Permit #2025010948

Permit Details

Status: INSPECT

Parcel Id: 06-12-31-5825-00000-001A
Block: 00000
Subdivision: 5825 -
Job Phone: 407-949-2393
Location Address: 890 CENTRAL AVE
Type: FS - FIRE SPRINKLER WET COMMERCIAL
Issue Date: 02/14/2025
NOC: Unknown
Applicant name: ARTHUR BATEMAN
Owner: PC TOWN CENTER DEVELOPMENT II LLC

Address

300 LAMBERT AVENUE

FLAGLER BEACH, FL 32136

Lot: 001A
Contracted Stated Job Value: ¤673,150.00
Job Description: FIRE SPRINKLERS FIRE PUMP
Type: CN

Contractor

PRECISION FIRE SYSTEMS, INC
Status Location Address State License Number Phone
ACTIVE

152 STEEPLE CHASE CIRCLE

SANFORD, FL 32771

FPC13-000123 (Exp: 06/30/2026) 321-363-1560

Inspection History

Type Request Date Result Inspector
FIRE SPRINKLER 1ST ROUGH 03/30/2026 PARTIALLY APPROVED RMARTIN
Note: 3/30/26 4th floor A,B,C rooms and corridor. 3/17/2026 - PREVIOUS INSPECTION NOTES 3/17/26 3rd floor A,B,C 2/4/2026 - PREVIOUS INSPECTION NOTES 2/4/26 4th floor D,E,F Spoke with contractor again about exposed PVC conduits in units, need verification from manufacture that this can be used in this application. 1/29/2026 - PREVIOUS INSPECTION NOTES 1/29/26 1st, 2nd, 3rd D,E,F good 1/9/2026 - PREVIOUS INSPECTION NOTES 1/9/26 1st floor unit A 1/7/2026 - PREVIOUS INSPECTION NOTES Need approved set of plans on site for inspection, visual 1st floor
FIRE SPRINKLER HYDROSTATIC TEST 03/30/2026 APPROVED RMARTIN
Note: 3/17/2026 - PREVIOUS INSPECTION NOTES 3/17/26 3rd floor A,B,C 3/3/2026 - PREVIOUS INSPECTION NOTES 3/3/26 2nd floor A,B,C 2/17/2026 - PREVIOUS INSPECTION NOTES 2/17/2026- 1st floor 2/4/2026 - PREVIOUS INSPECTION NOTES 2/4/26 4th floor. D,E,F 1/29/2026 - PREVIOUS INSPECTION NOTES 1/29/26 3rd floor hydro 1/13/2026 - PREVIOUS INSPECTION NOTES 1/9/2026 - PREVIOUS INSPECTION NOTES 1/7/2026 - PREVIOUS INSPECTION NOTES No hydro ready, no water, did a visual inspection 1st floor, will add the inspection 12/12/2025 - PREVIOUS INSPECTION NOTES D,E,F hydro
FIRE SPRINKLER HYDROSTATIC TEST 03/17/2026 PARTIALLY APPROVED RMARTIN
Note: 3/17/26 3rd floor A,B,C 3/3/2026 - PREVIOUS INSPECTION NOTES 3/3/26 2nd floor A,B,C 2/17/2026 - PREVIOUS INSPECTION NOTES 2/17/2026- 1st floor 2/4/2026 - PREVIOUS INSPECTION NOTES 2/4/26 4th floor. D,E,F 1/29/2026 - PREVIOUS INSPECTION NOTES 1/29/26 3rd floor hydro 1/13/2026 - PREVIOUS INSPECTION NOTES 1/9/2026 - PREVIOUS INSPECTION NOTES 1/7/2026 - PREVIOUS INSPECTION NOTES No hydro ready, no water, did a visual inspection 1st floor, will add the inspection 12/12/2025 - PREVIOUS INSPECTION NOTES D,E,F hydro
FIRE SPRINKLER 1ST ROUGH 03/17/2026 PARTIALLY APPROVED RMARTIN
