Permit #2025010948
Permit Details
Status: INSPECT
| Parcel Id: 06-12-31-5825-00000-001A |
| Block: 00000 |
| Subdivision: 5825 - |
| Job Phone: 407-949-2393 |
| Location Address: 890 CENTRAL AVE |
| Type: FS - FIRE SPRINKLER WET COMMERCIAL |
| Issue Date: 02/14/2025 |
| NOC: Unknown |
| Applicant name: ARTHUR BATEMAN |
| Owner: PC TOWN CENTER DEVELOPMENT II LLC |
|
Address 300 LAMBERT AVENUE FLAGLER BEACH, FL 32136 |
| Lot: 001A |
| Contracted Stated Job Value: ¤673,150.00 |
| Job Description: FIRE SPRINKLERS FIRE PUMP |
| Type: CN |
Contractor
PRECISION FIRE SYSTEMS, INC
| Status | Location Address | State License Number | Phone |
| ACTIVE |
152 STEEPLE CHASE CIRCLE SANFORD, FL 32771 |
FPC13-000123 (Exp: 06/30/2026) | 321-363-1560 |
Inspection History
| Type | Request Date | Result | Inspector |
| FIRE SPRINKLER 1ST ROUGH | 03/30/2026 | PARTIALLY APPROVED | RMARTIN |
| Note: 3/30/26 4th floor A,B,C rooms and corridor. 3/17/2026 - PREVIOUS INSPECTION NOTES 3/17/26 3rd floor A,B,C 2/4/2026 - PREVIOUS INSPECTION NOTES 2/4/26 4th floor D,E,F Spoke with contractor again about exposed PVC conduits in units, need verification from manufacture that this can be used in this application. 1/29/2026 - PREVIOUS INSPECTION NOTES 1/29/26 1st, 2nd, 3rd D,E,F good 1/9/2026 - PREVIOUS INSPECTION NOTES 1/9/26 1st floor unit A 1/7/2026 - PREVIOUS INSPECTION NOTES Need approved set of plans on site for inspection, visual 1st floor | |||
| FIRE SPRINKLER HYDROSTATIC TEST | 03/30/2026 | APPROVED | RMARTIN |
| Note: 3/17/2026 - PREVIOUS INSPECTION NOTES 3/17/26 3rd floor A,B,C 3/3/2026 - PREVIOUS INSPECTION NOTES 3/3/26 2nd floor A,B,C 2/17/2026 - PREVIOUS INSPECTION NOTES 2/17/2026- 1st floor 2/4/2026 - PREVIOUS INSPECTION NOTES 2/4/26 4th floor. D,E,F 1/29/2026 - PREVIOUS INSPECTION NOTES 1/29/26 3rd floor hydro 1/13/2026 - PREVIOUS INSPECTION NOTES 1/9/2026 - PREVIOUS INSPECTION NOTES 1/7/2026 - PREVIOUS INSPECTION NOTES No hydro ready, no water, did a visual inspection 1st floor, will add the inspection 12/12/2025 - PREVIOUS INSPECTION NOTES D,E,F hydro | |||
| FIRE SPRINKLER HYDROSTATIC TEST | 03/17/2026 | PARTIALLY APPROVED | RMARTIN |
| Note: 3/17/26 3rd floor A,B,C 3/3/2026 - PREVIOUS INSPECTION NOTES 3/3/26 2nd floor A,B,C 2/17/2026 - PREVIOUS INSPECTION NOTES 2/17/2026- 1st floor 2/4/2026 - PREVIOUS INSPECTION NOTES 2/4/26 4th floor. D,E,F 1/29/2026 - PREVIOUS INSPECTION NOTES 1/29/26 3rd floor hydro 1/13/2026 - PREVIOUS INSPECTION NOTES 1/9/2026 - PREVIOUS INSPECTION NOTES 1/7/2026 - PREVIOUS INSPECTION NOTES No hydro ready, no water, did a visual inspection 1st floor, will add the inspection 12/12/2025 - PREVIOUS INSPECTION NOTES D,E,F hydro | |||
| FIRE SPRINKLER 1ST ROUGH | 03/17/2026 | PARTIALLY APPROVED | RMARTIN |
| Note: 3/17/26 3rd floor A,B,C 2/4/2026 - PREVIOUS INSPECTION NOTES 2/4/26 4th floor D,E,F Spoke with contractor again about exposed PVC conduits in units, need verification from manufacture that this can be used in this application. 1/29/2026 - PREVIOUS INSPECTION NOTES 1/29/26 1st, 2nd, 3rd D,E,F good 1/9/2026 - PREVIOUS INSPECTION NOTES 1/9/26 1st floor unit A 1/7/2026 - PREVIOUS INSPECTION NOTES Need approved set of plans on site for inspection, visual 1st floor | |||
