I want to search for...

Permit #2025030882

Permit Details

Status: CANCEL

Parcel Id: 06-12-31-0000-000A0-0014
Block: 000A0
Subdivision: 1033 - COASTAL PARK OF BUNNELL
Job Phone: (386)566-0467
Location Address: 1250 BELLE TERRE PKWY
Type: CIA - COMMERCIAL INTERIOR EXTERIOR ALTERATION
NOC: NO DOCUMENTATION
Applicant name: PAUL KEITH CULVER
Owner: CITY OF PALM COAST

Address

160 LAKE AVENUE

PALM COAST, FL 32164

Lot: 0014
Contracted Stated Job Value: ¤24,650.00
Job Description: OPENING IN EXTERIOR WALL AND ELECTRICAL FOR FUTURE "BABY BOX" INSTALLATION
Type: CN

Contractor

PAUL CULVER CONSTRUCTION INC
Status Location Address State License Number Phone Fax
ACTIVE

1301 BEVILLE RD SUITE #6

DAYTONA BEACH, FL 32119

CGC059149 (Exp: 08/31/2026) (386)763-4190 (386)322-6724

Sub Contractors

PAUL NOEL BIELEFELDT
Status Location Address State License Number Phone Fax
ACTIVE

320 Aragon Street

Holly Hill, FL 32117

EC0001646 (Exp: 08/31/2026) (386) 677-0447 386-673-9868

Inspection History

Type Request Date Result Inspector
ABOVE CEILING
BUILDING FINAL
FIRE FINAL
U - UTILITY COMMERCIAL FINAL

Review History

Department Status Date In Date Out
BLD HOLD 03/20/2025 04/10/2025
Note: Held By: PATRICK BUCKLEY - (386)986-3786 - PBUCKLEY@PALMCOASTGOV.COM AFTER REVIEWING THE SUBMITTED DOCUMENTS FOR THIS PERMIT INCLUDING, THE MANUFACTURER - SAFE HAVEN - INSTALLATION INSTRUCTIONS AND PRODUCT DETAILS, FOR THE "BABY BOX", I HAVE DECIDED THAT THE PALM COAST BUILDING DIVISION WILL NOT BE PERMITTING THE BABY BOX. THE REASON FOR THIS DECISION IS: ACCORDING TO THE MANUFACTURER, THE BABY BOX IS PROVIDED WITH A 120v / 15 AMP ELECTRICAL SUPPLY AND INTERNAL WIRING SYSTEM OPERATING AT 5 AMPS TO OPERATE A HEATING UNIT, ALARM, PHOTO-EYE, LOCK, LIGHT AND SENSORS. THE ELECTRICAL SYSTEM INTERNAL TO THE BABY BOX IS NOT A UNDERWRITERS LABORATORIES (U.L.) LISTED AND LABELED PRODUCT AND THERE IS NO EVIDENCE THAT ANY OF THE COMPONENTS USED IN THE ELECTRICAL SYSTEM AS BEING U.L. LISTED. ADDITIONALLY, THE ELECTRICAL DESIGN OF THE BABY BOX IS NOT DESIGNED BY A LICENSED ELECTRICAL ENGINEER IN THE STATE WHERE THE PRODUCT IS MANUFACTURED OR THE STATE OF FLORIDA. ACCORDING TO THE MANUFACTURER, THE EQUIPMENT IS CONNECTED TO AN ELECTRICAL SUPPLY BY A CORD AND PLUG. BECAUSE OF THIS, THE EQUIPMENT IS NOT REQUIRED TO BE PERMITTED. THEREFORE WE ARE GOING TO REMOVE THE MANUFACTURER'S LITERATURE FROM THE PERMIT RECORD AND OUR REVIEWS WILL BE LIMITED TO THE WORK CREATING THE OPENING IN THE EXTERIOR WALL AND THE ELECTRICAL WORK EXTENDING AN ELECTRICAL CIRCUIT TO THE POINT WHERE THE CORD CAN BE CONNECTED TO THE OUTLET. I HAVE CHANGED THE DESCRIPTION OF WORK IN THE PERMIT SYSTEM TO: CONSTRUCT OPENING IN EXTERIOR WALL AND ELECTRICAL FOR FUTURE "BABY BOX" INSTALLATION. PLEASE PROVIDE A NEW PERMIT APPLICATION THAT PROVIDES THE SAME OR SIMILAR DESCRIPTION OF WORK. UPON RESUBMITTAL OF THE NEW PERMIT APPLICATION, WE WILL COMPLETE OUR REVIEWS TO RELEASE THE PERMIT BUT THEY WILL BE NOTED THAT THE BABY BOX IS NOT A PART OF THE PERMITTED WORK AND WAS NOT REVIEWED OR APPROVED UNDER THIS PERMIT.
DSD COMPLETE 03/20/2025 03/24/2025
Note: Released By: JACQUELINE GONZALEZ - (386)986-3751 - JGONZALEZ@PALMCOASTGOV.COM
ELEC CANCEL 03/20/2025 04/01/2025
FI1 COMPLETE 03/20/2025 04/10/2025
Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM
MECH CANCEL 03/20/2025 03/31/2025
PLUM CANCEL 03/20/2025 03/31/2025
UD1 COMPLETE 03/20/2025 03/28/2025
Note: Released By: GREG DEGLER - (386)986-2384 - GDEGLER@PALMCOASTGOV.COM
UD2 CANCEL 03/20/2025 03/20/2025
Note: 1) no grease trap or grease interceptor
ELEC HOLD 03/20/2025 04/10/2025
Note: Held By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM 1. Submit one line drawing showing wire sizes and breaker sizes for new circuit.
ELEC CANCEL
BLD CANCEL