I want to search for...

Permit #2025030100

Permit Details

Status: COED

Parcel Id: 07-11-31-7015-00010-0430
CONDITIONED SPACE: 2093 sqft
GARAGE: 502 sqft
OPENED PORCH (WITH ROOF) : 386 sqft
PATIO/DECK (NO ROOF) : 130 sqft
Total Square Footage: 3111 sqft
Block: 00010
Subdivision: -
Job Phone: 386-627-0430
Location Address: 93 COCHISE CT
Type: BR - BUILDING RESIDENTIAL -SINGLE FAMILY
Issue Date: 04/01/2025
NOC: RECORDED
Applicant name: ANNA WIKTORIA LISOWSKI
Owner: GOLDEN FOX PROPERTIES LLC

Address

72 HERNANDEZ AVE

PALM COAST, FL 32137

Lot: 0430
Contracted Stated Job Value: ¤300,000.00
Job Description: SINGLE FAMILY RESIDENCE
Type: CN

Contractor

GOLDEN FOX HOME REMODELING, INC
Status Location Address State License Number Phone
ACTIVE

72 HERNANDEZ AVE

PALM COAST, FL 32137

CBC1259266 (Exp: 08/31/2026) 386-627-0430

Sub Contractors

DANIEL J LUSINSKI
Status Location Address Mailing Address State License Number Phone
ACTIVE

389 PALM COAST PARKWAY SW

PALM COAST, FL 32137

#4

PALM COAST, FL 32137

CCC1330133 (Exp: 08/31/2026) 386-338-7926
WILLIAM TODD SIKES
Status Location Address State License Number Phone
ACTIVE

83 PORT ROYAL DR

ST AUGUSTINE, FL 32084

EC0002726 (Exp: 08/31/2026) 904-762-8762
JUAN CARLOS GONZALEZ
Status Location Address State License Number
ACTIVE

1328 COUNTY ROAD 308

CRESCENT CITY, FL 32112

RF11067806 (Exp: 08/31/2027)
SCOTT H STILLWELL
Status Location Address State License Number Phone
ACTIVE

