Status: FINAL

Parcel Id: 07-11-31-7030-00080-0010
Block: 00080
Subdivision: -
Job Phone: 719-717-0211
Location Address: 23 RAELAND LN
Type: GEN - GENERATOR
Issue Date: 11/21/2024
NOC: Unknown
Applicant name: JOHN THOMAS BONACCORSO
Owner: THOMAS JOHN E & SUSAN C H&W LIFE ESTATE

Address

23 RAELAND LANE

PALM COAST, FL 32164

Lot: 0010
Contracted Stated Job Value: ¤4,800.00
Job Description: 22 KW Generator and 200-amp Transfer Switch
Type: CN

Contractor

BONACCORSO ELECTRIC SERVICE TECHNOLOGY LLC
Status Location Address State License Number Phone
ACTIVE

62 FOREST HILL DR

PALM COAST, FL 32137

EC0002298 (Exp: 08/31/2026) 719-717-0211

Inspection History

Type Request Date Result Inspector
ELECTRIC FINAL 03/14/2025 FINAL APPROVED RMARTIN
Note: 2/18/2025 - PREVIOUS INSPECTION NOTES #1-not emergency disconnect install . #2- not combination smoke and carbon monoxide detector install on bedroom on side wall by generator . Electrician installer need to be on side for next inspection power was disconnect from house , unit did not work , owner start tuning breakers on and off , , owner call electrician and they start using profanity turn inspector . unit turn on after several attents from owner
ELECTRIC FINAL 02/18/2025 Disapproved -FEE REQUIRED CVANSTRAHLEN
Note: #1-not emergency disconnect install . #2- not combination smoke and carbon monoxide detector install on bedroom on side wall by generator . Electrician installer need to be on side for next inspection power was disconnect from house , unit did not work , owner start tuning breakers on and off , , owner call electrician and they start using profanity turn inspector . unit turn on after several attents from owner

Review History

Department Status Date In Date Out
ZON COMPLETE 11/18/2024 11/19/2024
Note: Released By: ALISHA MOBLEY - (386)986-3751 - AMOBLEY@PALMCOASTGOV.COM
ELEC COMPLETE 11/18/2024 11/19/2024
Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM
ELEC HOLD 11/06/2024 11/14/2024
Note: Held By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM 1. Provide note on plans that generator exhaust must be minimum 10ft from any opening into the building per FBC Residential 2023 8Th edition M1905.2.5. If using the exception to 5ft, carbon monoxide detectors will be inspected on generator final.
ZON HOLD 11/06/2024 11/07/2024
Note: Held By: TRACEY DOAK - (386)986-3751 - TDOAK@PALMCOASTGOV.COM Site plan must always show setbacks from proposed generator to front, side and rear property lines - noting that the generator cannot be located in the platted easement. In this case, there is a 10' platted easement on the left side so the setback of the generator must be at least 10' from the property line.

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
ADJUSTMENT 10% (¤12.25) 11/21/2024
ADMINISTRATIVE RESIDENTIAL ¤30.00 11/21/2024
INSPECTION - RESIDENTIAL ¤60.00 11/21/2024
PLAN REVIEW - MISC 32.50 ¤32.50 11/21/2024
SURCHARGE FS 533.721 ¤2.00 11/21/2024
SURCHARGE - FS 468.631 ¤2.00 11/21/2024
SITE PLAN 15 ¤15.00 11/21/2024
Fees Total Due: ¤0.00 Total Paid: ¤129.25