Permit #2025031207

Permit Details

Status: EXPIRED

Parcel Id: 34-10-30-5860-00000-00H0
Subdivision: 5860 -
Job Phone: 877-906-1113
Location Address: 18 REDBUD RD
Type: CE - COMMERCIAL ELECTRIC
Issue Date: 03/27/2025
NOC: Unknown
Applicant name: JOSEPH HORATIO STRADA JR
Owner: TRAILS OF PALM COAST HOMEOWNERS ASSOCIATION INC

Address

2695 DOBBS ROAD

ST. AUGUSTINE, FL 32086

Contracted Stated Job Value: ¤1,200.00
Job Description: 200AMP IRRIGATION SERVICE PEDESTAL. REF#2024020031
Type: CN
Original Permit #: 2024020031

Contractor

STRADA SERVICES LLC
Status Location Address State License Number Phone
ACTIVE

3400 ST JOHNS PARKWAY

SANFORD, FL 32771

EC13003715 (Exp: 08/31/2026) 877-906-1113

Inspection History

Type Request Date Result Inspector
ELECTRIC FINAL 03/28/2025 Disapproved - NO FEE RMARTIN
Note: Need to close up un-used opening in pump control box on top of pump NEC 110.12 also approved plans call for 30 amp breaker for pump, there is a 40 amp installed, need to revise plan and wire accordingly 6/14/2024 - PREVIOUS INSPECTION NOTES *** NOTES ADDED BY RMARTIN 6/14/2024 11:20:00 AM *** Pump calls for a max breaker of 30 amps not 40. *** NOTES ADDED BY RMARTIN 6/14/2024 11:19:50 AM *** 6/7/2024 - PREVIOUS INSPECTION NOTES *** NOTES ADDED BY JMUNSON 6/7/2024 9:38:20 AM *** Pump calls for a max breaker of 30 amps not 40. 5/15/2024 - PREVIOUS INSPECTION NOTES 5/15/24 Power release and email sent to FPL @ 10am , once meter is set call in for final 5/13/2024 - PREVIOUS INSPECTION NOTES 5/13/234 Make all repairs before calling in re-inspection 3/27/2024 - PREVIOUS INSPECTION NOTES 3/27/24 1. No approved plans on site FBC 107.3.1 2. Breakers are required to be labeled NEC 210.5 3. Ground wire must be protected NEC 250.64 4. Liquid tight can not be in areas subjust to physical damaage NEC 356.12 5. Connection made for ground wire to ground rods are not approved per manufacturer specs 3/21/2024 - PREVIOUS INSPECTION NOTES NEED TO HAVE SCH. 80 PVC WHERE SUBJECT TO PHYSICAL DAMAGE NEC 300.5, NEED TO UN-COVER GROUND RODS TO BE INSPECTED, NEED TO PROVIDE SITE STICKS FOR SERVICE CONDUIT DEPTH, NEED APPROVED PLANS ON SITE, GROUNDING CONDUCTOR NEEDS TO BE PROTECTED/SLEEVED NEC 250.64
ELECTRIC FINAL 06/14/2024 Disapproved -FEE REQUIRED RMARTIN
Note: *** NOTES ADDED BY RMARTIN 6/14/2024 11:20:00 AM *** Pump calls for a max breaker of 30 amps not 40. *** NOTES ADDED BY RMARTIN 6/14/2024 11:19:50 AM *** 6/7/2024 - PREVIOUS INSPECTION NOTES *** NOTES ADDED BY JMUNSON 6/7/2024 9:38:20 AM *** Pump calls for a max breaker of 30 amps not 40. 5/15/2024 - PREVIOUS INSPECTION NOTES 5/15/24 Power release and email sent to FPL @ 10am , once meter is set call in for final 5/13/2024 - PREVIOUS INSPECTION NOTES 5/13/234 Make all repairs before calling in re-inspection 3/27/2024 - PREVIOUS INSPECTION NOTES 3/27/24 1. No approved plans on site FBC 107.3.1 2. Breakers are required to be labeled NEC 210.5 3. Ground wire must be protected NEC 250.64 4. Liquid tight can not be in areas subjust to physical damaage NEC 356.12 5. Connection made for ground wire to ground rods are not approved per manufacturer specs 3/21/2024 - PREVIOUS INSPECTION NOTES NEED TO HAVE SCH. 80 PVC WHERE SUBJECT TO PHYSICAL DAMAGE NEC 300.5, NEED TO UN-COVER GROUND RODS TO BE INSPECTED, NEED TO PROVIDE SITE STICKS FOR SERVICE CONDUIT DEPTH, NEED APPROVED PLANS ON SITE, GROUNDING CONDUCTOR NEEDS TO BE PROTECTED/SLEEVED NEC 250.64
ELECTRIC FINAL 06/07/2024 Disapproved -FEE REQUIRED JMUNSON
Note: *** NOTES ADDED BY JMUNSON 6/7/2024 9:38:20 AM *** Pump calls for a max breaker of 30 amps not 40. 5/15/2024 - PREVIOUS INSPECTION NOTES 5/15/24 Power release and email sent to FPL @ 10am , once meter is set call in for final 5/13/2024 - PREVIOUS INSPECTION NOTES 5/13/234 Make all repairs before calling in re-inspection 3/27/2024 - PREVIOUS INSPECTION NOTES 3/27/24 1. No approved plans on site FBC 107.3.1 2. Breakers are required to be labeled NEC 210.5 3. Ground wire must be protected NEC 250.64 4. Liquid tight can not be in areas subjust to physical damaage NEC 356.12 5. Connection made for ground wire to ground rods are not approved per manufacturer specs 3/21/2024 - PREVIOUS INSPECTION NOTES NEED TO HAVE SCH. 80 PVC WHERE SUBJECT TO PHYSICAL DAMAGE NEC 300.5, NEED TO UN-COVER GROUND RODS TO BE INSPECTED, NEED TO PROVIDE SITE STICKS FOR SERVICE CONDUIT DEPTH, NEED APPROVED PLANS ON SITE, GROUNDING CONDUCTOR NEEDS TO BE PROTECTED/SLEEVED NEC 250.64
