I want to search for...
Permit #2024090416
Permit Details
Status: COED
| Total Square Footage: 30027 sqft |
| Block: 00000 |
| Subdivision: 2334 - EVOLVE PALM COAST - SANDLAKE SUBDIVISION LOT 4 |
| Job Phone: 304-694-7694 |
| Location Address: 43 EVOLVE PKWY |
| Type: BM - BUILDING MULTI - APARTMENT |
| Issue Date: 09/26/2024 |
| NOC: RECORDED |
| Applicant name: MATTHEW ADAM ROGERS |
| Owner: EVOLVE PALM COAST LLC |
|
Address 2918-A MARTINSVILLE ROAD GREENSBORO, NC 27408 |
| Lot: 0040 |
| Contracted Stated Job Value: ¤1,650,000.00 |
| Job Description: BLDG 900 - (22 UNITS) |
| Type: CN |
| Original Permit #: 2024030358 |
Contractor
EVOLVE CONSTRUCTION OF FL LLC
| Status | Location Address | State License Number | Phone |
| INACTIVE |
2018A MARTINSVILLE RD GREENSBORO, NC 27408 |
CGC1532932 (Exp: 08/31/2026) | 304-694-7694 |
Sub Contractors
PAUL LEONARD RICHARDS
| Status | Location Address | State License Number | Phone | Fax |
| ACTIVE |
671 BUSINESS PARK BLVD WINTER GARDEN, FL 34787 |
CAC057235 (Exp: 08/31/2026) | 407-877-8090 | 407-877-8479 |
TRACEY LYNN HYMAN-MONTEE
| Status | Location Address | State License Number | Phone | Fax |
| ACTIVE |
75 STUMPFIELD ROAD PENSACOLA, FL 32503 |
CFC1430978 (Exp: 08/31/2026) | 850-477-0388 | 850-477-0381 |
MARK ASSELIN
| Status | Location Address | State License Number | Phone |
| ACTIVE |
3508 LENOX AVE JACKSONVILLE, FL 32254 |
EC13009251 (Exp: 08/31/2026) | 904-726-7966 |
JOSHUA DAVID CADILLAC
| Status | Location Address | State License Number | Phone |
| CANCEL |
3264 S UNIVERSITY DRIVE MIRMAR, FL 33025 |
CCC1333894 (Exp: 08/31/2026) | 954-333-8697 |
Inspection History
| Type | Request Date | Result | Inspector |
| EXTERIOR ARCHITECTURAL FEATURES | 11/25/2025 | APPROVED | RPICATAGI |
| U - UTILITY COMMERCIAL FINAL | 11/19/2025 | FINAL APPROVED | BWRIGHT |
| BUILDING FINAL | 11/19/2025 | FINAL APPROVED | KSANDOE |
| FIRE FINAL | 11/18/2025 | APPROVED | RMARTIN |
| U -UTILITY RESIDENTIAL FINAL | 11/18/2025 | FINAL APPROVED | BWRIGHT |
| Note: Inspector Notes from Inspection 9035 IRR WITH POND WATER. NO CC | |||
| ELECTRIC FINAL | 11/13/2025 | APPROVED | JMUNSON |
| Note: 11/12/2025 - PREVIOUS INSPECTION NOTES 11/12/2025 - bottom 3 breakers are not labeled 11/10/2025 - PREVIOUS INSPECTION NOTES 1. Label all ODU disconnects 2. Label house panel 3. Label all breakers in house panel 4. Make sure panel schdule uploaded to Building Dept. matches what was installed in house panel | |||
| ELECTRIC FINAL | 11/12/2025 | Disapproved - NO FEE | JMUNSON |
| Note: 11/12/2025 - bottom 3 breakers are not labeled 11/10/2025 - PREVIOUS INSPECTION NOTES 1. Label all ODU disconnects 2. Label house panel 3. Label all breakers in house panel 4. Make sure panel schdule uploaded to Building Dept. matches what was installed in house panel | |||
| ELECTRIC FINAL | 11/10/2025 | Disapproved - NO FEE | MKRASKI |
| Note: 1. Label all ODU disconnects 2. Label house panel 3. Label all breakers in house panel 4. Make sure panel schdule uploaded to Building Dept. matches what was installed in house panel | |||
| HORIZONTAL ASSEMB PENETRATIONS | 11/07/2025 | APPROVED | KSANDOE |
