I want to search for...

Permit #2024100958

Permit Details

Status: FINAL

Parcel Id: 15-11-31-2832-00000-0690
Block: 00000
Subdivision: -
Job Phone: 904-610-4499
Location Address: 75 LAGARE ST
Type: GEN - GENERATOR
Issue Date: 11/04/2024
NOC: RECORDED
Applicant name: ANTHONY MODESTO SCHREIBER
Owner: BEIER OPHELIA FAIR & & EDWARD W&H

Address

75 LAGARE ST

PALM COAST, FL 32137

Lot: 0690
Contracted Stated Job Value: ¤17,179.00
Job Description: INSTALLATION OF 24KW GENERATOR WITH ATS AND 250 GALLON UG LP TANK
Type: CN

Contractor

AA SERVICE AND REPAIR NORTH FLORIDA AC
Status Location Address State License Number Phone Fax
INACTIVE

PO BOX 57896

JACKSONVILLE, FL 32258

CMC1249701 (Exp: 08/31/2026) 904-610-4499 904-288-8164

Sub Contractors

ANTHONY MODESTO SCHREIBER
Status Location Address State License Number Phone Fax
ACTIVE

PO BOX 57896

JACKSONVILLE, FL 32258

CFC1427665 (Exp: 08/31/2026) 904-626-8199 904-288-8164

Inspection History

Type Request Date Result Inspector
ELECTRIC FINAL 03/10/2025 FINAL APPROVED MKRASKI
ELECTRIC FINAL 01/24/2025 Disapproved -FEE REQUIRED HCAMACHO
Note: 1. Emergency stuff needs to be installed. NEC 445.18(D) 1/21/2025 - PREVIOUS INSPECTION NOTES 12/11/2024 - PREVIOUS INSPECTION NOTES 12/10/2024 - PREVIOUS INSPECTION NOTES Via phone call 12-11-24 1. External shut off needs to be installed. 2. Co2 detector will need to be installed in bedroom next to generator. Due to generator exhaust is within 10' of soffit to bedroom.
ELECTRIC FINAL 01/21/2025 CANCELLED BY APPLICANT HCAMACHO
Note: 12/11/2024 - PREVIOUS INSPECTION NOTES 12/10/2024 - PREVIOUS INSPECTION NOTES Via phone call 12-11-24 1. External shut off needs to be installed. 2. Co2 detector will need to be installed in bedroom next to generator. Due to generator exhaust is within 10' of soffit to bedroom.
ELECTRIC FINAL 12/11/2024 Disapproved - NO FEE BTAYLOR
Note: 12/10/2024 - PREVIOUS INSPECTION NOTES Via phone call 12-11-24 1. External shut off needs to be installed. 2. Co2 detector will need to be installed in bedroom next to generator. Due to generator exhaust is within 10' of soffit to bedroom.
ELECTRIC FINAL 12/10/2024 CANCELLED BY APPLICANT MKRASKI
Note: Via phone call
GAS FINAL 12/10/2024 APPROVED - AS NOTED MKRASKI
Note: Clean up yard where tank was buried, no tripping hazards, Check at start up
GAS ROUGH 11/21/2024 APPROVED - AS NOTED MGIBSON
Note: WHEN U/G TANK WAS INSTALLED SEWER MAIN WAS BROKEN APP. 10'

Review History

Department Status Date In Date Out
ZON COMPLETE 11/19/2024 11/19/2024
Note: Released By: ALISHA MOBLEY - (386)986-3751 - AMOBLEY@PALMCOASTGOV.COM
GAS COMPLETE 11/13/2024 11/15/2024
Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM
ZON HOLD 11/13/2024 11/13/2024
Note: Held By: TRACEY DOAK - (386)986-3751 - TDOAK@PALMCOASTGOV.COM On revised site plan, pease provide setback to front property line as well, you only indicated the side
ELEC COMPLETE 10/30/2024 11/04/2024
Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM
ELEC HOLD 10/22/2024 10/28/2024
Note: Held By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM 1. Submit wire size going to the generator.
ZON COMPLETE 10/22/2024 10/22/2024
Note: Released By: TRACEY DOAK - (386)986-3751 - TDOAK@PALMCOASTGOV.COM
GAS COMPLETE 10/22/2024 10/28/2024
Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
REINSPECTION RESIDENTIAL ¤40.00 03/07/2025
SURCHARGE FS 533.721 ¤2.00 11/04/2024
SURCHARGE - FS 468.631 ¤2.00 11/04/2024
SITE PLAN 15 ¤15.00 11/04/2024
ADJUSTMENT 10% (¤12.25) 11/04/2024
ADMINISTRATIVE RESIDENTIAL ¤30.00 11/04/2024
INSPECTION - RESIDENTIAL ¤60.00 11/04/2024
PLAN REVIEW - MISC 32.50 ¤32.50 11/04/2024
Fees Total Due: ¤0.00 Total Paid: ¤169.25