Permit #2025011144

Permit Details

Status: COED

Parcel Id: 07-11-31-7028-00340-0040
Block: 00340
Subdivision: 7028 -
Job Phone: 386-503-6922
Location Address: 10 POST LN
Type: RF - REROOF
Issue Date: 01/30/2025
NOC: RECORDED
Applicant name: JOSE E ORTIZ JR
Owner: MOROSHEK GREGORY & YELENA MOROSHEK H&W

Address

5050 XIMINES LANE N

PLYMOUTH, MN 55442

Lot: 0040
Contracted Stated Job Value: ¤18,000.00
Job Description: re-roof
Type: CN

Contractor

JOSE E ORTIZ JR LLC
Status Location Address State License Number Phone
ACTIVE

4601 E MOODY BLVD, STE A3

BUNNELL, FL 32110

CCC1334839 (Exp: 08/31/2026) 386-313-6055

Inspection History

Type Request Date Result Inspector
ROOF IN PROGRESS- MIDROOF 02/25/2025 APPROVED - AS NOTED MCONTRYMAN
Note: 2/25/25 Approved based upon engineers letter 2/12/2025 - PREVIOUS INSPECTION NOTES 2/12/25: Revised engineer's letter has been submitted to and approved by the City. 1). Fastener spacing exceeds the maximum spacing along the panel as required by the specifications in the Engineer's revised letter. (4-3/4"). 2/10/2025 8:58:26 AM- PREVIOUS INSPECTION NOTES 2/4/2025 - PREVIOUS INSPECTION NOTES 2/4/25: 1). Original roof deck is 15/32" OSB, Manufacturer's approved installation instructions for the installed roof panels clearly requires B-C 4ply plywood as shown in the instructions below. Correction or revision with manufacturer's engineer approval is required. ** Roof Deck: Armour 5-V Crimp 0.032” aluminum roof and wall panels are certified for use over solid or closely-spaced, nominal 15/32” B-C 4 Ply Plywood sheathing complying with 2020 Florida Building Code - Building, 7th Edition, Section 2303.1.5, with a minimum slope of 4% (1/2:12). Lap sealant shall be applied for installed slopes less than 25% (3:12).
ROOF FINAL 02/25/2025 FINAL APPROVED MCONTRYMAN
Note: Inspector Notes from Inspection 2468 2/25/25 Approved based upon engineers letter 2/12/2025 - PREVIOUS INSPECTION NOTES 2/12/25: Revised engineer's letter has been submitted to and approved by the City. 1). Fastener spacing exceeds the maximum spacing along the panel as required by the specifications in the Engineer's revised letter. (4-3/4"). 2/10/2025 8:58:26 AM- PREVIOUS INSPECTION NOTES 2/4/2025 - PREVIOUS INSPECTION NOTES 2/4/25: 1). Original roof deck is 15/32" OSB, Manufacturer's approved installation instructions for the installed roof panels clearly requires B-C 4ply plywood as shown in the instructions below. Correction or revision with manufacturer's engineer approval is required. ** Roof Deck: Armour 5-V Crimp 0.032” aluminum roof and wall panels are certified for use over solid or closely-spaced, nominal 15/32” B-C 4 Ply Plywood sheathing complying with 2020 Florida Building Code - Building, 7th Edition, Section 2303.1.5, with a minimum slope of 4% (1/2:12). Lap sealant shall be applied for installed slopes less than 25% (3:12).
ROOF AFFIDAVIT 02/18/2025 APPROVED NDIMATTINA
ROOF SHEATHING 02/12/2025 APPROVED - AS NOTED RSIMS
Note: *** NOTES ADDED BY RSIMS 2/12/2025 10:33:21 AM *** 2/12/25: Approved as noted based on submitted engineer's letter reviewed by the City. 2/7/2025 9:36:19 AM- PREVIOUS INSPECTION NOTES 2/4/2025 - PREVIOUS INSPECTION NOTES 2/4/25: 1). Original roof deck is 15/32" OSB, Manufacturer's approved installation instructions for the installed roof panels clearly requires B-C 4ply plywood as shown in the instructions below. Correction or revision with manufacturer's engineer approval is required. ** Roof Deck: Armour 5-V Crimp 0.032” aluminum roof and wall panels are certified for use over solid or closely-spaced, nominal 15/32” B-C 4 Ply Plywood sheathing complying with 2020 Florida Building Code - Building, 7th Edition, Section 2303.1.5, with a minimum slope of 4% (1/2:12). Lap sealant shall be applied for installed slopes less than 25% (3:12).
ROOF IN PROGRESS- MIDROOF 02/12/2025 Disapproved -FEE REQUIRED RSIMS