| HORIZONTAL ASSEMB FINAL | 11/07/2025 | APPROVED | KSANDOE |
| U-CROSS CONNECTION | 11/05/2025 | APPROVED - AS NOTED | BWRIGHT |
| Note: IRR WITH POND WATER. NO CC | |||
| PLUMBING FINAL | 11/04/2025 | APPROVED - AS NOTED | MGIBSON |
| Note: NEED HARD CAP- ON 3'' IN FIRE ROOM AND NEED VACUUME BREAKERS ON BOTH HOUSE HOSE BIBS BEFORE BUILDING FINAL 10/10/2025 - PREVIOUS INSPECTION NOTES SPOKE WITH RICH RUSSO | |||
| FRAMING | 10/29/2025 | APPROVED | FWILLIS |
| Note: 3/17/2025 - PREVIOUS INSPECTION NOTES | |||
| HVAC FINAL | 10/15/2025 | FINAL APPROVED | CPISCITELLI |
| PLUMBING FINAL | 10/10/2025 | CANCELLED BY APPLICANT | MGIBSON |
| Note: SPOKE WITH RICH RUSSO | |||
| FIREWALL PENETRATIONS | 10/07/2025 | APPROVED | FWILLIS |
| ROOF SHEATHING / BRACE / TIE DOWN | 10/06/2025 | APPROVED | FWILLIS |
| Note: INSPECTION OF THE ROOF COMPLETION. | |||
| U - SEWER TIE IN | 10/03/2025 | APPROVED | MGIBSON |
| INSULATION | 09/17/2025 | APPROVED | FWILLIS |
| ELECTRIC - EARLY POWER | 09/17/2025 | APPROVED - AS NOTED | MKRASKI |
| Note: Emailed FPL @ 1:30pm | |||
| BLD - SEWER TIE IN | 08/28/2025 | APPROVED | MGIBSON |
| WINDOW NAILING | 08/08/2025 | APPROVED | KSANDOE |
| Note: 3/17/2025 - PREVIOUS INSPECTION NOTES Windows Only, Three Floors. | |||
| STOREFRONT | 08/01/2025 | CANCELLED BY INSPECTOR | KSANDOE |
| FIREWALL FRAMING | 07/14/2025 | APPROVED | FWILLIS |
| FIREWALL FINAL | 07/14/2025 | APPROVED | FWILLIS |
| FIREWALL PENETRATIONS | 07/02/2025 | CANCELLED BY APPLICANT | WEB |
| FIREWALL DRYWALL NAILING | 07/01/2025 | APPROVED | FWILLIS |
| INSULATION | 06/23/2025 | APPROVED | KSANDOE |
| Note: 6/20/2025 - PREVIOUS INSPECTION NOTES 6/20/25 - BUILDING #900...INSPECTED A SIDE ALL THREE FLOORS. INSULATION INSPECTION. B SIDE, INSPECTED SECOND AND THIRD FLOORS ONLY . INSULATION INSPECTION. WILL DO FIRST FLOOR NEXT TIME. 6/2/2025 - PREVIOUS INSPECTION NOTES 6/2/25 - INSULATION ON END UNITS EACH FLOOR BEHIND THE SHOWER ONLY. 5/30/2025 11:29:58 AM- PREVIOUS INSPECTION NOTES 05/30/25 INSULATION INSPECTION WILL NOT BE APPROVED UNTIL STRUCTURAL INSPECTION REPORTS FOR INSPECTIONS BY TERRACON ENGINEERING HAVE BEEN UPLOADED TO THE PERMIT RECORD. DO NOT INSTALL DRYWALL UNTIL INSULATION INSPECTION HAS BEEN APPROVED. 5/28/2025 - PREVIOUS INSPECTION NOTES NO INSULATION INSTALLED | |||
| INSULATION | 06/20/2025 | PARTIALLY APPROVED | FWILLIS |
| Note: 6/20/25 - BUILDING #900...INSPECTED A SIDE ALL THREE FLOORS. INSULATION INSPECTION. B SIDE, INSPECTED SECOND AND THIRD FLOORS ONLY . INSULATION INSPECTION. WILL DO FIRST FLOOR NEXT TIME. 6/2/2025 - PREVIOUS INSPECTION NOTES 6/2/25 - INSULATION ON END UNITS EACH FLOOR BEHIND THE SHOWER ONLY. 5/30/2025 11:29:58 AM- PREVIOUS INSPECTION NOTES 05/30/25 INSULATION INSPECTION WILL NOT BE APPROVED UNTIL STRUCTURAL INSPECTION REPORTS FOR INSPECTIONS BY TERRACON ENGINEERING HAVE BEEN UPLOADED TO THE PERMIT RECORD. DO NOT INSTALL DRYWALL UNTIL INSULATION INSPECTION HAS BEEN APPROVED. 5/28/2025 - PREVIOUS INSPECTION NOTES NO INSULATION INSTALLED | |||
| HORIZONTAL ASSEMB FRAMING | 06/17/2025 | APPROVED | FWILLIS |
