I want to search for...

Permit #2025011247

Permit Details

Status: FINAL

Parcel Id: 07-11-31-7004-00050-0010
Block: 00050
Subdivision: -
Job Phone: 321-262-8278
Location Address: 1 CLEARVIEW CT N
Type: GEN - GENERATOR
Issue Date: 03/04/2025
NOC: RECORDED
Applicant name: NICHOLAS B JONES
Owner: TASSCHE FRANK & SUZANNE H&W

Address

1 CLEARVIEW COURT N

PALM COAST, FL 32137

Lot: 0010
Contracted Stated Job Value: ¤18,735.00
Job Description: Install 24kw Generac whole home generator
Type: CN

Contractor

ALL SOLUTIONS ELECTRICAL SERVICE LLC
Status Location Address State License Number Phone
ACTIVE

PO BOX 262

DELTONA, FL 32738

EC13010656 (Exp: 08/31/2026) 321-262-8278

Inspection History

Type Request Date Result Inspector
ELECTRIC FINAL 05/08/2025 FINAL APPROVED HCAMACHO
GAS ROUGH 05/08/2025 APPROVED HCAMACHO
Note: Existing gas on premisses
GAS FINAL 05/08/2025 FINAL APPROVED HCAMACHO
ELECTRIC FINAL 05/07/2025 CANCELLED BY APPLICANT WEB
Note: New inspection due to canceled inspection 4/16/2025 - PREVIOUS INSPECTION NOTES 1. No permit or aaproved papers on site.FBC [A] 105.7 NEEDS PERMIT ON SITE FBC [A]107.3.1 NEEDS APPROVED PLANS ON SITE 2. Homeowner was home but did not know how to operate Generator. Note- Contractor needs to be on site for operation of generator and remove panel covers for inspection.
ELECTRIC FINAL 05/05/2025 CANCELLED BY APPLICANT WEB
Note: 4/16/2025 - PREVIOUS INSPECTION NOTES 1. No permit or aaproved papers on site.FBC [A] 105.7 NEEDS PERMIT ON SITE FBC [A]107.3.1 NEEDS APPROVED PLANS ON SITE 2. Homeowner was home but did not know how to operate Generator. Note- Contractor needs to be on site for operation of generator and remove panel covers for inspection.
ELECTRIC FINAL 04/16/2025 Disapproved - NO FEE HCAMACHO
Note: 1. No permit or aaproved papers on site.FBC [A] 105.7 NEEDS PERMIT ON SITE FBC [A]107.3.1 NEEDS APPROVED PLANS ON SITE 2. Homeowner was home but did not know how to operate Generator. Note- Contractor needs to be on site for operation of generator and remove panel covers for inspection.

Review History

Department Status Date In Date Out
ELEC COMPLETE 02/20/2025 02/21/2025
Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM
GAS COMPLETE 02/06/2025 02/10/2025
Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM
ELEC HOLD 02/06/2025 02/11/2025
Note: Held By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM 2. Need to show disconnect between Generator and ATS NEC 445.18 and AHJ
BADMIN INFORMATION 02/04/2025 02/04/2025
Note: Marked INFORMATION By: SCOTT THOMAS - (386)986-3780 - STHOMAS@PALMCOASTGOV.COM REMOVE 'TASSCHE' FROM ALL FILE NAMES
ELEC HOLD 01/29/2025 02/04/2025
Note: Held By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM 1. #2 alum is not rated for the 100 amp breaker NEC 2020 310.16 2. Need to show disconnect between Generator and ATS NEC 445.18 and AHJ
GAS HOLD 01/29/2025 02/03/2025
Note: Held By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM Provide note on plans that generator exhaust must be minimum 10ft from any opening into the building per FBC Residential 2023 8Th edition M1905.2.5. If using the exception to 5ft, carbon monoxide detectors will be inspected on generator final.
ZON COMPLETE 01/29/2025 01/29/2025
Note: Released By: TRACEY DOAK - (386)986-3751 - TDOAK@PALMCOASTGOV.COM
PLFM COMPLETE 01/29/2025 01/30/2025
Note: Released By: JORDAN MYERS, C.F.M - (386)986-4789 - JMYERS@PALMCOASTGOV.COM According to the Site Plan and FEMA FIRMs, the generator will not fall inside the SFHA. No elevation certificate will be required.

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
ADJUSTMENT 10% (¤12.25) 03/04/2025
ADMINISTRATIVE RESIDENTIAL ¤30.00 03/04/2025
INSPECTION - RESIDENTIAL ¤60.00 03/04/2025
PLAN REVIEW - MISC 32.50 ¤32.50 03/04/2025
SURCHARGE FS 533.721 ¤2.00 03/04/2025
SURCHARGE - FS 468.631 ¤2.00 03/04/2025
SITE PLAN 15 ¤15.00 03/04/2025
Fees Total Due: ¤0.00 Total Paid: ¤129.25