Note: *** NOTES ADDED BY RSIMS 2/12/2025 10:37:05 AM *** 2/12/25: Revised engineer's letter has been submitted to and approved by the City. 1). Fastener spacing exceeds the maximum spacing along the panel as required by the specifications in the Engineer's revised letter. (4-3/4"). 2/10/2025 8:58:26 AM- PREVIOUS INSPECTION NOTES 2/4/2025 - PREVIOUS INSPECTION NOTES 2/4/25: 1). Original roof deck is 15/32" OSB, Manufacturer's approved installation instructions for the installed roof panels clearly requires B-C 4ply plywood as shown in the instructions below. Correction or revision with manufacturer's engineer approval is required. ** Roof Deck: Armour 5-V Crimp 0.032” aluminum roof and wall panels are certified for use over solid or closely-spaced, nominal 15/32” B-C 4 Ply Plywood sheathing complying with 2020 Florida Building Code - Building, 7th Edition, Section 2303.1.5, with a minimum slope of 4% (1/2:12). Lap sealant shall be applied for installed slopes less than 25% (3:12).
ROOF SHEATHING 02/10/2025 CANCELLED BY APPLICANT CPISCITELLI
Note: 2/4/2025 - PREVIOUS INSPECTION NOTES 2/4/25: 1). Original roof deck is 15/32" OSB, Manufacturer's approved installation instructions for the installed roof panels clearly requires B-C 4ply plywood as shown in the instructions below. Correction or revision with manufacturer's engineer approval is required. ** Roof Deck: Armour 5-V Crimp 0.032” aluminum roof and wall panels are certified for use over solid or closely-spaced, nominal 15/32” B-C 4 Ply Plywood sheathing complying with 2020 Florida Building Code - Building, 7th Edition, Section 2303.1.5, with a minimum slope of 4% (1/2:12). Lap sealant shall be applied for installed slopes less than 25% (3:12).
ROOF IN PROGRESS- MIDROOF 02/10/2025 CANCELLED BY APPLICANT CPISCITELLI
Note: 2/4/2025 - PREVIOUS INSPECTION NOTES 2/4/25: 1). Original roof deck is 15/32" OSB, Manufacturer's approved installation instructions for the installed roof panels clearly requires B-C 4ply plywood as shown in the instructions below. Correction or revision with manufacturer's engineer approval is required. ** Roof Deck: Armour 5-V Crimp 0.032” aluminum roof and wall panels are certified for use over solid or closely-spaced, nominal 15/32” B-C 4 Ply Plywood sheathing complying with 2020 Florida Building Code - Building, 7th Edition, Section 2303.1.5, with a minimum slope of 4% (1/2:12). Lap sealant shall be applied for installed slopes less than 25% (3:12).
ROOF IN PROGRESS- MIDROOF 02/04/2025 Disapproved - NO FEE RSIMS
Note: *** NOTES ADDED BY RSIMS 2/4/2025 10:57:43 AM *** 2/4/25: 1). Original roof deck is 15/32" OSB, Manufacturer's approved installation instructions for the installed roof panels clearly requires B-C 4ply plywood as shown in the instructions below. Correction or revision with manufacturer's engineer approval is required. ** Roof Deck: Armour 5-V Crimp 0.032” aluminum roof and wall panels are certified for use over solid or closely-spaced, nominal 15/32” B-C 4 Ply Plywood sheathing complying with 2020 Florida Building Code - Building, 7th Edition, Section 2303.1.5, with a minimum slope of 4% (1/2:12). Lap sealant shall be applied for installed slopes less than 25% (3:12).
ROOF SHEATHING 02/04/2025 Disapproved - NO FEE RSIMS
Note: *** NOTES ADDED BY RSIMS 2/4/2025 10:58:09 AM *** 2/4/25: 1). Original roof deck is 15/32" OSB, Manufacturer's approved installation instructions for the installed roof panels clearly requires B-C 4ply plywood as shown in the instructions below. Correction or revision with manufacturer's engineer approval is required. ** Roof Deck: Armour 5-V Crimp 0.032” aluminum roof and wall panels are certified for use over solid or closely-spaced, nominal 15/32” B-C 4 Ply Plywood sheathing complying with 2020 Florida Building Code - Building, 7th Edition, Section 2303.1.5, with a minimum slope of 4% (1/2:12). Lap sealant shall be applied for installed slopes less than 25% (3:12).

