I want to search for...
Permit #2025011247
Permit Details
Status: FINAL
| Parcel Id: 07-11-31-7004-00050-0010 |
| Block: 00050 |
| Subdivision: - |
| Job Phone: 321-262-8278 |
| Location Address: 1 CLEARVIEW CT N |
| Type: GEN - GENERATOR |
| Issue Date: 03/04/2025 |
| NOC: RECORDED |
| Applicant name: NICHOLAS B JONES |
| Owner: TASSCHE FRANK & SUZANNE H&W |
|
Address 1 CLEARVIEW COURT N PALM COAST, FL 32137 |
| Lot: 0010 |
| Contracted Stated Job Value: ¤18,735.00 |
| Job Description: Install 24kw Generac whole home generator |
| Type: CN |
Contractor
ALL SOLUTIONS ELECTRICAL SERVICE LLC
| Status | Location Address | State License Number | Phone |
| ACTIVE |
PO BOX 262 DELTONA, FL 32738 |
EC13010656 (Exp: 08/31/2026) | 321-262-8278 |
Inspection History
| Type | Request Date | Result | Inspector |
| ELECTRIC FINAL | 05/08/2025 | FINAL APPROVED | HCAMACHO |
| GAS ROUGH | 05/08/2025 | APPROVED | HCAMACHO |
| Note: Existing gas on premisses | |||
| GAS FINAL | 05/08/2025 | FINAL APPROVED | HCAMACHO |
| ELECTRIC FINAL | 05/07/2025 | CANCELLED BY APPLICANT | WEB |
| Note: New inspection due to canceled inspection 4/16/2025 - PREVIOUS INSPECTION NOTES 1. No permit or aaproved papers on site.FBC [A] 105.7 NEEDS PERMIT ON SITE FBC [A]107.3.1 NEEDS APPROVED PLANS ON SITE 2. Homeowner was home but did not know how to operate Generator. Note- Contractor needs to be on site for operation of generator and remove panel covers for inspection. | |||
| ELECTRIC FINAL | 05/05/2025 | CANCELLED BY APPLICANT | WEB |
| Note: 4/16/2025 - PREVIOUS INSPECTION NOTES 1. No permit or aaproved papers on site.FBC [A] 105.7 NEEDS PERMIT ON SITE FBC [A]107.3.1 NEEDS APPROVED PLANS ON SITE 2. Homeowner was home but did not know how to operate Generator. Note- Contractor needs to be on site for operation of generator and remove panel covers for inspection. | |||
| ELECTRIC FINAL | 04/16/2025 | Disapproved - NO FEE | HCAMACHO |
| Note: 1. No permit or aaproved papers on site.FBC [A] 105.7 NEEDS PERMIT ON SITE FBC [A]107.3.1 NEEDS APPROVED PLANS ON SITE 2. Homeowner was home but did not know how to operate Generator. Note- Contractor needs to be on site for operation of generator and remove panel covers for inspection. |
Review History
| Department | Status | Date In | Date Out |
| ELEC | COMPLETE | 02/20/2025 | 02/21/2025 |
| Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM | |||
| GAS | COMPLETE | 02/06/2025 | 02/10/2025 |
| Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM | |||
| ELEC | HOLD | 02/06/2025 | 02/11/2025 |
| Note: Held By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM 2. Need to show disconnect between Generator and ATS NEC 445.18 and AHJ | |||
| BADMIN | INFORMATION | 02/04/2025 | 02/04/2025 |
| Note: Marked INFORMATION By: SCOTT THOMAS - (386)986-3780 - STHOMAS@PALMCOASTGOV.COM REMOVE 'TASSCHE' FROM ALL FILE NAMES | |||
| ELEC | HOLD | 01/29/2025 | 02/04/2025 |
| Note: Held By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM 1. #2 alum is not rated for the 100 amp breaker NEC 2020 310.16 2. Need to show disconnect between Generator and ATS NEC 445.18 and AHJ | |||
| GAS | HOLD | 01/29/2025 | 02/03/2025 |
| Note: Held By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM Provide note on plans that generator exhaust must be minimum 10ft from any opening into the building per FBC Residential 2023 8Th edition M1905.2.5. If using the exception to 5ft, carbon monoxide detectors will be inspected on generator final. | |||
| ZON | COMPLETE | 01/29/2025 | 01/29/2025 |
| Note: Released By: TRACEY DOAK - (386)986-3751 - TDOAK@PALMCOASTGOV.COM | |||
| PLFM | COMPLETE | 01/29/2025 | 01/30/2025 |
| Note: Released By: JORDAN MYERS, C.F.M - (386)986-4789 - JMYERS@PALMCOASTGOV.COM According to the Site Plan and FEMA FIRMs, the generator will not fall inside the SFHA. No elevation certificate will be required. |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| ADJUSTMENT 10% | (¤12.25) | 03/04/2025 |
| ADMINISTRATIVE RESIDENTIAL | ¤30.00 | 03/04/2025 |
| INSPECTION - RESIDENTIAL | ¤60.00 | 03/04/2025 |
| PLAN REVIEW - MISC 32.50 | ¤32.50 | 03/04/2025 |
| SURCHARGE FS 533.721 | ¤2.00 | 03/04/2025 |
| SURCHARGE - FS 468.631 | ¤2.00 | 03/04/2025 |
| SITE PLAN 15 | ¤15.00 | 03/04/2025 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤129.25 |