Permit #2024101436

Permit Details

Status: FINAL

Block: 00000
Subdivision: 2334 - EVOLVE PALM COAST - SANDLAKE SUBDIVISION LOT 4
Job Phone: 407-949-2393
Location Address: 70 EVOLVE PKWY
Type: FS - FIRE SPRINKLER WET COMMERCIAL
Issue Date: 04/23/2025
NOC: RECORDED
Applicant name: ARTHUR BATEMAN
Owner: EVOLVE PALM COAST LLC

Address

2918-A MARTINVILLE ROAD

GREENSBORO, NC 27408

Lot: 0040
Contracted Stated Job Value: ¤33,100.00
Job Description: Bldg 1200 wet pipe system of automatic sprinklers
Type: CN

Contractor

PRECISION FIRE SYSTEMS, INC
Status Location Address State License Number Phone
ACTIVE

152 STEEPLE CHASE CIRCLE

SANFORD, FL 32771

FPC13-000123 (Exp: 06/30/2026) 321-363-1560

Inspection History

Type Request Date Result Inspector
FIRE SPRINKLER FINAL 01/26/2026 FINAL APPROVED RMARTIN
FIRE SPRINKLER 1ST ROUGH 07/16/2025 APPROVED RMARTIN
FIRE SPRINKLER HYDROSTATIC TEST 06/20/2025 APPROVED RMARTIN

Review History

Department Status Date In Date Out
FI1 COMPLETE 03/20/2025 04/02/2025
Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM
FI1 HOLD 10/31/2024 11/13/2024
Note: Held By: LEE MILLER - (386)986-3783 - WMILLER@PALMCOASTGOV.COM Please provide a written response to each comment below in a response letter and provide clouded response changes on plan sheets and add page locations for each response. 1. Plans submitted cannot be uploaded as one file. Each sheet must be a separate page and names according to the document requirements on the permit portal page for review. http://docs.palmcoastgov.com/departments/building/online/document-requirements.pdf 2. Please provide type and location of Bell alarm per NFPA 13-R 8.1.7 (14) 3. Please provide pressure gauges with shutoff on supply and system side and show in riser diagram per NFPA 13-R 6.12.1 and 6.12.2 4. A local water flow alarm shall be provided on all sprinkler systems per NFPA 13-R 6.16 (please identify the flow alarm in the legend once the legend is provided). 5. 7.3.3* Garages that are accessible only from a single dwelling unit shall be considered as part of that dwelling unit. 7.3.3.1 Garages that meet the criteria of 7.3.3 shall be protected in accordance with one of the following: (1) Use of a residential sprinkler in accordance with Section 7.1 (2) Use of an extended coverage sprinkler discharging water not less than its listed flow rate for light hazard (3) Quick-response spray sprinkler at light hazard spacing in accordance with NFPA 13 designed to discharge at 0.05 gpm/ft2 (2.04 mm/min) density (please identify method of garage protection via sambal once a legend has been provided or other means of showing method as appropriate). 6. Rack Storage... Please confirm the calculations where made based on simultaneous operation of the most hydraulically remote eight sprinklers. Per NFPA 13, 16.3.2.7.7 7. Please provide method of freeze protection per nfpa 13r section 6.7.2 8. Please provide legend for sprinkler type and orientation etc.
UD1 COMPLETE 10/31/2024 11/05/2024
Note: Released By: GREG DEGLER - (386)986-2384 - GDEGLER@PALMCOASTGOV.COM

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
ADJUSTMENT 10% (¤54.64) 04/23/2025
ADMINISTRATIVE - COMMERCIAL ¤75.00 04/23/2025
INSPECTION - FIRE COMMERCIAL ¤80.40 04/23/2025
PLAN REVIEW - COMMERCIAL ¤391.00 04/23/2025
SURCHARGE FS 533.721 ¤4.92 04/23/2025
SURCHARGE - FS 468.631 ¤7.38 04/23/2025
Fees Total Due: ¤0.00 Total Paid: ¤504.06