I want to search for...
Permit #2024100958
Permit Details
Status: FINAL
| Parcel Id: 15-11-31-2832-00000-0690 |
| Block: 00000 |
| Subdivision: - |
| Job Phone: 904-610-4499 |
| Location Address: 75 LAGARE ST |
| Type: GEN - GENERATOR |
| Issue Date: 11/04/2024 |
| NOC: RECORDED |
| Applicant name: ANTHONY MODESTO SCHREIBER |
| Owner: BEIER OPHELIA FAIR & & EDWARD W&H |
|
Address 75 LAGARE ST PALM COAST, FL 32137 |
| Lot: 0690 |
| Contracted Stated Job Value: ¤17,179.00 |
| Job Description: INSTALLATION OF 24KW GENERATOR WITH ATS AND 250 GALLON UG LP TANK |
| Type: CN |
Contractor
AA SERVICE AND REPAIR NORTH FLORIDA AC
| Status | Location Address | State License Number | Phone | Fax |
| INACTIVE |
PO BOX 57896 JACKSONVILLE, FL 32258 |
CMC1249701 (Exp: 08/31/2026) | 904-610-4499 | 904-288-8164 |
Sub Contractors
ANTHONY MODESTO SCHREIBER
| Status | Location Address | State License Number | Phone | Fax |
| ACTIVE |
PO BOX 57896 JACKSONVILLE, FL 32258 |
CFC1427665 (Exp: 08/31/2026) | 904-626-8199 | 904-288-8164 |
Inspection History
| Type | Request Date | Result | Inspector |
| ELECTRIC FINAL | 03/10/2025 | FINAL APPROVED | MKRASKI |
| ELECTRIC FINAL | 01/24/2025 | Disapproved -FEE REQUIRED | HCAMACHO |
| Note: 1. Emergency stuff needs to be installed. NEC 445.18(D) 1/21/2025 - PREVIOUS INSPECTION NOTES 12/11/2024 - PREVIOUS INSPECTION NOTES 12/10/2024 - PREVIOUS INSPECTION NOTES Via phone call 12-11-24 1. External shut off needs to be installed. 2. Co2 detector will need to be installed in bedroom next to generator. Due to generator exhaust is within 10' of soffit to bedroom. | |||
| ELECTRIC FINAL | 01/21/2025 | CANCELLED BY APPLICANT | HCAMACHO |
| Note: 12/11/2024 - PREVIOUS INSPECTION NOTES 12/10/2024 - PREVIOUS INSPECTION NOTES Via phone call 12-11-24 1. External shut off needs to be installed. 2. Co2 detector will need to be installed in bedroom next to generator. Due to generator exhaust is within 10' of soffit to bedroom. | |||
| ELECTRIC FINAL | 12/11/2024 | Disapproved - NO FEE | BTAYLOR |
| Note: 12/10/2024 - PREVIOUS INSPECTION NOTES Via phone call 12-11-24 1. External shut off needs to be installed. 2. Co2 detector will need to be installed in bedroom next to generator. Due to generator exhaust is within 10' of soffit to bedroom. | |||
| ELECTRIC FINAL | 12/10/2024 | CANCELLED BY APPLICANT | MKRASKI |
| Note: Via phone call | |||
| GAS FINAL | 12/10/2024 | APPROVED - AS NOTED | MKRASKI |
| Note: Clean up yard where tank was buried, no tripping hazards, Check at start up | |||
| GAS ROUGH | 11/21/2024 | APPROVED - AS NOTED | MGIBSON |
| Note: WHEN U/G TANK WAS INSTALLED SEWER MAIN WAS BROKEN APP. 10' |
Review History
| Department | Status | Date In | Date Out |
| ZON | COMPLETE | 11/19/2024 | 11/19/2024 |
| Note: Released By: ALISHA MOBLEY - (386)986-3751 - AMOBLEY@PALMCOASTGOV.COM | |||
| GAS | COMPLETE | 11/13/2024 | 11/15/2024 |
| Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM | |||
| ZON | HOLD | 11/13/2024 | 11/13/2024 |
| Note: Held By: TRACEY DOAK - (386)986-3751 - TDOAK@PALMCOASTGOV.COM On revised site plan, pease provide setback to front property line as well, you only indicated the side | |||
| ELEC | COMPLETE | 10/30/2024 | 11/04/2024 |
| Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM | |||
| ELEC | HOLD | 10/22/2024 | 10/28/2024 |
| Note: Held By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM 1. Submit wire size going to the generator. | |||
| ZON | COMPLETE | 10/22/2024 | 10/22/2024 |
| Note: Released By: TRACEY DOAK - (386)986-3751 - TDOAK@PALMCOASTGOV.COM | |||
| GAS | COMPLETE | 10/22/2024 | 10/28/2024 |
| Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| REINSPECTION RESIDENTIAL | ¤40.00 | 03/07/2025 |
| SURCHARGE FS 533.721 | ¤2.00 | 11/04/2024 |
| SURCHARGE - FS 468.631 | ¤2.00 | 11/04/2024 |
| SITE PLAN 15 | ¤15.00 | 11/04/2024 |
| ADJUSTMENT 10% | (¤12.25) | 11/04/2024 |
| ADMINISTRATIVE RESIDENTIAL | ¤30.00 | 11/04/2024 |
| INSPECTION - RESIDENTIAL | ¤60.00 | 11/04/2024 |
| PLAN REVIEW - MISC 32.50 | ¤32.50 | 11/04/2024 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤169.25 |