| HORIZONTAL ASSEMB DRYWALL | 06/16/2025 | APPROVED | FWILLIS |
| Note: 6/10/2025 - PREVIOUS INSPECTION NOTES | |||
| FIREWALL PENETRATIONS | 06/12/2025 | APPROVED | FWILLIS |
| Note: 6/12/25 - CORNER UNITS EACH FLOOR BEHIND THE SHOWER STALL. ALSO PENERTRATIONS TOP PLATE FRAMING EACH FLOOR. 6/11/2025 - PREVIOUS INSPECTION NOTES | |||
| FIREWALL PENETRATIONS | 06/11/2025 | PARTIALLY APPROVED | FWILLIS |
| HORIZONTAL ASSEMB FRAMING | 06/11/2025 | CANCELLED BY APPLICANT | WEB |
| HORIZONTAL ASSEMB DRYWALL | 06/10/2025 | PARTIALLY APPROVED | FWILLIS |
| PLUMBING 2ND ROUGH | 06/09/2025 | APPROVED - AS NOTED | MGIBSON |
| Note: WALKED WITH PLUMBER AND POINTED OUT MIN, DEFICIENCES | |||
| INSULATION | 06/02/2025 | PARTIALLY APPROVED | FWILLIS |
| Note: 6/2/25 - INSULATION ON END UNITS EACH FLOOR BEHIND THE SHOWER ONLY. 5/30/2025 11:29:58 AM- PREVIOUS INSPECTION NOTES 05/30/25 INSULATION INSPECTION WILL NOT BE APPROVED UNTIL STRUCTURAL INSPECTION REPORTS FOR INSPECTIONS BY TERRACON ENGINEERING HAVE BEEN UPLOADED TO THE PERMIT RECORD. DO NOT INSTALL DRYWALL UNTIL INSULATION INSPECTION HAS BEEN APPROVED. 5/28/2025 - PREVIOUS INSPECTION NOTES NO INSULATION INSTALLED | |||
| INSULATION | 05/30/2025 | Disapproved - NO FEE | PBUCKLEY |
| Note: 05/30/25 INSULATION INSPECTION WILL NOT BE APPROVED UNTIL STRUCTURAL INSPECTION REPORTS FOR INSPECTIONS BY TERRACON ENGINEERING HAVE BEEN UPLOADED TO THE PERMIT RECORD. DO NOT INSTALL DRYWALL UNTIL INSULATION INSPECTION HAS BEEN APPROVED. 5/28/2025 - PREVIOUS INSPECTION NOTES NO INSULATION INSTALLED | |||
| HVAC ROUGH | 05/29/2025 | APPROVED | CPISCITELLI |
| Note: 5/28/2025 - PREVIOUS INSPECTION NOTES 5/9/2025 - PREVIOUS INSPECTION NOTES inspected exhaust and fresh air seams to be able to wrap | |||
| HVAC ROUGH | 05/28/2025 | CANCELLED BY APPLICANT | RMARTIN |
| Note: 5/9/2025 - PREVIOUS INSPECTION NOTES inspected exhaust and fresh air seams to be able to wrap | |||
| LATH/BRICK/WATER BARRIER | 05/28/2025 | APPROVED | FWILLIS |
| INSULATION | 05/28/2025 | Disapproved - NO FEE | FWILLIS |
| Note: NO INSULATION INSTALLED | |||
| FIREWALL PENETRATIONS | 05/20/2025 | APPROVED | FWILLIS |
| HORIZONTAL ASSEMB FRAMING | 05/12/2025 | APPROVED | FWILLIS |
| Note: BREEZEWAY AND THIRD FLOOR | |||
| HVAC ROUGH | 05/09/2025 | PARTIALLY APPROVED | CPISCITELLI |
| Note: inspected exhaust and fresh air seams to be able to wrap | |||
| ELECTRIC 2ND ROUGH | 05/08/2025 | APPROVED | RMARTIN |
| FIREWALL DRYWALL NAILING | 03/27/2025 | APPROVED | FWILLIS |
| Note: SECOND LAYER | |||
| FIREWALL DRYWALL NAILING | 03/26/2025 | APPROVED | FWILLIS |
| Note: 3/26/25 - BREEZEWAY | |||
| LATH/BRICK/WATER BARRIER | 03/26/2025 | APPROVED | FWILLIS |
| Note: 3/26/25 - BREEZEWAY 3/18/2025 - PREVIOUS INSPECTION NOTES NOT READY FOR INSPECTION NOT COMPLETE. | |||
| FOUND SURVEY APPROVED (OFFICE) | 03/25/2025 | APPROVED | DLEAP |
| LATH/BRICK/WATER BARRIER | 03/18/2025 | Disapproved - NO FEE | FWILLIS |
| Note: NOT READY FOR INSPECTION NOT COMPLETE. | |||
| WINDOW NAILING | 03/17/2025 | PARTIALLY APPROVED | FWILLIS |
| Note: Windows Only, Three Floors. | |||