4500 US 1 UNIT 206

BUNNELL, FL 32110

CAC1819433 (Exp: 08/31/2026) 386-864-4404

Inspection History

Type Request Date Result Inspector
U-CROSS CONNECTION 02/17/2026 APPROVED - AS NOTED BWRIGHT
Note: Irr with potable using pvb. No cc
U -UTILITY RESIDENTIAL FINAL 02/17/2026 FINAL APPROVED BWRIGHT
BLD - BUILDING FINAL 11/12/2025 FINAL APPROVED HCAMACHO
U-CROSS CONNECTION 11/06/2025 CANCELLED BY APPLICANT WEB
ROW - FINAL APRON (AFTER POUR) 10/08/2025 APPROVED EMADISON
Note: AT THE TIME OF THE INSPECTION, ALL MINIMUM CITY REQUIREMENTS WERE MET. NIETHER THE INSPECTOR NOR THE CITY IS RESPONSIBLE IF, FOR WHATEVER REASON, SITE CONDITIONS CHANGE OVER TIME AFTER THE INSPECTION. IT IS THE BUILDER'S RESPONSIBILITY TO ENSURE THAT NOTHING CHANGES AFTER THIS INSPECTION IS APPROVED
ROW - STORMWATER FINAL 10/08/2025 APPROVED EMADISON
Note: AT THE TIME OF THE INSPECTION, ALL MINIMUM CITY REQUIREMENTS WERE MET. NIETHER THE INSPECTOR NOR THE CITY IS RESPONSIBLE IF, FOR WHATEVER REASON, SITE CONDITIONS CHANGE OVER TIME AFTER THE INSPECTION. IT IS THE BUILDER'S RESPONSIBILITY TO ENSURE THAT NOTHING CHANGES AFTER THIS INSPECTION IS APPROVED
ROW- FINAL SURVEY/GRADING CERTIFICATION 10/06/2025 APPROVED EMADISON
Note:
ROW FIELD SURVEY /GRADING CERTIFICATION 10/06/2025 APPROVED - AS NOTED EMADISON
Note: ** 10/06/25 BEFORE THE ROW STORMWATER FINAL ** ALONG BOTH THE RIGHT AND LEFT PROPERTY LINESNEED TO SOFTEN THE SLOPE TO BE MORE MAINTAINABLE SHOULD BE A 4:1 SLOPE ** LEFT SIDE NEED TO REMOVE THE OUTER SHRUBBERY AT A/C UNIT AND BARK MULCH FROM THE DRAINAGE CONVEYANCE AND INSTALL SOD. ** REAR OF PROPERTY NEED TO REPAIR WASHOUT UNDERNEATH SOD TRIPPING HAZZARD
ROW- FINAL SURVEY/GRADING CERTIFICATION 10/02/2025 Disapproved -FEE REQUIRED EMADISON
Note: ** 10/02/25 FINAL SURVEY IS REQUIRED TO SHOW ALL DRAINAGE FEATURES (CULVERTS) WITHIN 100 FEET ** DRIVEWAY TO THE RIGHT HAS (2) CULVERTS AS STATED IN PREVIOUS INSPECT ION NEED TO SHOW ** ALL ** DRAINAGWE FEATURES ** "7) The elevations and/or inverts of all drainage structures within 100 feet of the property lines, including culverts, inlets, swales, weirs, etc., both upstream and downstream of the property. This includes the ditch bottom and top of bank of ditches located on the property or in Reserved Parcels adjacent to the property. Section 300.01 B(7) V-15" ________________________________________________________________________________________________________________________ 10/1/2025 - PREVIOUS INSPECTION NOTES ** 10/01/25 FINAL SURVEY IS REQUIRED TO SHOW ALL DRAINAGE FEATURES (CULVERTS) WITHIN 100 FEET ** "7) The elevations and/or inverts of all drainage structures within 100 feet of the property lines, including culverts, inlets, swales, weirs, etc., both upstream and downstream of the property. This includes the ditch bottom and top of bank of ditches located on the property or in Reserved Parcels adjacent to the property. Section 300.01 B(7) V-15"
ROW- FINAL SURVEY/GRADING CERTIFICATION 10/01/2025 Disapproved -FEE REQUIRED EMADISON
Note: ** 10/01/25 FINAL SURVEY IS REQUIRED TO SHOW ALL DRAINAGE FEATURES (CULVERTS) WITHIN 100 FEET ** "7) The elevations and/or inverts of all drainage structures within 100 feet of the property lines, including culverts, inlets, swales, weirs, etc., both upstream and downstream of the property. This includes the ditch bottom and top of bank of ditches located on the property or in Reserved Parcels adjacent to the property. Section 300.01 B(7) V-15"
ROW - DRAINAGE 09/26/2025 APPROVED - AS NOTED EMADISON
Note: ** 09/26/25 MET BUILDER ON SITE AS WELL AS NEIGHBOR (JOHN) FROM 91 COCHISE CT REGARDING GRADE BUILDER HAS NOT YET SUBMITTED HIS FINAL SURVEY FOR REVIEW ALTHOUGH PROPERTY HAS BEEN GRADED AND SODDED. THE ONLY STANDING WATER IS BEING HELD INSIDE OF THE CULVERT FOR THIS PROPERTY AFTER THE HRAVY RAIN FROM YESTERDAYS RAIN STORM. THE BUILDER HAS MATCHED GRADE AT BOTH OF THE PROPERTY LINES AS REQUIRED BY THE CITY OF PALM COAST. AS FOR ENSURING THAT THERE IS POSITIVE FALL IN THE ROADSIDE SWALE AND THE CULVERT PIPE THE FINAL SURVEY WILL HAVE TO BE CONDUCTED. _____________________________________________________________________________________________________________________ 2024120349
ROW- PRE-APRON (PRE-POUR) 09/04/2025 APPROVED - AS NOTED EMADISON