Review History

Department Status Date In Date Out
BLD COMPLETE 02/24/2025 02/24/2025
Note: Released By: PETER KNAPIK - (386)986-3783 - PKNAPIK@PALMCOASTGOV.COM
BLD COMPLETE 02/11/2025 02/11/2025
Note: Released By: PETER KNAPIK - (386)986-3783 - PKNAPIK@PALMCOASTGOV.COM
BLD HOLD 02/10/2025 02/11/2025
Note: Held By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM Provide uplift calculations or Engineer to include certification statement in accordance with Florida Administrative Code 61G15-18.011 (4) certiying this roof deck can withstand the uplift pressures
BLD HOLD 02/07/2025 02/07/2025
Note: Held By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM THIS IS THE CORRECT REVIEW. PREVIOUS WAS COMPLETED IN ERROR This letter not accepted. You cannot override the Engineer of the product approval report. You can provide a report from a licensed Florida P.E. that is site specific, evaluates the existing roof deck and includes deck material and size. The report also needs to show that the roof deck can withstand the new uplifts occurred by the metal panel roofing. (Provide Calculations)
BLD COMPLETE 02/06/2025 02/07/2025
Note: Released By: PETER KNAPIK - (386)986-3783 - PKNAPIK@PALMCOASTGOV.COM
BLD COMPLETE 01/30/2025 01/30/2025
Note: Released By: PETER KNAPIK - (386)986-3783 - PKNAPIK@PALMCOASTGOV.COM
BLD HOLD 01/28/2025 01/28/2025
Note: Held By: PETER KNAPIK - (386)986-3783 - PKNAPIK@PALMCOASTGOV.COM 1. Please indicate the specific metal shingle to be used by providing the digit after the point. 2. FL# 5259 R30 is out of cycle. We are in the 2023 review cycle.
BLD HOLD 01/28/2025 01/29/2025
Note: Held By: PETER KNAPIK - (386)986-3783 - PKNAPIK@PALMCOASTGOV.COM 1. Please indicate the specific metal panel to be used by providing the digit after the point. Example 24397.1,2,3,4. They are different sheets and instalation requirements.

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
REINSPECTION RESIDENTIAL ¤40.00 02/19/2025
SURCHARGE FS 533.721 ¤2.00 01/30/2025
SURCHARGE - FS 468.631 ¤2.00 01/30/2025
ADJUSTMENT 10% (¤9.00) 01/30/2025
ADMINISTRATIVE RESIDENTIAL ¤30.00 01/30/2025
INSPECTION - RESIDENTIAL ¤60.00 01/30/2025
Fees Total Due: ¤0.00 Total Paid: ¤125.00