Permit #2024121089

Permit Details

Status: FINAL

Parcel Id: 07-11-31-7012-00140-0400
Total Square Footage: 3305 sqft
Block: 00140
Subdivision: 7012 -
Job Phone: 321-439-6423
Location Address: 80 BARRINGTON DR
Type: ME - MECHANICAL
Issue Date: 12/30/2024
NOC: Unknown
Applicant name: JACOB ALI ANZANI
Owner: LAMBERSON JAMES REID & JUDITH ELAINE LAMBERSON TRU

Address

80 BARRINGTON DRIVE

PALM COAST, FL 32137

Lot: 0400
Contracted Stated Job Value: ¤9,800.00
Job Description: HVAC CO like for like
Type: CN

Contractor

BLUE LINE ROOFING
Status Location Address State License Number Phone
INACTIVE

881 BARTON BOULEVARD

ROCKLEDGE, FL 32955

CAC1821980 (Exp: 08/31/2026) 321-439-6423

Inspection History

Type Request Date Result Inspector
HVAC FINAL 02/18/2025 FINAL APPROVED JSTEWART
Note: 2/6/2025 - PREVIOUS INSPECTION NOTES *** NOTES ADDED BY JSTEWART 2/6/2025 2:35:38 PM *** Condensor and Air Handler are not Listed of being compatible,(Lookup of model Numbers), will need to swap air handler to match Condensor. does not meet 14.30 seer requiremnet. (Mixed equipment). FBEC C501.6 1/22/2025 - PREVIOUS INSPECTION NOTES *** NOTES ADDED BY JSTEWART 1/22/2025 12:14:06 PM *** 1. Please seal supply plenum at AHU, Tape used is not holding loss of Air/heat is high. FBCM.603.1 2. Please revise AHRI cert to match equipment installed. FBC [A] 107.4 3. Please change breaker for ODU requires 40amp max, 50amp is installed. MFBC 1303 4. Please secure Liquid tight (power) at disconnect (within 12" of entrance to box. NEC 334.30 5. Please verify Mixed equipment is compatible in Voltage, terms of capacity, warranty, etc. (ties in with the correct AHRI certification)
HVAC FINAL 02/06/2025 Disapproved -FEE REQUIRED JSTEWART
Note: *** NOTES ADDED BY JSTEWART 2/6/2025 2:35:38 PM *** Condensor and Air Handler are not Listed of being compatible,(Lookup of model Numbers), will need to swap air handler to match Condensor. does not meet 14.30 seer requiremnet. (Mixed equipment). FBEC C501.6 1/22/2025 - PREVIOUS INSPECTION NOTES *** NOTES ADDED BY JSTEWART 1/22/2025 12:14:06 PM *** 1. Please seal supply plenum at AHU, Tape used is not holding loss of Air/heat is high. FBCM.603.1 2. Please revise AHRI cert to match equipment installed. FBC [A] 107.4 3. Please change breaker for ODU requires 40amp max, 50amp is installed. MFBC 1303 4. Please secure Liquid tight (power) at disconnect (within 12" of entrance to box. NEC 334.30 5. Please verify Mixed equipment is compatible in Voltage, terms of capacity, warranty, etc. (ties in with the correct AHRI certification)
HVAC FINAL 01/22/2025 Disapproved -FEE REQUIRED JSTEWART
Note: *** NOTES ADDED BY JSTEWART 1/22/2025 12:14:06 PM *** 1. Please seal supply plenum at AHU, Tape used is not holding loss of Air/heat is high. FBCM.603.1 2. Please revise AHRI cert to match equipment installed. FBC [A] 107.4 3. Please change breaker for ODU requires 40amp max, 50amp is installed. MFBC 1303 4. Please secure Liquid tight (power) at disconnect (within 12" of entrance to box. NEC 334.30 5. Please verify Mixed equipment is compatible in Voltage, terms of capacity, warranty, etc. (ties in with the correct AHRI certification)

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
REINSPECTION RESIDENTIAL ¤40.00 02/14/2025
REINSPECTION RESIDENTIAL ¤40.00 01/24/2025
SURCHARGE FS 533.721 ¤2.00 12/30/2024
SURCHARGE - FS 468.631 ¤2.00 12/30/2024
ADJUSTMENT 10% (¤9.00) 12/30/2024
ADMINISTRATIVE RESIDENTIAL ¤30.00 12/30/2024
INSPECTION - MECHANICAL ¤60.00 12/30/2024
Fees Total Due: ¤0.00 Total Paid: ¤165.00