I want to search for...
Permit #2024100974
Permit Details
Status: FINAL
| Parcel Id: 07-11-31-7034-00720-0090 |
| Block: 00720 |
| Subdivision: - |
| Job Phone: 904-610-4499 |
| Location Address: 6 EGAN DR |
| Type: GEN - GENERATOR |
| Issue Date: 11/04/2024 |
| NOC: RECORDED |
| Applicant name: ANTHONY MODESTO SCHREIBER |
| Owner: BERARDINO JOSEPH & SHIRLEY H&W |
|
Address 6 EGAN DRIVE PALM COAST, FL 32164 |
| Lot: 0090 |
| Contracted Stated Job Value: ¤14,900.00 |
| Job Description: INSTALLATION OF 22KW GENERATOR WITH ATS ALONG WITH 2-120LP TANKS ABOVE GROUND |
| Type: CN |
Contractor
AA SERVICE AND REPAIR NORTH FLORIDA AC
| Status | Location Address | State License Number | Phone | Fax |
| INACTIVE |
PO BOX 57896 JACKSONVILLE, FL 32258 |
CMC1249701 (Exp: 08/31/2026) | 904-610-4499 | 904-288-8164 |
Sub Contractors
ANTHONY MODESTO SCHREIBER
| Status | Location Address | State License Number | Phone | Fax |
| ACTIVE |
PO BOX 57896 JACKSONVILLE, FL 32258 |
CFC1427665 (Exp: 08/31/2026) | 904-626-8199 | 904-288-8164 |
Inspection History
| Type | Request Date | Result | Inspector |
| ELECTRIC FINAL | 04/22/2025 | FINAL APPROVED | MCONTRYMAN |
| Note: 1/21/2025 - PREVIOUS INSPECTION NOTES 1-21-25 1. No disconect between panel and generator. NEC 445.18 12/16/2024 - PREVIOUS INSPECTION NOTES 12/16/2024 1. No disconect between panel and generator. NEC 445.18 2. No carbon monoxide detectors installed in the house as per notes. Required due to perforated soffit. 12/13/2024 - PREVIOUS INSPECTION NOTES 12/13/2024 1. Service technician needs to be on site for start up. 2. No disconect between panel and generator. NEC 445.18 | |||
| ELECTRIC FINAL | 01/21/2025 | Disapproved - NO FEE | BTAYLOR |
| Note: 1-21-25 1. No disconect between panel and generator. NEC 445.18 12/16/2024 - PREVIOUS INSPECTION NOTES 12/16/2024 1. No disconect between panel and generator. NEC 445.18 2. No carbon monoxide detectors installed in the house as per notes. Required due to perforated soffit. 12/13/2024 - PREVIOUS INSPECTION NOTES 12/13/2024 1. Service technician needs to be on site for start up. 2. No disconect between panel and generator. NEC 445.18 | |||
| ELECTRIC FINAL | 12/16/2024 | Disapproved -FEE REQUIRED | PKNAPIK |
| Note: 12/16/2024 1. No disconect between panel and generator. NEC 445.18 2. No carbon monoxide detectors installed in the house as per notes. Required due to perforated soffit. 12/13/2024 - PREVIOUS INSPECTION NOTES 12/13/2024 1. Service technician needs to be on site for start up. 2. No disconect between panel and generator. NEC 445.18 | |||
| ELECTRIC FINAL | 12/13/2024 | Disapproved - NO FEE | PKNAPIK |
| Note: 12/13/2024 1. Service technician needs to be on site for start up. 2. No disconect between panel and generator. NEC 445.18 | |||
| GAS FINAL | 12/10/2024 | APPROVED | MGIBSON |
| GAS ROUGH | 11/07/2024 | APPROVED | MGIBSON |
Review History
| Department | Status | Date In | Date Out |
| BADMIN | INFORMATION | 11/04/2024 | 11/04/2024 |
| Note: Marked INFORMATION By: CINDY CHIRI-GONCALVES - (386)986-4737 - CGONCALVES@PALMCOASTGOV.COM please provide a legible copy | |||
| ELEC | COMPLETE | 10/30/2024 | 11/04/2024 |
| Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM | |||
| ELEC | HOLD | 10/23/2024 | 10/28/2024 |
| Note: Held By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM 1. Submit wire sizes for generator. | |||
| ZON | COMPLETE | 10/23/2024 | 10/23/2024 |
| Note: Released By: TRACEY DOAK - (386)986-3751 - TDOAK@PALMCOASTGOV.COM | |||
| GAS | COMPLETE | 10/23/2024 | 10/28/2024 |
| Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| ADJUSTMENT 10% | (¤12.25) | 11/04/2024 |
| ADMINISTRATIVE RESIDENTIAL | ¤30.00 | 11/04/2024 |
| INSPECTION - RESIDENTIAL | ¤60.00 | 11/04/2024 |
| PLAN REVIEW - MISC 32.50 | ¤32.50 | 11/04/2024 |
| SURCHARGE FS 533.721 | ¤2.00 | 11/04/2024 |
| SURCHARGE - FS 468.631 | ¤2.00 | 11/04/2024 |
| SITE PLAN 15 | ¤15.00 | 11/04/2024 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤129.25 |