Note: 3/17/26 3rd floor A,B,C 2/4/2026 - PREVIOUS INSPECTION NOTES 2/4/26 4th floor D,E,F Spoke with contractor again about exposed PVC conduits in units, need verification from manufacture that this can be used in this application. 1/29/2026 - PREVIOUS INSPECTION NOTES 1/29/26 1st, 2nd, 3rd D,E,F good 1/9/2026 - PREVIOUS INSPECTION NOTES 1/9/26 1st floor unit A 1/7/2026 - PREVIOUS INSPECTION NOTES Need approved set of plans on site for inspection, visual 1st floor
FIRE SPRINKLER HYDROSTATIC TEST 03/03/2026 PARTIALLY APPROVED RMARTIN
Note: 3/3/26 2nd floor A,B,C 2/17/2026 - PREVIOUS INSPECTION NOTES 2/17/2026- 1st floor 2/4/2026 - PREVIOUS INSPECTION NOTES 2/4/26 4th floor. D,E,F 1/29/2026 - PREVIOUS INSPECTION NOTES 1/29/26 3rd floor hydro 1/13/2026 - PREVIOUS INSPECTION NOTES 1/9/2026 - PREVIOUS INSPECTION NOTES 1/7/2026 - PREVIOUS INSPECTION NOTES No hydro ready, no water, did a visual inspection 1st floor, will add the inspection 12/12/2025 - PREVIOUS INSPECTION NOTES D,E,F hydro
FIRE SPRINKLER HYDROSTATIC TEST 02/17/2026 PARTIALLY APPROVED JMUNSON
Note: 2/17/2026- 1st floor 2/4/2026 - PREVIOUS INSPECTION NOTES 2/4/26 4th floor. D,E,F 1/29/2026 - PREVIOUS INSPECTION NOTES 1/29/26 3rd floor hydro 1/13/2026 - PREVIOUS INSPECTION NOTES 1/9/2026 - PREVIOUS INSPECTION NOTES 1/7/2026 - PREVIOUS INSPECTION NOTES No hydro ready, no water, did a visual inspection 1st floor, will add the inspection 12/12/2025 - PREVIOUS INSPECTION NOTES D,E,F hydro
FIRE SPRINKLER HYDROSTATIC TEST 02/04/2026 PARTIALLY APPROVED RMARTIN
Note: 2/4/26 4th floor. D,E,F 1/29/2026 - PREVIOUS INSPECTION NOTES 1/29/26 3rd floor hydro 1/13/2026 - PREVIOUS INSPECTION NOTES 1/9/2026 - PREVIOUS INSPECTION NOTES 1/7/2026 - PREVIOUS INSPECTION NOTES No hydro ready, no water, did a visual inspection 1st floor, will add the inspection 12/12/2025 - PREVIOUS INSPECTION NOTES D,E,F hydro
FIRE SPRINKLER 1ST ROUGH 02/04/2026 PARTIALLY APPROVED RMARTIN
Note: 2/4/26 4th floor D,E,F Spoke with contractor again about exposed PVC conduits in units, need verification from manufacture that this can be used in this application. 1/29/2026 - PREVIOUS INSPECTION NOTES 1/29/26 1st, 2nd, 3rd D,E,F good 1/9/2026 - PREVIOUS INSPECTION NOTES 1/9/26 1st floor unit A 1/7/2026 - PREVIOUS INSPECTION NOTES Need approved set of plans on site for inspection, visual 1st floor
FIRE SPRINKLER 1ST ROUGH 01/29/2026 PARTIALLY APPROVED RMARTIN
Note: 1/29/26 1st, 2nd, 3rd D,E,F good 1/9/2026 - PREVIOUS INSPECTION NOTES 1/9/26 1st floor unit A 1/7/2026 - PREVIOUS INSPECTION NOTES Need approved set of plans on site for inspection, visual 1st floor
FIRE SPRINKLER HYDROSTATIC TEST 01/29/2026 PARTIALLY APPROVED RMARTIN
Note: 1/29/26 3rd floor hydro 1/13/2026 - PREVIOUS INSPECTION NOTES 1/9/2026 - PREVIOUS INSPECTION NOTES 1/7/2026 - PREVIOUS INSPECTION NOTES No hydro ready, no water, did a visual inspection 1st floor, will add the inspection 12/12/2025 - PREVIOUS INSPECTION NOTES D,E,F hydro
FIRE SPRINKLER HYDROSTATIC TEST 01/13/2026 CANCELLED BY APPLICANT RMARTIN