Note: ** 09/04/25 READY TO POUR ** At the time of the inspection all minimum city requirements were met. It is the builder’s responsibility to ensure that nothing changes after this Inspection is approved. This includes but is not limited to, the Culvert Pipe Elevation from the time of the inspection approval to the concrete pour. ** BUILDERS RESPONSIBILITY TO ENSURE CULVERT ELEVATION IS WITHIN TOLERANCE BEFORE THE POUR IN THE EVENT OF RAIN CHECK COMPACTION OF MATERIAL **MAKE SURE THERE IS 3000 PSI CONCRETE REINFORCED WITH WWF 6X6.W1.4 MESH OR FIBERGLASS REINFORCED CONCRETE (FRC) DRAWING 300,E RESIDENTIAL CULVERT DETAIL
GRAVITY SEWER TEST 09/02/2025 APPROVED - AS NOTED MGIBSON
Note: Inspector Notes from Inspection 2060 THIS WAS A VIRTUAL INSPECTION WHERE BUILDING MAIN DRAIN EXITS HOME NEED SLEEVE OR RELIEVING ARCH, WATER SERVICE NOT RAN YET, FBC 3303.5 SWALE BLOCKEDBY PORTABLE
SEWER TIE IN 09/02/2025 APPROVED - AS NOTED MGIBSON
Note: Inspector Notes from Inspection 2075 THIS WAS A VIRTUAL INSPECTION Inspector Notes from Inspection 2060 THIS WAS A VIRTUAL INSPECTION WHERE BUILDING MAIN DRAIN EXITS HOME NEED SLEEVE OR RELIEVING ARCH, WATER SERVICE NOT RAN YET, FBC 3303.5 SWALE BLOCKEDBY PORTABLE Inspector Notes from Inspection 2075 THIS WAS A VIRTUAL INSPECTIO Inspector Notes from Inspection 2060 THIS WAS A VIRTUAL INSPECTION WHERE BUILDING MAIN DRAIN EXITS HOME NEED SLEEVE OR RELIEVING ARCH, WATER SERVICE NOT RAN YET, FBC 3303.5 SWALE BLOCKEDBY PORTABLE
ELECTRIC - EARLY POWER 08/22/2025 APPROVED HCAMACHO
Note: Inspector Notes from Inspection 2200 5/29/25 Okay to release e-mail to FPL 1. Please repair silt fence before next inspection FBC 3307.1
INSULATION 07/25/2025 APPROVED BTAYLOR
Note: 7/23/2025 - PREVIOUS INSPECTION NOTES 7/23/25: 1). Dryer exhaust duct will need to be boxed out where it comes out from the wall and enters attic space in order to meet fire code requirements. FBC-R302.11. 2). Interior garage door is not installed (unable to inspect). FBC-[A]110.1 (a window nailing inspection will need to be added to the permit if there is a delay on receiving that door). 3). Previosly listed notes from All Rough inspection are not fully resolved. Duct sizes in the main area do not match the Energy Calc requirements. Correction or revision required. FBC [A]107.4
INSULATION 07/23/2025 Disapproved -FEE REQUIRED RSIMS
Note: *** NOTES ADDED BY RSIMS 7/23/2025 1:12:57 PM *** 7/23/25: 1). Dryer exhaust duct will need to be boxed out where it comes out from the wall and enters attic space in order to meet fire code requirements. FBC-R302.11. 2). Interior garage door is not installed (unable to inspect). FBC-[A]110.1 (a window nailing inspection will need to be added to the permit if there is a delay on receiving that door). 3). Previosly listed notes from All Rough inspection are not fully resolved. Duct sizes in the main area do not match the Energy Calc requirements. Correction or revision required. FBC [A]107.4
LATH/BRICK/ WATER BARRIER 07/18/2025 APPROVED HCAMACHO
ALL ROUGH 07/18/2025 APPROVED - AS NOTED HCAMACHO
Note: 1. A/C layout does not match, there are a couple of A/C boots missing in the main area of the house.Please revise or install what is missing. 2. Attic access in the master closet needs to be framed to the correct size. Nothing there, only marked on the floor. *Will check at insualtion.*
ROOF VALLEY & METAL 07/08/2025 APPROVED HCAMACHO
WALL SHEATHING 06/30/2025 APPROVED HCAMACHO
ROOF SHEATHING / BRACES/TIES/DOWN CELL 06/30/2025 APPROVED HCAMACHO
ELECTRIC-TUG 05/29/2025 APPROVED - AS NOTED MCONTRYMAN
Note: 5/29/25 Okay to release e-mail to FPL 1. Please repair silt fence before next inspection FBC 3307.1
TIE BEAM / LINTEL 05/19/2025 APPROVED JSTEWART
FORMBOARD SURVEY (OFFICE USE ONLY) 05/16/2025 APPROVED RRICKS
MONOLITHIC SLAB 04/29/2025 APPROVED HCAMACHO
MONOLITHIC SLAB 04/28/2025 Disapproved - NO FEE HCAMACHO
Note: 1. Drain pipe for WM is crossing through garage footing and coming out in the next footing, needs sleeve. FBCR P2603.4 2. Water pipes are running parallel inside the garage footer, move pipes outside footer.
PLUMBING 1ST ROUGH UNDERGROUND 04/22/2025 APPROVED - AS NOTED MGIBSON
Note: WHERE BUILDING MAIN DRAIN EXITS HOME NEED SLEEVE OR RELIEVING ARCH, WATER SERVICE NOT RAN YET, FBC 3303.5 SWALE BLOCKEDBY PORTABLE
GEOTECHNICAL REPORT APPROVAL (OFFICE USE) 04/21/2025 APPROVED JMUNSON
WATER METER INSTALLATION REQUEST 04/07/2025 APPROVED CBOWERMASTER

