I want to search for...
Permit #2025010774
Permit Details
Status: FINAL
| Parcel Id: 07-11-31-7034-01290-0120 |
| Block: 01290 |
| Subdivision: 7034 - |
| Job Phone: 904-610-4499 |
| Location Address: 69 EDWARD DR |
| Type: GEN - GENERATOR |
| Issue Date: 02/20/2025 |
| NOC: RECORDED |
| Applicant name: ANTHONY MODESTO SCHREIBER |
| Owner: ALTUNA FRANCISO J & MARIA T H&W |
|
Address 69 EDWARD DRIVE PALM COAST, FL 32164 |
| Lot: 0120 |
| Contracted Stated Job Value: ¤16,490.00 |
| Job Description: INSTALLATION OF 26KW GENERATOR WITH ATS & 320 GAL U/G LP TANK |
| Type: CN |
Contractor
AA SERVICE AND REPAIR NORTH FLORIDA AC
| Status | Location Address | State License Number | Phone | Fax |
| INACTIVE |
PO BOX 57896 JACKSONVILLE, FL 32258 |
CMC1249701 (Exp: 08/31/2026) | 904-610-4499 | 904-288-8164 |
Sub Contractors
ANTHONY MODESTO SCHREIBER
| Status | Location Address | State License Number | Phone | Fax |
| ACTIVE |
PO BOX 57896 JACKSONVILLE, FL 32258 |
CFC1427665 (Exp: 08/31/2026) | 904-626-8199 | 904-288-8164 |
Inspection History
| Type | Request Date | Result | Inspector |
| ELECTRIC FINAL | 03/04/2025 | FINAL APPROVED | RSIMS |
| Note: *** NOTES ADDED BY RSIMS 3/4/2025 2:46:28 PM *** | |||
| GAS FINAL | 03/03/2025 | APPROVED | MGIBSON |
| GAS ROUGH | 02/25/2025 | APPROVED | MGIBSON |
Review History
| Department | Status | Date In | Date Out |
| ELEC | COMPLETE | 02/18/2025 | 02/20/2025 |
| Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM | |||
| ELEC | HOLD | 02/05/2025 | 02/10/2025 |
| Note: Held By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM 2. Need to show emergency shut down disconnect. NEC 2020 445.18 (D) | |||
| ZON | COMPLETE | 01/31/2025 | 01/31/2025 |
| Note: Released By: TRACEY DOAK - (386)986-3751 - TDOAK@PALMCOASTGOV.COM | |||
| ELEC | HOLD | 01/31/2025 | 02/05/2025 |
| Note: Held By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM 2. Need to show emergency shut down disconnect. NEC 2020 445.18 (D) | |||
| ELEC | HOLD | 01/21/2025 | 01/27/2025 |
| Note: Held By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM 1. Wrong wire size for a 26 KW generator. 2. Need to show emergency shut down disconnect. NEC 2020 445.18 (D) | |||
| GAS | COMPLETE | 01/21/2025 | 01/24/2025 |
| Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM | |||
| ZON | HOLD | 01/21/2025 | 01/21/2025 |
| Note: Held By: ALISHA MOBLEY - (386)986-3751 - AMOBLEY@PALMCOASTGOV.COM Generator encroaching in 5ft utility easement |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| ADJUSTMENT 10% | (¤12.25) | 02/20/2025 |
| ADMINISTRATIVE RESIDENTIAL | ¤30.00 | 02/20/2025 |
| INSPECTION - RESIDENTIAL | ¤60.00 | 02/20/2025 |
| PLAN REVIEW - MISC 32.50 | ¤32.50 | 02/20/2025 |
| SURCHARGE FS 533.721 | ¤2.00 | 02/20/2025 |
| SURCHARGE - FS 468.631 | ¤2.00 | 02/20/2025 |
| SITE PLAN 15 | ¤15.00 | 02/20/2025 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤129.25 |