| FRAMING | 03/17/2025 | CANCELLED BY APPLICANT | FWILLIS |
Review History
| Department | Status | Date In | Date Out |
| BLD | COMPLETE | 10/02/2025 | 10/09/2025 |
| Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM | |||
| BLD | COMPLETE | 06/02/2025 | 06/18/2025 |
| Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM | |||
| BLD | COMPLETE | 04/22/2025 | 04/24/2025 |
| Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM | |||
| MECH | COMPLETE | 04/09/2025 | 04/11/2025 |
| Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM | |||
| PLENG | COMPLETE | 03/25/2025 | 03/25/2025 |
| Note: Released By: DENNIS R. LEAP, P.E. - (386)986-2482 - DLEAP@PALMCOASTGOV.COM | |||
| PLENG | HOLD | 03/12/2025 | 03/13/2025 |
| Note: Held By: DENNIS R. LEAP, P.E. - (386)986-2482 - DLEAP@PALMCOASTGOV.COM 1. Label plan "FOUNDATION SURVEY" and not SPECIFIC PURPOSE SURVEY. 2. Highlight foundation for specific foundation being permitted for in this permit application. | |||
| BLD | CANCEL | 09/26/2024 | 09/26/2024 |
| PLFM | INFORMATION | 09/13/2024 | 09/16/2024 |
| Note: Marked INFORMATION By: JORDAN MYERS, C.F.M - (386)986-4789 - JMYERS@PALMCOASTGOV.COM Vertical construction is not authorized until floodplain requirements have been met. | |||
| MECH | COMPLETE | 09/10/2024 | 09/13/2024 |
| Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM | |||
| UD1 | COMPLETE | 09/10/2024 | 09/12/2024 |
| Note: Released By: GREG DEGLER - (386)986-2384 - GDEGLER@PALMCOASTGOV.COM | |||
| PLUM | COMPLETE | 09/10/2024 | 09/13/2024 |
| Note: Released By: PATRICK BUCKLEY - (386)986-3786 - PBUCKLEY@PALMCOASTGOV.COM | |||
| ARCHR | COMPLETE | 09/10/2024 | 09/16/2024 |
| Note: Released By: RICHARD PICATAGI - (386)986-3760 - RPICATAGI@PALMCOASTGOV.COM | |||
| BLD | COMPLETE | 09/10/2024 | 09/13/2024 |
| Note: Released By: PATRICK BUCKLEY - (386)986-3786 - PBUCKLEY@PALMCOASTGOV.COM | |||
| DSD | COMPLETE | 09/10/2024 | 09/12/2024 |
| Note: Released By: DAMARIS RAMIREZ - (386)986-3750 - DRAMIREZ@PALMCOASTGOV.COM | |||
| ELEC | COMPLETE | 09/10/2024 | 09/13/2024 |
| Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM | |||
| FI1 | COMPLETE | 09/10/2024 | 09/13/2024 |
| Note: Released By: LEE MILLER - (386)986-3783 - WMILLER@PALMCOASTGOV.COM | |||
| GAS | CANCEL | 09/10/2024 | 09/13/2024 |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| IMPACT FEE PARKS | ¤39,621.78 | 05/23/2025 |
| IMPACT FEE TRANSPORTATION | ¤43,164.00 | 05/23/2025 |
| IMPACT FEE FIRE | ¤9,417.98 | 04/02/2025 |
| FC IMPACT FEE LAW ENFORCEMENT | ¤2,442.00 | 09/26/2024 |
| FC IMPACT FEE LIBRARY | ¤3,058.00 | 09/26/2024 |
| IMPACT FEE SCHOOL | ¤29,920.00 | 09/26/2024 |
| ADJUSTMENT 10% | (¤1,203.75) | 09/26/2024 |
| ADMINISTRATIVE - COMMERCIAL | ¤75.00 | 09/26/2024 |
| INSPECTION COMMERCIAL | ¤11,550.00 | 09/26/2024 |
| INSPECTION - FIRE COMMERCIAL | ¤412.50 | 09/26/2024 |
| FC IMPACT FEE EMS | ¤704.00 | 09/26/2024 |
| SURCHARGE FS 533.721 | ¤108.34 | 09/26/2024 |
| SURCHARGE - FS 468.631 | ¤162.51 | 09/26/2024 |
| SITE PLAN 30 | ¤30.00 | 09/26/2024 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤139,462.36 |