Review History

Department Status Date In Date Out
MECH COMPLETE 10/16/2025 10/17/2025
Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM
ENGIN1 COMPLETE 05/16/2025 05/16/2025
Note: Released By: RODNEY RICKS - (386)986-2001 - RRICKS@PALMCOASTGOV.COM
ZON COMPLETE 05/16/2025 05/16/2025
Note: Released By: CINDY CHIRI-GONCALVES - (386)986-4737 - CGONCALVES@PALMCOASTGOV.COM
BLD COMPLETE 04/16/2025 04/21/2025
Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM
ZON COMPLETE 03/18/2025 03/18/2025
Note: Released By: CINDY CHIRI-GONCALVES - (386)986-4737 - CGONCALVES@PALMCOASTGOV.COM
ENGIN1 COMPLETE 03/18/2025 03/18/2025
Note: Released By: LEVI SALYERDS - (386)986-2575 - LSALYERDS@PALMCOASTGOV.COM
SW1 COMPLETE 03/18/2025 03/21/2025
Note: Released By: RODNEY RICKS - - RRICKS@PALMCOASTGOV.COM
ENGIN1 COMPLETE 03/11/2025 03/12/2025
Note: Released By: LEVI SALYERDS - (386)986-2326 - LSALYERDS@PALMCOASTGOV.COM
ZON HOLD 03/11/2025 03/12/2025
Note: Held By: CINDY CHIRI-GONCALVES - (386)986-4737 - CGONCALVES@PALMCOASTGOV.COM repeat comment ae and x shaded not X Held By: CINDY CHIRI-GONCALVES - (386)986-4737 - CGONCALVES@PALMCOASTGOV.COM Site plan : flood zone show two AE and or X 0.2% please update site plan
SW1 COMPLETE 03/11/2025 03/17/2025
Note: Released By: RODNEY RICKS - - RRICKS@PALMCOASTGOV.COM
BADMIN COMPLETE 03/04/2025 03/10/2025
Note: Released By: PETER KNAPIK - (386)986-3783 - PKNAPIK@PALMCOASTGOV.COM
BLD COMPLETE 03/04/2025 03/10/2025
Note: Released By: PETER KNAPIK - (386)986-3783 - PKNAPIK@PALMCOASTGOV.COM
CUSVC COMPLETE 03/04/2025 03/06/2025
Note: Released By: REBECCA SANDERS - - RSANDERS@PALMCOASTGOV.COM
ELEC COMPLETE 03/04/2025 03/10/2025
Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM
ENGIN1 HOLD 03/04/2025 03/04/2025
Note: Held By: LEVI SALYERDS - (386)986-2326 - LSALYERDS@PALMCOASTGOV.COM 1. Proposed elevations along the house are shown as 2' below the FFE. 2. Grade must fall 0.5' in the first 10' from the house. 3. Include the culvert type and size on the site plan. 13"x17" CMP, 15" CMP, or 15" HDPE. 4. Elevations should be shown on a 20' grid including shots 10' outside of the property lines on the sides and rear. 5. Include the adjacent swale and culvert info.
GAS CANCEL 03/04/2025 03/07/2025
LOCATE COMPLETE 03/04/2025 03/11/2025
Note: Released By: CANDACE BOWERMASTER - - CBOWERMASTER@PALMCOASTGOV.COM
MECH COMPLETE 03/04/2025 03/07/2025
Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM
SW1 HOLD 03/04/2025 03/05/2025
Note: Held By: RODNEY RICKS - - RRICKS@PALMCOASTGOV.COM 1.Grade must fall 0.5' in the first 10' from the house 2. Include the culvert type and size on the site plan. 13"x17" CMP, 15" CMP, or 15" HDPE. 3. Elevations should be shown on a 20' grid including shots 10' outside of the property lines on the sides and rear. 4. Include the adjacent swale and culvert info. 5. Lot drainage features should clearly be depicted and include flow arrows.
ZON HOLD 03/04/2025 03/04/2025
Note: Held By: CINDY CHIRI-GONCALVES - (386)986-4737 - CGONCALVES@PALMCOASTGOV.COM Site plan : flood zone show two AE and or X 0.2% please update site plan
SWALE COMPLETE 03/04/2025 03/21/2025
Note: Released By: LEVI SALYERDS - (386)986-2575 - LSALYERDS@PALMCOASTGOV.COM