| FIRE SPRINKLER HYDROSTATIC TEST | 03/03/2026 | PARTIALLY APPROVED | RMARTIN |
| Note: 3/3/26 2nd floor A,B,C 2/17/2026 - PREVIOUS INSPECTION NOTES 2/17/2026- 1st floor 2/4/2026 - PREVIOUS INSPECTION NOTES 2/4/26 4th floor. D,E,F 1/29/2026 - PREVIOUS INSPECTION NOTES 1/29/26 3rd floor hydro 1/13/2026 - PREVIOUS INSPECTION NOTES 1/9/2026 - PREVIOUS INSPECTION NOTES 1/7/2026 - PREVIOUS INSPECTION NOTES No hydro ready, no water, did a visual inspection 1st floor, will add the inspection 12/12/2025 - PREVIOUS INSPECTION NOTES D,E,F hydro | |||
| FIRE SPRINKLER HYDROSTATIC TEST | 02/17/2026 | PARTIALLY APPROVED | JMUNSON |
| Note: 2/17/2026- 1st floor 2/4/2026 - PREVIOUS INSPECTION NOTES 2/4/26 4th floor. D,E,F 1/29/2026 - PREVIOUS INSPECTION NOTES 1/29/26 3rd floor hydro 1/13/2026 - PREVIOUS INSPECTION NOTES 1/9/2026 - PREVIOUS INSPECTION NOTES 1/7/2026 - PREVIOUS INSPECTION NOTES No hydro ready, no water, did a visual inspection 1st floor, will add the inspection 12/12/2025 - PREVIOUS INSPECTION NOTES D,E,F hydro | |||
| FIRE SPRINKLER HYDROSTATIC TEST | 02/04/2026 | PARTIALLY APPROVED | RMARTIN |
| Note: 2/4/26 4th floor. D,E,F 1/29/2026 - PREVIOUS INSPECTION NOTES 1/29/26 3rd floor hydro 1/13/2026 - PREVIOUS INSPECTION NOTES 1/9/2026 - PREVIOUS INSPECTION NOTES 1/7/2026 - PREVIOUS INSPECTION NOTES No hydro ready, no water, did a visual inspection 1st floor, will add the inspection 12/12/2025 - PREVIOUS INSPECTION NOTES D,E,F hydro | |||
| FIRE SPRINKLER 1ST ROUGH | 02/04/2026 | PARTIALLY APPROVED | RMARTIN |
| Note: 2/4/26 4th floor D,E,F Spoke with contractor again about exposed PVC conduits in units, need verification from manufacture that this can be used in this application. 1/29/2026 - PREVIOUS INSPECTION NOTES 1/29/26 1st, 2nd, 3rd D,E,F good 1/9/2026 - PREVIOUS INSPECTION NOTES 1/9/26 1st floor unit A 1/7/2026 - PREVIOUS INSPECTION NOTES Need approved set of plans on site for inspection, visual 1st floor | |||
| FIRE SPRINKLER 1ST ROUGH | 01/29/2026 | PARTIALLY APPROVED | RMARTIN |
| Note: 1/29/26 1st, 2nd, 3rd D,E,F good 1/9/2026 - PREVIOUS INSPECTION NOTES 1/9/26 1st floor unit A 1/7/2026 - PREVIOUS INSPECTION NOTES Need approved set of plans on site for inspection, visual 1st floor | |||
| FIRE SPRINKLER HYDROSTATIC TEST | 01/29/2026 | PARTIALLY APPROVED | RMARTIN |
| Note: 1/29/26 3rd floor hydro 1/13/2026 - PREVIOUS INSPECTION NOTES 1/9/2026 - PREVIOUS INSPECTION NOTES 1/7/2026 - PREVIOUS INSPECTION NOTES No hydro ready, no water, did a visual inspection 1st floor, will add the inspection 12/12/2025 - PREVIOUS INSPECTION NOTES D,E,F hydro | |||
| FIRE SPRINKLER HYDROSTATIC TEST | 01/13/2026 | CANCELLED BY APPLICANT | RMARTIN |
