKS ON WATER DISTRIBUTION LINES , EXPANTION FITTING ON FIRST FLOOR LEAKING. CHECK ALL THAT APPLY. SHOCK ARRESTORS FOR DISHWASHERS IN ALL UNITS ARE INSIDE OF WALLS, SEAL ALL FLOOR PENITRATIONSWITH CONCREATE
ELECTRIC FINAL 09/23/2025 APPROVED RMARTIN
Note: 9/22/2025 - PREVIOUS INSPECTION NOTES Need GFCI protection on outlets in garage nec 210.8 A Need to lable outside A/C disconnects
PLUMBING FINAL 09/23/2025 APPROVED MGIBSON
Note: 9/22/2025 - PREVIOUS INSPECTION NOTES HOT WATER NEEDS TO BE WORKING
HVAC FINAL 09/23/2025 FINAL APPROVED CPISCITELLI
Note: 9/22/2025 - PREVIOUS INSPECTION NOTES
HVAC FINAL 09/22/2025 CANCELLED BY APPLICANT RMARTIN
PLUMBING FINAL 09/22/2025 PARTIALLY APPROVED MGIBSON
Note: HOT WATER NEEDS TO BE WORKING
ELECTRIC FINAL 09/22/2025 Disapproved - NO FEE RMARTIN
Note: Need GFCI protection on outlets in garage nec 210.8 A Need to lable outside A/C disconnects
PLUMBING FINAL 09/18/2025 CANCELLED BY APPLICANT WEB
INSULATION 09/16/2025 APPROVED FWILLIS
U - SEWER TIE IN 08/28/2025 CANCELLED BY APPLICANT WEB
Note: Inspector Notes from Inspection 3080 5/7/2025 - PREVIOUS INSPECTION NOTES VENTS NOT TIED IN ON HUB DRAINS AT ALL UNITS ON TOP FLOOR IN MECHANICAL ROOMS , MULTIPLE LEAKS ON WATER DISTRIBUTION LINES , EXPANTION FITTING ON FIRST FLOOR LEAKING. CHECK ALL THAT APPLY. SHOCK ARRESTORS FOR DISHWASHERS IN ALL UNITS ARE INSIDE OF WALLS, SEAL ALL FLOOR PENITRATIONSWITH CONCREATE
BLD - SEWER TIE IN 08/28/2025 APPROVED MGIBSON
ELECTRIC - EARLY POWER 08/13/2025 APPROVED MKRASKI
ELECTRIC - EARLY POWER 08/05/2025 CANCELLED BY APPLICANT WEB
Note: 7/18/2025 - PREVIOUS INSPECTION NOTES Will need revision on Service Grounding Change from water pipe and ground rod to ufer and revision on Unit main disconnect change, plans call for 100A and 125A are installed on all units. Will need to call back in when ready for power into the appartments, released power for only house panel that will need to be locked out at all times along with th other disconnects at the service.
STOREFRONT 07/30/2025 CANCELLED BY INSPECTOR KSANDOE
ELECTRIC - EARLY POWER 07/18/2025 PARTIALLY APPROVED RMARTIN
Note: Will need revision on Service Grounding Change from water pipe and ground rod to ufer and revision on Unit main disconnect change, plans call for 100A and 125A are installed on all units. Will need to call back in when ready for power into the appartments, released power for only house panel that will need to be locked out at all times along with th other disconnects at the service.
ELECTRIC - EARLY POWER 07/17/2025 CANCELLED BY APPLICANT WEB
FIREWALL FRAMING 07/14/2025 APPROVED FWILLIS
Note: 6/4/2025 - PREVIOUS INSPECTION NOTES GARAGE UNITS, FIRST FLOOR (A&B), AND HALLWAYS SEPARATING GARAGE AND UNITS. BUILDING #700.
FIREWALL FINAL 07/14/2025 APPROVED FWILLIS
FIREWALL FRAMING 06/04/2025 PARTIALLY APPROVED FWILLIS
Note: GARAGE UNITS, FIRST FLOOR (A&B), AND HALLWAYS SEPARATING GARAGE AND UNITS. BUILDING #700.