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
PLAN REVIEW - REVISION ¤32.50 02/17/2026
REINSPECTION RESIDENTIAL ¤40.00 02/17/2026
SW ENG - INSPECTION 20 ¤20.00 02/17/2026
SW ENG INSPECTION 80 ¤80.00 04/01/2025
SW ENG PRE APRON ¤30.00 04/01/2025
SW ENG - REVIEW 20 ¤20.00 04/01/2025
SW ENG RES REVIEW 200 ¤200.00 04/01/2025
SEWER CREDIT (¤1,466.00) 04/01/2025
SEWER INSPECTION ¤25.00 04/01/2025
SEWER CAPITAL FACILITY ¤6,120.52 04/01/2025
WATER CAPITAL FACILITY FEE ¤4,351.14 04/01/2025
SITE PLAN 30 ¤30.00 04/01/2025
CONNECTION FEES ¤1,187.26 04/01/2025
FC IMPACT FEE EMS ¤62.00 04/01/2025
IMPACT FEE FIRE ¤434.51 04/01/2025
FC IMPACT FEE LAW ENFORCEMENT ¤218.00 04/01/2025
FC IMPACT FEE LIBRARY ¤268.00 04/01/2025
IMPACT FEE PARKS ¤1,828.01 04/01/2025
IMPACT FEE SCHOOL ¤5,450.00 04/01/2025
IMPACT FEE TRANSPORTATION ¤1,916.00 04/01/2025
WATER -IRRIGATION INSPECTION ¤25.00 04/01/2025
SURCHARGE FS 533.721 ¤13.52 04/01/2025
SURCHARGE - FS 468.631 ¤20.28 04/01/2025
SW ENG - FOUNDATION SURVEY ¤20.00 04/01/2025
WATER- TURN ON ¤25.00 04/01/2025
ADJUSTMENT 10% (¤150.20) 04/01/2025
ADMINISTRATIVE RESIDENTIAL ¤30.00 04/01/2025
INSPECTION - RESIDENTIAL ¤1,146.75 04/01/2025
PLAN REVIEW - RESIDENTIAL ¤325.26 04/01/2025
Fees Total Due: ¤0.00 Total Paid: ¤22,302.55