I want to search for...
Permit #2024101258
Permit Details
Status: FINAL
| Parcel Id: 07-11-31-7028-00450-0200 |
| Block: 00450 |
| Subdivision: - |
| Job Phone: 904-437-0869 |
| Location Address: 98 PORT ROYAL DR |
| Type: GEN - GENERATOR |
| Issue Date: 11/07/2024 |
| NOC: RECORDED |
| Applicant name: EDUARD REUT |
| Owner: BURGOS BILLIE-JO & JOSEPH ANTHONY H&W |
|
Address 98 PORT ROYAL DR PALM COAST, FL 32164 |
| Lot: 0200 |
| Contracted Stated Job Value: ¤16,000.00 |
| Job Description: Installation generator and gas tank 250 Ug LP |
| Type: CN |
Contractor
FLORIDA POWER & AUTOMATION INC
| Status | Location Address | State License Number | Phone |
| ACTIVE |
94 EDWARD DRIVE PALM COAST, FL 32164 |
ER13016194 (Exp: 08/31/2026) | 904-437-0869 |
Sub Contractors
JAMES DOUGLAS II
| Status | Location Address | State License Number | Phone |
| ACTIVE |
357 SUNSET AVE HOLLY HILL, FL 32117 |
21340 (Exp: 08/31/2026) | 386-236-8005 |
Inspection History
| Type | Request Date | Result | Inspector |
| ELECTRIC FINAL | 12/18/2024 | FINAL APPROVED | PKNAPIK |
| Note: 12/17/2024 - PREVIOUS INSPECTION NOTES 12/17/24: Generator run test complete and approved. 1). Generator exhaust is located within 10ft of a bedroom window and/or a fully vented soffit. Therefore smoke detectors in both bedrooms on the generator side require combination detectors at a minimum. These will need to remain interconnected and will need to be tested during re-inspection. FBC-M1905.2.5 exceptions 1, 2 and 3. | |||
| ELECTRIC FINAL | 12/17/2024 | Disapproved - NO FEE | RSIMS |
| Note: *** NOTES ADDED BY RSIMS 12/17/2024 10:52:53 AM *** 12/17/24: Generator run test complete and approved. 1). Generator exhaust is located within 10ft of a bedroom window and/or a fully vented soffit. Therefore smoke detectors in both bedrooms on the generator side require combination detectors at a minimum. These will need to remain interconnected and will need to be tested during re-inspection. FBC-M1905.2.5 exceptions 1, 2 and 3. | |||
| GAS FINAL | 12/17/2024 | APPROVED | RSIMS |
| GAS ROUGH | 12/09/2024 | APPROVED | MGIBSON |
| Note: 12/3/2024 - PREVIOUS INSPECTION NOTES NEED SITE TUBES FOR DEPTH | |||
| GAS ROUGH | 12/03/2024 | Disapproved - NO FEE | MGIBSON |
| Note: NEED SITE TUBES FOR DEPTH |
Review History
| Department | Status | Date In | Date Out |
| ELEC | COMPLETE | 10/28/2024 | 11/04/2024 |
| Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM | |||
| ZON | COMPLETE | 10/28/2024 | 10/29/2024 |
| Note: Released By: ALISHA MOBLEY - (386)986-3751 - AMOBLEY@PALMCOASTGOV.COM | |||
| GAS | COMPLETE | 10/28/2024 | 11/04/2024 |
| Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| ADJUSTMENT 10% | (¤12.25) | 11/07/2024 |
| ADMINISTRATIVE RESIDENTIAL | ¤30.00 | 11/07/2024 |
| INSPECTION - RESIDENTIAL | ¤60.00 | 11/07/2024 |
| PLAN REVIEW - MISC 32.50 | ¤32.50 | 11/07/2024 |
| SURCHARGE FS 533.721 | ¤2.00 | 11/07/2024 |
| SURCHARGE - FS 468.631 | ¤2.00 | 11/07/2024 |
| SITE PLAN 15 | ¤15.00 | 11/07/2024 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤129.25 |