HORIZONTAL ASSEMB FRAMING 05/28/2025 APPROVED FWILLIS
HORIZONTAL ASSEMB DRYWALL 05/28/2025 APPROVED FWILLIS
Note: 5/28/25 - THREE FLOORS 4/23/2025 - PREVIOUS INSPECTION NOTES NAILS MISSING IN AREA BY THE STAIRS
HORIZONTAL ASSEMB FRAMING 05/23/2025 APPROVED FWILLIS
WINDOW NAILING 05/20/2025 APPROVED FWILLIS
Note: 5/20/25 - WINDOW NAILING #700 3/17/2025 - PREVIOUS INSPECTION NOTES Includes First Floor Doors Only. (All Windlows Three FLoors)
INSULATION 05/16/2025 APPROVED FWILLIS
Note: 5/16/25 - THIRD FLOOR WALLS ONLY INSULATION. Inspector Notes from Inspection 3443 5/14/25 "B" SIDE OF #700. 5/13/2025 - PREVIOUS INSPECTION NOTES BUILDING #700 THE "A" SIDE ALL THREE FLOORS.
FIREWALL PENETRATIONS 05/14/2025 APPROVED - AS NOTED FWILLIS
Note: 5/14/25 "B" SIDE OF #700. 5/13/2025 - PREVIOUS INSPECTION NOTES BUILDING #700 THE "A" SIDE ALL THREE FLOORS.
FIREWALL PENETRATIONS 05/13/2025 PARTIALLY APPROVED FWILLIS
Note: BUILDING #700 THE "A" SIDE ALL THREE FLOORS.
PLUMBING 2ND ROUGH 05/12/2025 APPROVED - AS NOTED MGIBSON
Note: 5/7/2025 - PREVIOUS INSPECTION NOTES VENTS NOT TIED IN ON HUB DRAINS AT ALL UNITS ON TOP FLOOR IN MECHANICAL ROOMS , MULTIPLE LEAKS ON WATER DISTRIBUTION LINES , EXPANTION FITTING ON FIRST FLOOR LEAKING. CHECK ALL THAT APPLY. SHOCK ARRESTORS FOR DISHWASHERS IN ALL UNITS ARE INSIDE OF WALLS, SEAL ALL FLOOR PENITRATIONSWITH CONCREATE
LATH/BRICK/WATER BARRIER 05/08/2025 APPROVED FWILLIS
PLUMBING 2ND ROUGH 05/07/2025 Disapproved - NO FEE MGIBSON
Note: VENTS NOT TIED IN ON HUB DRAINS AT ALL UNITS ON TOP FLOOR IN MECHANICAL ROOMS , MULTIPLE LEAKS ON WATER DISTRIBUTION LINES , EXPANTION FITTING ON FIRST FLOOR LEAKING. CHECK ALL THAT APPLY
PLUMBING 2ND ROUGH 05/05/2025 CANCELLED BY APPLICANT WEB
HORIZONTAL ASSEMB FRAMING 04/29/2025 APPROVED FWILLIS
Note: RC (Resilient Channel) INSPECTIONS THIRD FLOOR PAGE FE1A1.
INSULATION 04/25/2025 PARTIALLY APPROVED FWILLIS
Note: BATHROOM AREAS ON ALL FLOORS WHERE THERE IS A FIREWALL. INSULATION BOTH SIDES.
HORIZONTAL ASSEMB DRYWALL 04/23/2025 Disapproved - NO FEE FWILLIS
Note: NAILS MISSING IN AREA BY THE STAIRS
HVAC ROUGH 04/23/2025 APPROVED CPISCITELLI
Note: 4/22/2025 - PREVIOUS INSPECTION NOTES need to attach 2 garage fans and move a dryer box and tape one duct 4/21/2025 - PREVIOUS INSPECTION NOTES 3/13/2025 - PREVIOUS INSPECTION NOTES Inspected seams on all exhaust on all three floors
ELECTRIC 2ND ROUGH 04/23/2025 APPROVED RMARTIN
Note: 4/22/2025 - PREVIOUS INSPECTION NOTES 1st floor only, still need to schedule fire alarm and sprinkler rough
FIREWALL PENETRATIONS 04/23/2025 APPROVED FWILLIS
Note: FIRST, SECOND AND THIRD FLOOR, CABLES GOING THRU THE TOP PLATE ARE FIRE CAULKED. BATHROOM WALL ON BOTH SIDES OF THE BUILDING, EACH FLOOR ONLY.
ELECTRIC 2ND ROUGH 04/22/2025 PARTIALLY APPROVED RMARTIN
Note: 1st floor only, still need to schedule fire alarm and sprinkler rough
HVAC ROUGH 04/22/2025 PARTIALLY APPROVED CPISCITELLI
Note: need to attach 2 garage fans and move a dryer box and tape one duct 4/21/2025 - PREVIOUS INSPECTION NOTES 3/13/2025 - PREVIOUS INSPECTION NOTES Inspected seams on all exhaust on all three floors
HVAC ROUGH 04/21/2025 CANCELLED BY APPLICANT RMARTIN
Note: 3/13/2025 - PREVIOUS INSPECTION NOTES Inspected seams on all exhaust on all three floors
FIREWALL DRYWALL NAILING 03/26/2025 APPROVED FWILLIS
Note: SECOND LAYER OF 5/8. BREEZEWAY GARAGE SIDE.
