Permit #2024101434
Permit Details
Status: FINAL
| Block: 00000 |
| Subdivision: 2334 - EVOLVE PALM COAST - SANDLAKE SUBDIVISION LOT 4 |
| Job Phone: 407-949-2393 |
| Location Address: 47 EVOLVE PKWY |
| Type: FS - FIRE SPRINKLER WET COMMERCIAL |
| Issue Date: 04/23/2025 |
| NOC: Unknown |
| Applicant name: ARTHUR BATEMAN |
| Owner: EVOLVE PALM COAST LLC |
|
Address 2918-A MARTINVILLE ROAD GREENSBORO, NC 27408 |
| Lot: 0040 |
| Contracted Stated Job Value: ¤33,100.00 |
| Job Description: Bldg 1000 wet pipe system of automatic sprinklers |
| Type: CN |
Contractor
PRECISION FIRE SYSTEMS, INC
| Status | Location Address | State License Number | Phone |
| ACTIVE |
152 STEEPLE CHASE CIRCLE SANFORD, FL 32771 |
FPC13-000123 (Exp: 06/30/2026) | 321-363-1560 |
Inspection History
| Type | Request Date | Result | Inspector |
| FIRE SPRINKLER 1ST ROUGH | 12/17/2025 | APPROVED | RMARTIN |
| FIRE SPRINKLER FINAL | 12/17/2025 | FINAL APPROVED | RMARTIN |
| FIRE SPRINKLER HYDROSTATIC TEST | 06/05/2025 | APPROVED | RMARTIN |
Review History
| Department | Status | Date In | Date Out |
| FI1 | COMPLETE | 03/20/2025 | 04/02/2025 |
| Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM | |||
| BADMIN | INFORMATION | 03/13/2025 | 03/13/2025 |
| Note: Marked INFORMATION By: MICHELLE RAMOS - (386)986-3780 - MRAMOS@PALMCOASTGOV.COM Please rename your file names. Example FP-2 = FP-2 no names or numbers | |||
| FI1 | HOLD | 10/31/2024 | 11/13/2024 |
| Note: Held By: LEE MILLER - (386)986-3783 - WMILLER@PALMCOASTGOV.COM Please provide a written response to each comment below in a response letter and provide clouded response changes on plan sheets and add page locations for each response. 1. Plans submitted cannot be uploaded as one file. Each sheet must be a separate page and names according to the document requirements on the permit portal page for review. http://docs.palmcoastgov.com/departments/building/online/document-requirements.pdf 2. Please provide type and location of Bell alarm per NFPA 13-R 8.1.7 (14) 3. Please provide pressure gauges with shutoff on supply and system side and show in riser diagram per NFPA 13-R 6.12.1 and 6.12.2 4. A local water flow alarm shall be provided on all sprinkler systems per NFPA 13-R 6.16 (please identify the flow alarm in the legend once the legend is provided). 5. 7.3.3* Garages that are accessible only from a single dwelling unit shall be considered as part of that dwelling unit. 7.3.3.1 Garages that meet the criteria of 7.3.3 shall be protected in accordance with one of the following: (1) Use of a residential sprinkler in accordance with Section 7.1 (2) Use of an extended coverage sprinkler discharging water not less than its listed flow rate for light hazard (3) Quick-response spray sprinkler at light hazard spacing in accordance with NFPA 13 designed to discharge at 0.05 gpm/ft2 (2.04 mm/min) density (please identify method of garage protection via sambal once a legend has been provided or other means of showing method as appropriate). 6. Rack Storage... Please confirm the calculations where made based on simultaneous operation of the most hydraulically remote eight sprinklers. Per NFPA 13, 16.3.2.7.7 7. Please provide method of freeze protection per nfpa 13r section 6.7.2 8. Please provide legend for sprinkler type and orientation etc. | |||
| UD1 | COMPLETE | 10/31/2024 | 11/05/2024 |
| Note: Released By: GREG DEGLER - (386)986-2384 - GDEGLER@PALMCOASTGOV.COM |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| ADJUSTMENT 10% | (¤54.64) | 04/23/2025 |
| ADMINISTRATIVE - COMMERCIAL | ¤75.00 | 04/23/2025 |
| INSPECTION - FIRE COMMERCIAL | ¤80.40 | 04/23/2025 |
| PLAN REVIEW - COMMERCIAL | ¤391.00 | 04/23/2025 |
| SURCHARGE FS 533.721 | ¤4.92 | 04/23/2025 |
| SURCHARGE - FS 468.631 | ¤7.38 | 04/23/2025 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤504.06 |