Note: 1/9/2026 - PREVIOUS INSPECTION NOTES 1/7/2026 - PREVIOUS INSPECTION NOTES No hydro ready, no water, did a visual inspection 1st floor, will add the inspection 12/12/2025 - PREVIOUS INSPECTION NOTES D,E,F hydro
FIRE SPRINKLER HYDROSTATIC TEST 01/09/2026 CANCELLED BY APPLICANT RMARTIN
Note: 1/7/2026 - PREVIOUS INSPECTION NOTES No hydro ready, no water, did a visual inspection 1st floor, will add the inspection 12/12/2025 - PREVIOUS INSPECTION NOTES D,E,F hydro
FIRE SPRINKLER 1ST ROUGH 01/09/2026 PARTIALLY APPROVED RMARTIN
Note: 1/9/26 1st floor unit A 1/7/2026 - PREVIOUS INSPECTION NOTES Need approved set of plans on site for inspection, visual 1st floor
FIRE SPRINKLER 1ST ROUGH 01/07/2026 PARTIALLY APPROVED RMARTIN
Note: Need approved set of plans on site for inspection, visual 1st floor
FIRE SPRINKLER HYDROSTATIC TEST 01/07/2026 Disapproved - NO FEE RMARTIN
Note: No hydro ready, no water, did a visual inspection 1st floor, will add the inspection 12/12/2025 - PREVIOUS INSPECTION NOTES D,E,F hydro
FIRE SPRINKLER HYDROSTATIC TEST 12/12/2025 PARTIALLY APPROVED RMARTIN
Note: D,E,F hydro
FIRE SPRINKLER 1ST ROUGH 12/12/2025 APPROVED - AS NOTED RMARTIN
Note: D, E,F Please have approved plans on site for next inspections
FIRE SPRINKLER 1ST ROUGH
Note: 3/30/2026 - PREVIOUS INSPECTION NOTES 3/30/26 4th floor A,B,C rooms and corridor. 3/17/2026 - PREVIOUS INSPECTION NOTES 3/17/26 3rd floor A,B,C 2/4/2026 - PREVIOUS INSPECTION NOTES 2/4/26 4th floor D,E,F Spoke with contractor again about exposed PVC conduits in units, need verification from manufacture that this can be used in this application. 1/29/2026 - PREVIOUS INSPECTION NOTES 1/29/26 1st, 2nd, 3rd D,E,F good 1/9/2026 - PREVIOUS INSPECTION NOTES 1/9/26 1st floor unit A 1/7/2026 - PREVIOUS INSPECTION NOTES Need approved set of plans on site for inspection, visual 1st floor
FIRE SPRINKLER FINAL

Review History

Department Status Date In Date Out
FI1 COMPLETE 02/11/2025 02/11/2025
Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM
FI1 HOLD 01/23/2025 02/06/2025
Note: Held By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM Please provide proof weatherproofing or guarding for alarm bell. (Outdoor water motor-operated or electrically operated bells need to be weatherproofed and guarded). Per NFPA 13 (2019) 16.11.1.2 Need to show sprinklers in stairways. NFPA 13 9.3.4
UD1 COMPLETE 01/23/2025 01/31/2025
Note: Released By: GREG DEGLER - (386)986-2384 - GDEGLER@PALMCOASTGOV.COM

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
ADJUSTMENT 10% (¤829.04) 02/14/2025
ADMINISTRATIVE - COMMERCIAL ¤75.00 02/14/2025
INSPECTION - FIRE COMMERCIAL ¤464.40 02/14/2025
PLAN REVIEW - COMMERCIAL ¤7,751.00 02/14/2025
SURCHARGE FS 533.721 ¤74.61 02/14/2025
SURCHARGE - FS 468.631 ¤111.92 02/14/2025
Fees Total Due: ¤0.00 Total Paid: ¤7,647.89