I want to search for...

Permit #2025030562

Permit Details

Status: FINAL

Subdivision: 2159 - CITY METER BOX
Job Phone: (386)437-3068
Location Address: 2445 OLD KINGS RD N
Type: CE - COMMERCIAL ELECTRIC
Issue Date: 03/18/2025
NOC: Unknown
Applicant name: WILLIAM FRANK DUDLEY JR.
Owner: CITY OF PALM COAST

Address

160 LAKE AVE

PALM COAST, FL 32164

Contracted Stated Job Value: ¤11,140.00
Job Description: Install power for new retention pond fountain
Type: CN

Contractor

PALMETTO ELECTRIC CO.
Status Location Address State License Number Phone
ACTIVE

P.O. BOX 978

Bunnell, FL 32110

EC0003177 (Exp: 08/31/2026) (386)437-3068

Inspection History

Type Request Date Result Inspector
ELECTRIC FINAL 07/23/2025 FINAL APPROVED MKRASKI
ELECTRIC FINAL 07/22/2025 Disapproved - NO FEE MKRASKI
Note: 1. Wiring and conduit size does not match approved plans, 2. Breaker not labeled in panel NEC 408.4

Review History

Department Status Date In Date Out
ELEC COMPLETE 07/22/2025 07/23/2025
Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM
ELEC COMPLETE 03/14/2025 03/14/2025
Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM
ELEC HOLD 03/13/2025 03/14/2025
Note: Held By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM 1. Fountain needs to be GFCI protected. NEC 2020 680.51(A)

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
ADJUSTMENT 10% (¤16.75) 03/18/2025
ADMINISTRATIVE - COMMERCIAL ¤75.00 03/18/2025
INSPECTION- ELECTRICAL ¤60.00 03/18/2025
PLAN REVIEW - MISC 32.50 ¤32.50 03/18/2025
SURCHARGE FS 533.721 ¤2.00 03/18/2025
SURCHARGE - FS 468.631 ¤2.26 03/18/2025
Fees Total Due: ¤0.00 Total Paid: ¤155.01