Permit #2024101259
Permit Details
Status: FINAL
| Parcel Id: 07-11-31-7006-00090-0100 |
| Block: 00090 |
| Subdivision: - |
| Job Phone: 904-437-0869 |
| Location Address: 19 FLARESTONE CT |
| Type: GEN - GENERATOR |
| Issue Date: 11/15/2024 |
| NOC: RECORDED |
| Applicant name: EDUARD REUT |
| Owner: MARION MARTIN JAMES & TRACY J H&W |
|
Address 19 FLARESTONE COURT PALM COAST, FL 32137 |
| Lot: 0100 |
| Contracted Stated Job Value: ¤16,865.00 |
| Job Description: Installation generator and gas tank 250 Ug LP |
| Type: CN |
Contractor
FLORIDA POWER & AUTOMATION INC
| Status | Location Address | State License Number | Phone |
| ACTIVE |
94 EDWARD DRIVE PALM COAST, FL 32164 |
ER13016194 (Exp: 08/31/2026) | 904-437-0869 |
Sub Contractors
JAMES DOUGLAS II
| Status | Location Address | State License Number | Phone |
| ACTIVE |
357 SUNSET AVE HOLLY HILL, FL 32117 |
21340 (Exp: 08/31/2026) | 386-236-8005 |
Inspection History
| Type | Request Date | Result | Inspector |
| ELECTRIC FINAL | 02/25/2025 | FINAL APPROVED | HCAMACHO |
| ELECTRIC FINAL | 02/20/2025 | Disapproved - NO FEE | HCAMACHO |
| Note: NEC 445.18 DISCONNECTING MEANS | |||
| GAS FINAL | 02/19/2025 | APPROVED - AS NOTED | MGIBSON |
| Note: CHECK FOR SCREEN AT TERMINATION OF REGULATOR VENT AT ELECTRICAL FINAL | |||
| GAS ROUGH | 02/11/2025 | APPROVED | MGIBSON |
| GAS ROUGH | 02/03/2025 | CANCELLED BY APPLICANT | WEB |
Review History
| Department | Status | Date In | Date Out |
| GAS | COMPLETE | 12/11/2024 | 12/16/2024 |
| Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM | |||
| ZON | COMPLETE | 12/11/2024 | 12/12/2024 |
| Note: Released By: ALISHA MOBLEY - (386)986-3751 - AMOBLEY@PALMCOASTGOV.COM | |||
| GAS | COMPLETE | 11/15/2024 | 11/15/2024 |
| Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM | |||
| GAS | HOLD | 11/07/2024 | 11/14/2024 |
| Note: Held By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM Provide note on plans that generator exhaust must be minimum 10ft from any opening into the building per FBC Residential 2023 8Th edition M1905.2.5. If using the exception to 5ft, carbon monoxide detectors will be inspected on generator final. (Second Request) | |||
| ZON | COMPLETE | 11/07/2024 | 11/07/2024 |
| Note: Released By: TRACEY DOAK - (386)986-3751 - TDOAK@PALMCOASTGOV.COM | |||
| PLFM | COMPLETE | 10/29/2024 | 11/05/2024 |
| Note: Released By: JORDAN MYERS, C.F.M - (386)986-4789 - JMYERS@PALMCOASTGOV.COM According to the Site Plan and FEMA FIRMs, the generator will not fall inside the SFHA. No elevation certificate will be required. | |||
| ELEC | COMPLETE | 10/28/2024 | 11/04/2024 |
| Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM | |||
| ZON | COMPLETE | 10/28/2024 | 10/29/2024 |
| Note: Released By: TRACEY DOAK - (386)986-3751 - TDOAK@PALMCOASTGOV.COM | |||
| GAS | HOLD | 10/28/2024 | 11/04/2024 |
| Note: Held By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM Provide note on plans that generator exhaust must be minimum 10ft from any opening into the building per FBC Residential 2023 8Th edition M1905.2.5. If using the exception to 5ft, carbon monoxide detectors will be inspected on generator final. |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| ADJUSTMENT 10% | (¤12.25) | 11/15/2024 |
| ADMINISTRATIVE RESIDENTIAL | ¤30.00 | 11/15/2024 |
| INSPECTION - RESIDENTIAL | ¤60.00 | 11/15/2024 |
| PLAN REVIEW - MISC 32.50 | ¤32.50 | 11/15/2024 |
| SURCHARGE FS 533.721 | ¤2.00 | 11/15/2024 |
| SURCHARGE - FS 468.631 | ¤2.00 | 11/15/2024 |
| SITE PLAN 15 | ¤15.00 | 11/15/2024 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤129.25 |