I want to search for...
Permit #2025030882
Permit Details
Status: CANCEL
| Parcel Id: 06-12-31-0000-000A0-0014 |
| Block: 000A0 |
| Subdivision: 1033 - COASTAL PARK OF BUNNELL |
| Job Phone: (386)566-0467 |
| Location Address: 1250 BELLE TERRE PKWY |
| Type: CIA - COMMERCIAL INTERIOR EXTERIOR ALTERATION |
| NOC: NO DOCUMENTATION |
| Applicant name: PAUL KEITH CULVER |
| Owner: CITY OF PALM COAST |
|
Address 160 LAKE AVENUE PALM COAST, FL 32164 |
| Lot: 0014 |
| Contracted Stated Job Value: ¤24,650.00 |
| Job Description: OPENING IN EXTERIOR WALL AND ELECTRICAL FOR FUTURE "BABY BOX" INSTALLATION |
| Type: CN |
Contractor
PAUL CULVER CONSTRUCTION INC
| Status | Location Address | State License Number | Phone | Fax |
| ACTIVE |
1301 BEVILLE RD SUITE #6 DAYTONA BEACH, FL 32119 |
CGC059149 (Exp: 08/31/2026) | (386)763-4190 | (386)322-6724 |
Sub Contractors
PAUL NOEL BIELEFELDT
| Status | Location Address | State License Number | Phone | Fax |
| ACTIVE |
320 Aragon Street Holly Hill, FL 32117 |
EC0001646 (Exp: 08/31/2026) | (386) 677-0447 | 386-673-9868 |
Inspection History
| Type | Request Date | Result | Inspector |
| ABOVE CEILING | |||
| BUILDING FINAL | |||
| FIRE FINAL | |||
| U - UTILITY COMMERCIAL FINAL |
Review History
| Department | Status | Date In | Date Out |
| BLD | HOLD | 03/20/2025 | 04/10/2025 |
| Note: Held By: PATRICK BUCKLEY - (386)986-3786 - PBUCKLEY@PALMCOASTGOV.COM AFTER REVIEWING THE SUBMITTED DOCUMENTS FOR THIS PERMIT INCLUDING, THE MANUFACTURER - SAFE HAVEN - INSTALLATION INSTRUCTIONS AND PRODUCT DETAILS, FOR THE "BABY BOX", I HAVE DECIDED THAT THE PALM COAST BUILDING DIVISION WILL NOT BE PERMITTING THE BABY BOX. THE REASON FOR THIS DECISION IS: ACCORDING TO THE MANUFACTURER, THE BABY BOX IS PROVIDED WITH A 120v / 15 AMP ELECTRICAL SUPPLY AND INTERNAL WIRING SYSTEM OPERATING AT 5 AMPS TO OPERATE A HEATING UNIT, ALARM, PHOTO-EYE, LOCK, LIGHT AND SENSORS. THE ELECTRICAL SYSTEM INTERNAL TO THE BABY BOX IS NOT A UNDERWRITERS LABORATORIES (U.L.) LISTED AND LABELED PRODUCT AND THERE IS NO EVIDENCE THAT ANY OF THE COMPONENTS USED IN THE ELECTRICAL SYSTEM AS BEING U.L. LISTED. ADDITIONALLY, THE ELECTRICAL DESIGN OF THE BABY BOX IS NOT DESIGNED BY A LICENSED ELECTRICAL ENGINEER IN THE STATE WHERE THE PRODUCT IS MANUFACTURED OR THE STATE OF FLORIDA. ACCORDING TO THE MANUFACTURER, THE EQUIPMENT IS CONNECTED TO AN ELECTRICAL SUPPLY BY A CORD AND PLUG. BECAUSE OF THIS, THE EQUIPMENT IS NOT REQUIRED TO BE PERMITTED. THEREFORE WE ARE GOING TO REMOVE THE MANUFACTURER'S LITERATURE FROM THE PERMIT RECORD AND OUR REVIEWS WILL BE LIMITED TO THE WORK CREATING THE OPENING IN THE EXTERIOR WALL AND THE ELECTRICAL WORK EXTENDING AN ELECTRICAL CIRCUIT TO THE POINT WHERE THE CORD CAN BE CONNECTED TO THE OUTLET. I HAVE CHANGED THE DESCRIPTION OF WORK IN THE PERMIT SYSTEM TO: CONSTRUCT OPENING IN EXTERIOR WALL AND ELECTRICAL FOR FUTURE "BABY BOX" INSTALLATION. PLEASE PROVIDE A NEW PERMIT APPLICATION THAT PROVIDES THE SAME OR SIMILAR DESCRIPTION OF WORK. UPON RESUBMITTAL OF THE NEW PERMIT APPLICATION, WE WILL COMPLETE OUR REVIEWS TO RELEASE THE PERMIT BUT THEY WILL BE NOTED THAT THE BABY BOX IS NOT A PART OF THE PERMITTED WORK AND WAS NOT REVIEWED OR APPROVED UNDER THIS PERMIT. | |||
| DSD | COMPLETE | 03/20/2025 | 03/24/2025 |
| Note: Released By: JACQUELINE GONZALEZ - (386)986-3751 - JGONZALEZ@PALMCOASTGOV.COM | |||
| ELEC | CANCEL | 03/20/2025 | 04/01/2025 |
| FI1 | COMPLETE | 03/20/2025 | 04/10/2025 |
| Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM | |||
| MECH | CANCEL | 03/20/2025 | 03/31/2025 |
| PLUM | CANCEL | 03/20/2025 | 03/31/2025 |
| UD1 | COMPLETE | 03/20/2025 | 03/28/2025 |
| Note: Released By: GREG DEGLER - (386)986-2384 - GDEGLER@PALMCOASTGOV.COM | |||
| UD2 | CANCEL | 03/20/2025 | 03/20/2025 |
| Note: 1) no grease trap or grease interceptor | |||
| ELEC | HOLD | 03/20/2025 | 04/10/2025 |
| Note: Held By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM 1. Submit one line drawing showing wire sizes and breaker sizes for new circuit. | |||
| ELEC | CANCEL | ||
| BLD | CANCEL |