Permit #2024090452

Permit Details

Status: EXPIRED

Parcel Id: 07-11-31-7027-00100-0100
Block: 00100
Subdivision: 7027 -
Job Phone: 386-597-3728
Location Address: 28 WOODSTONE LN
Type: ME - MECHANICAL
Issue Date: 09/11/2024
NOC: Unknown
Applicant name: ROBERT BRUCE DAVENPORT
Owner: JAROSZ CALVIN & JULIE H&W

Address

28 WOODSTONE LANE

PALM COAST, FL 32164

Lot: 0100
Contracted Stated Job Value: ¤6,500.00
Job Description: HVAC LIKE FOR LIKE TONNAGE
Type: CN

Contractor

COMFORT AIRE LLC
Status Location Address State License Number Phone
ACTIVE

250 PALM COAST PKWY NE 607-210

PALM COAST, FL 32137

CAC1819719 (Exp: 08/31/2026) 386-401-9222

Inspection History

Type Request Date Result Inspector
HVAC FINAL 12/26/2024 Disapproved - NO FEE MKRASKI
Note: 12/26/24 1. Truss's have been screwed into for all thread to hang AHU in attic, A engineered truss repair letter is required and needs to be uploaded and approved by Building Dept. before calling in for re-inspection 10/3/24 1. Ducts not connected to AHU properly FBCR M1601.4.1 2. AHU pan in attic must be 3'' larger then AHU Entire unit 3. Plywood can not be used as a stand under AHU and is molded 9/16/2024 - PREVIOUS INSPECTION NOTES 1. Ducts not connected to AHU properly FBCR M1601.4.1 2. AHU pan in attic must be 3'' larger then AHU 3. Romex requires proper connector going into AHU disconnect NEC 334.15 4. NOTICE TO OWNER UNIT IN ATTIC POSTED AT PANEL FBCR EC R 403.3.6 5. High voltage romex has been stripped back going in AHU disconnect exposin wiring, Sheathing must extend 1/4'' into disconnect NEC 334
FINAL - BUILDING MISC 12/26/2024 CANCELLED BY INSPECTOR MKRASKI
HVAC FINAL 10/03/2024 Disapproved - NO FEE MKRASKI
Note: 10/3/24 1. Ducts not connected to AHU properly FBCR M1601.4.1 (appears that the wrong size elbow was use) Must be properly sealed and connected per manufacter specs 2. AHU pan in attic must be 3'' larger then AHU Entire unit FBC M1411.3.1 3. Plywood can not be used as a stand under AHU and is molded FBC M1411.3.1.2 9/16/2024 - PREVIOUS INSPECTION NOTES 1. Ducts not connected to AHU properly FBCR M1601.4.1 2. AHU pan in attic must be 3'' larger then AHU 3. Romex requires proper connector going into AHU disconnect NEC 334.15 4. NOTICE TO OWNER UNIT IN ATTIC POSTED AT PANEL FBCR EC R 403.3.6 5. High voltage romex has been stripped back going in AHU disconnect exposin wiring, Sheathing must extend 1/4'' into disconnect NEC 334
HVAC FINAL 09/16/2024 Disapproved -FEE REQUIRED MKRASKI
Note: 1. Ducts not connected to AHU properly FBCR M1601.4.1 2. AHU pan in attic must be 3'' larger then AHU 3. Romex requires proper connector going into AHU disconnect NEC 334.15 4. NOTICE TO OWNER UNIT IN ATTIC POSTED AT PANEL FBCR EC R 403.3.6 5. High voltage romex has been stripped back going in AHU disconnect exposin wiring, Sheathing must extend 1/4'' into disconnect NEC 334
HVAC FINAL
Note: 12/26/2024 - PREVIOUS INSPECTION NOTES 12/26/24 1. Truss's have been screwed into for all thread to hang AHU in attic, A engineered truss repair letter is required and needs to be uploaded and approved by Building Dept. before calling in for re-inspection 10/3/24 1. Ducts not connected to AHU properly FBCR M1601.4.1 2. AHU pan in attic must be 3'' larger then AHU Entire unit 3. Plywood can not be used as a stand under AHU and is molded 9/16/2024 - PREVIOUS INSPECTION NOTES 1. Ducts not connected to AHU properly FBCR M1601.4.1 2. AHU pan in attic must be 3'' larger then AHU 3. Romex requires proper connector going into AHU disconnect NEC 334.15 4. NOTICE TO OWNER UNIT IN ATTIC POSTED AT PANEL FBCR EC R 403.3.6 5. High voltage romex has been stripped back going in AHU disconnect exposin wiring, Sheathing must extend 1/4'' into disconnect NEC 334

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
REINSPECTION RESIDENTIAL ¤40.00 10/01/2024
SURCHARGE FS 533.721 ¤2.00 09/11/2024
SURCHARGE - FS 468.631 ¤2.00 09/11/2024
ADJUSTMENT 10% (¤9.00) 09/11/2024
ADMINISTRATIVE RESIDENTIAL ¤30.00 09/11/2024
INSPECTION - MECHANICAL ¤60.00 09/11/2024
Fees Total Due: ¤0.00 Total Paid: ¤125.00