FOUND SURVEY APPROVED (OFFICE) 03/25/2025 APPROVED DLEAP
FIREWALL DRYWALL NAILING 03/21/2025 APPROVED FWILLIS
Note: Building #700 Breezeway Garage side First layer.
LATH/BRICK/WATER BARRIER 03/18/2025 APPROVED FWILLIS
WINDOW NAILING 03/17/2025 PARTIALLY APPROVED FWILLIS
Note: Includes First Floor Doors Only. (All Windlows Three FLoors)
FRAMING 03/17/2025 CANCELLED BY APPLICANT FWILLIS
HVAC ROUGH 03/13/2025 PARTIALLY APPROVED CPISCITELLI
Note: Inspected seams on all exhaust on all three floors

Review History

Department Status Date In Date Out
BLD COMPLETE 10/03/2025 10/15/2025
Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM
BLD HOLD 09/25/2025 10/01/2025
Note: Held By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM 1. Submit the pictures that go along with the report
BLD COMPLETE 06/02/2025 06/18/2025
Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM
PLENG COMPLETE 03/25/2025 03/25/2025
Note: Released By: DENNIS R. LEAP, P.E. - (386)986-2482 - DLEAP@PALMCOASTGOV.COM
PLENG HOLD 03/12/2025 03/13/2025
Note: Held By: DENNIS R. LEAP, P.E. - (386)986-2482 - DLEAP@PALMCOASTGOV.COM 1. Label plan "FOUNDATION SURVEY" and not SPECIFIC PURPOSE SURVEY. 2. Highlight foundation for specific foundation being permitted for in this permit application.
BLD CANCEL 09/26/2024 09/26/2024
PLFM INFORMATION 09/13/2024 09/16/2024
Note: Marked INFORMATION By: JORDAN MYERS, C.F.M - (386)986-4789 - JMYERS@PALMCOASTGOV.COM Vertical construction is not authorized until floodplain requirements have been met.
ELEC COMPLETE 09/09/2024 09/13/2024
Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM
FI1 COMPLETE 09/09/2024 09/13/2024
Note: Released By: LEE MILLER - (386)986-3783 - WMILLER@PALMCOASTGOV.COM
GAS CANCEL 09/09/2024 09/13/2024
MECH COMPLETE 09/09/2024 09/13/2024
Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM
UD1 COMPLETE 09/09/2024 09/12/2024
Note: Released By: GREG DEGLER - (386)986-2384 - GDEGLER@PALMCOASTGOV.COM
PLUM COMPLETE 09/09/2024 09/13/2024
Note: Released By: PATRICK BUCKLEY - (386)986-3786 - PBUCKLEY@PALMCOASTGOV.COM
ARCHR COMPLETE 09/09/2024 09/16/2024
Note: Released By: RICHARD PICATAGI - (386)986-3760 - RPICATAGI@PALMCOASTGOV.COM
BLD COMPLETE 09/09/2024 09/13/2024
Note: Released By: PATRICK BUCKLEY - (386)986-3786 - PBUCKLEY@PALMCOASTGOV.COM
DSD COMPLETE 09/09/2024 09/09/2024
Note: Released By: BARBIE BEMBRY - (386)986-3780 - BUILDINGDIVISION@PALMCOASTGOV.COM

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
IMPACT FEE PARKS ¤39,621.78 05/23/2025
IMPACT FEE TRANSPORTATION ¤43,164.00 05/23/2025
IMPACT FEE FIRE ¤9,417.98 04/02/2025
FC IMPACT FEE LAW ENFORCEMENT ¤2,442.00 09/26/2024
FC IMPACT FEE LIBRARY ¤3,058.00 09/26/2024
IMPACT FEE SCHOOL ¤29,920.00 09/26/2024
ADJUSTMENT 10% (¤1,203.75) 09/26/2024
ADMINISTRATIVE - COMMERCIAL ¤75.00 09/26/2024
INSPECTION COMMERCIAL ¤11,550.00 09/26/2024
INSPECTION - FIRE COMMERCIAL ¤412.50 09/26/2024
FC IMPACT FEE EMS ¤704.00 09/26/2024
SURCHARGE FS 533.721 ¤108.34 09/26/2024
SURCHARGE - FS 468.631 ¤162.51 09/26/2024
SITE PLAN 30 ¤30.00 09/26/2024
Fees Total Due: ¤0.00 Total Paid: ¤139,462.36