I want to search for...
Permit #2025030314
Permit Details
Status: FINAL
| Parcel Id: 07-11-31-7026-00630-0120 |
| Block: 00630 |
| Subdivision: 7026 - |
| Job Phone: 305-525-3466 |
| Location Address: 98 PINE GROVE DR |
| Type: ME - MECHANICAL |
| Issue Date: 03/10/2025 |
| NOC: Unknown |
| Applicant name: MICHAEL J PERTIERRA |
| Owner: PURDY JACQUELINE R |
|
Address 98 PINE GROVE DRIVE PALM COAST, FL 32164 |
| Lot: 0120 |
| Contracted Stated Job Value: ¤5,900.00 |
| Job Description: HVAC CO LIKE FOR LIKE |
| Type: CN |
Contractor
MIAMI COOL, INC
| Status | Location Address | State License Number | Phone |
| INACTIVE |
12223 SW 133 CT MIAMI, FL 33186 |
CAC1817122 (Exp: 08/31/2026) | 305-525-3466 |
Inspection History
| Type | Request Date | Result | Inspector |
| HVAC FINAL | 04/30/2025 | FINAL APPROVED | RSIMS |
| Note: *** NOTES ADDED BY RSIMS 4/30/2025 9:44:55 AM *** 4/29/2025 - PREVIOUS INSPECTION NOTES 4/29/25: A Virtual inspection will be available IF requested at the time of scheduling the re-inspection. If requesting a Virtual Re-inspection, please schedule the re-inspection for the same day that the deficiencies will be corrected and a FaceTime or Google Meet live virtual inspection can be completed. (Pictures are not approved). 1). AHU - heater core label has incorrect information: Minimum ampacity (30.8-amp) exceeds maximum breaker amperage. (30amp.). Please verify that the breaker is consistant with the correct label once replaced. | |||
| HVAC FINAL | 04/29/2025 | Disapproved - NO FEE | RSIMS |
| Note: *** NOTES ADDED BY RSIMS 4/29/2025 1:20:11 PM *** 4/29/25: A Virtual inspection will be available IF requested at the time of scheduling the re-inspection. If requesting a Virtual Re-inspection, please schedule the re-inspection for the same day that the deficiencies will be corrected and a FaceTime or Google Meet live virtual inspection can be completed. (Pictures are not approved). 1). AHU - heater core label has incorrect information: Minimum ampacity (30.8-amp) exceeds maximum breaker amperage. (30amp.). Please verify that the breaker is consistant with the correct label once replaced. |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| ADJUSTMENT 10% | (¤9.00) | 03/10/2025 |
| ADMINISTRATIVE RESIDENTIAL | ¤30.00 | 03/10/2025 |
| INSPECTION - MECHANICAL | ¤60.00 | 03/10/2025 |
| SURCHARGE FS 533.721 | ¤2.00 | 03/10/2025 |
| SURCHARGE - FS 468.631 | ¤2.00 | 03/10/2025 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤85.00 |