| Note: 1/9/2026 - PREVIOUS INSPECTION NOTES 1/7/2026 - PREVIOUS INSPECTION NOTES No hydro ready, no water, did a visual inspection 1st floor, will add the inspection 12/12/2025 - PREVIOUS INSPECTION NOTES D,E,F hydro | |||
| FIRE SPRINKLER HYDROSTATIC TEST | 01/09/2026 | CANCELLED BY APPLICANT | RMARTIN |
| Note: 1/7/2026 - PREVIOUS INSPECTION NOTES No hydro ready, no water, did a visual inspection 1st floor, will add the inspection 12/12/2025 - PREVIOUS INSPECTION NOTES D,E,F hydro | |||
| FIRE SPRINKLER 1ST ROUGH | 01/09/2026 | PARTIALLY APPROVED | RMARTIN |
| Note: 1/9/26 1st floor unit A 1/7/2026 - PREVIOUS INSPECTION NOTES Need approved set of plans on site for inspection, visual 1st floor | |||
| FIRE SPRINKLER 1ST ROUGH | 01/07/2026 | PARTIALLY APPROVED | RMARTIN |
| Note: Need approved set of plans on site for inspection, visual 1st floor | |||
| FIRE SPRINKLER HYDROSTATIC TEST | 01/07/2026 | Disapproved - NO FEE | RMARTIN |
| Note: No hydro ready, no water, did a visual inspection 1st floor, will add the inspection 12/12/2025 - PREVIOUS INSPECTION NOTES D,E,F hydro | |||
| FIRE SPRINKLER HYDROSTATIC TEST | 12/12/2025 | PARTIALLY APPROVED | RMARTIN |
| Note: D,E,F hydro | |||
| FIRE SPRINKLER 1ST ROUGH | 12/12/2025 | APPROVED - AS NOTED | RMARTIN |
| Note: D, E,F Please have approved plans on site for next inspections | |||
| FIRE SPRINKLER 1ST ROUGH | |||
| Note: 3/30/2026 - PREVIOUS INSPECTION NOTES 3/30/26 4th floor A,B,C rooms and corridor. 3/17/2026 - PREVIOUS INSPECTION NOTES 3/17/26 3rd floor A,B,C 2/4/2026 - PREVIOUS INSPECTION NOTES 2/4/26 4th floor D,E,F Spoke with contractor again about exposed PVC conduits in units, need verification from manufacture that this can be used in this application. 1/29/2026 - PREVIOUS INSPECTION NOTES 1/29/26 1st, 2nd, 3rd D,E,F good 1/9/2026 - PREVIOUS INSPECTION NOTES 1/9/26 1st floor unit A 1/7/2026 - PREVIOUS INSPECTION NOTES Need approved set of plans on site for inspection, visual 1st floor | |||
| FIRE SPRINKLER FINAL |
Review History
| Department | Status | Date In | Date Out |
| FI1 | COMPLETE | 02/11/2025 | 02/11/2025 |
| Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM | |||
| FI1 | HOLD | 01/23/2025 | 02/06/2025 |
| Note: Held By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM Please provide proof weatherproofing or guarding for alarm bell. (Outdoor water motor-operated or electrically operated bells need to be weatherproofed and guarded). Per NFPA 13 (2019) 16.11.1.2 Need to show sprinklers in stairways. NFPA 13 9.3.4 | |||
| UD1 | COMPLETE | 01/23/2025 | 01/31/2025 |
| Note: Released By: GREG DEGLER - (386)986-2384 - GDEGLER@PALMCOASTGOV.COM |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| ADJUSTMENT 10% | (¤829.04) | 02/14/2025 |
| ADMINISTRATIVE - COMMERCIAL | ¤75.00 | 02/14/2025 |
| INSPECTION - FIRE COMMERCIAL | ¤464.40 | 02/14/2025 |
| PLAN REVIEW - COMMERCIAL | ¤7,751.00 | 02/14/2025 |
| SURCHARGE FS 533.721 | ¤74.61 | 02/14/2025 |
| SURCHARGE - FS 468.631 | ¤111.92 | 02/14/2025 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤7,647.89 |