ELECTRIC FINAL 05/15/2024 PARTIALLY APPROVED MKRASKI
Note: 5/15/24 Power release and email sent to FPL @ 10am , once meter is set call in for final 5/13/2024 - PREVIOUS INSPECTION NOTES 5/13/234 Make all repairs before calling in re-inspection 3/27/2024 - PREVIOUS INSPECTION NOTES 3/27/24 1. No approved plans on site FBC 107.3.1 2. Breakers are required to be labeled NEC 210.5 3. Ground wire must be protected NEC 250.64 4. Liquid tight can not be in areas subjust to physical damaage NEC 356.12 5. Connection made for ground wire to ground rods are not approved per manufacturer specs 3/21/2024 - PREVIOUS INSPECTION NOTES NEED TO HAVE SCH. 80 PVC WHERE SUBJECT TO PHYSICAL DAMAGE NEC 300.5, NEED TO UN-COVER GROUND RODS TO BE INSPECTED, NEED TO PROVIDE SITE STICKS FOR SERVICE CONDUIT DEPTH, NEED APPROVED PLANS ON SITE, GROUNDING CONDUCTOR NEEDS TO BE PROTECTED/SLEEVED NEC 250.64
ELECTRIC FINAL 05/13/2024 CANCELLED BY APPLICANT WEB
Note: 3/27/2024 - PREVIOUS INSPECTION NOTES 3/27/24 1. No approved plans on site FBC 107.3.1 2. Breakers are required to be labeled NEC 210.5 3. Ground wire must be protected NEC 250.64 4. Liquid tight can not be in areas subjust to physical damaage NEC 356.12 5. Connection made for ground wire to ground rods are not approved per manufacturer specs 3/21/2024 - PREVIOUS INSPECTION NOTES NEED TO HAVE SCH. 80 PVC WHERE SUBJECT TO PHYSICAL DAMAGE NEC 300.5, NEED TO UN-COVER GROUND RODS TO BE INSPECTED, NEED TO PROVIDE SITE STICKS FOR SERVICE CONDUIT DEPTH, NEED APPROVED PLANS ON SITE, GROUNDING CONDUCTOR NEEDS TO BE PROTECTED/SLEEVED NEC 250.64
ELECTRIC FINAL 05/13/2024 Disapproved -FEE REQUIRED MKRASKI
Note: 5/13/234 Make all repairs before calling in re-inspection 3/27/2024 - PREVIOUS INSPECTION NOTES 3/27/24 1. No approved plans on site FBC 107.3.1 2. Breakers are required to be labeled NEC 210.5 3. Ground wire must be protected NEC 250.64 4. Liquid tight can not be in areas subjust to physical damaage NEC 356.12 5. Connection made for ground wire to ground rods are not approved per manufacturer specs 3/21/2024 - PREVIOUS INSPECTION NOTES NEED TO HAVE SCH. 80 PVC WHERE SUBJECT TO PHYSICAL DAMAGE NEC 300.5, NEED TO UN-COVER GROUND RODS TO BE INSPECTED, NEED TO PROVIDE SITE STICKS FOR SERVICE CONDUIT DEPTH, NEED APPROVED PLANS ON SITE, GROUNDING CONDUCTOR NEEDS TO BE PROTECTED/SLEEVED NEC 250.64
ELECTRIC FINAL 03/27/2024 Disapproved -FEE REQUIRED MKRASKI
Note: 3/27/24 1. No approved plans on site FBC 107.3.1 2. Breakers are required to be labeled NEC 210.5 3. Ground wire must be protected NEC 250.64 4. Liquid tight can not be in areas subjust to physical damaage NEC 356.12 5. Connection made for ground wire to ground rods are not approved per manufacturer specs 3/21/2024 - PREVIOUS INSPECTION NOTES NEED TO HAVE SCH. 80 PVC WHERE SUBJECT TO PHYSICAL DAMAGE NEC 300.5, NEED TO UN-COVER GROUND RODS TO BE INSPECTED, NEED TO PROVIDE SITE STICKS FOR SERVICE CONDUIT DEPTH, NEED APPROVED PLANS ON SITE, GROUNDING CONDUCTOR NEEDS TO BE PROTECTED/SLEEVED NEC 250.64
ELECTRIC FINAL 03/21/2024 Disapproved - NO FEE RMARTIN
Note: NEED TO HAVE SCH. 80 PVC WHERE SUBJECT TO PHYSICAL DAMAGE NEC 300.5, NEED TO UN-COVER GROUND RODS TO BE INSPECTED, NEED TO PROVIDE SITE STICKS FOR SERVICE CONDUIT DEPTH, NEED APPROVED PLANS ON SITE, GROUNDING CONDUCTOR NEEDS TO BE PROTECTED/SLEEVED NEC 250.64
ELECTRIC FINAL
Note: 3/28/2025 - PREVIOUS INSPECTION NOTES Need to close up un-used opening in pump control box on top of pump NEC 110.12 also approved plans call for 30 amp breaker for pump, there is a 40 amp installed, need to revise plan and wire accordingly 6/14/2024 - PREVIOUS INSPECTION NOTES *** NOTES ADDED BY RMARTIN 6/14/2024 11:20:00 AM *** Pump calls for a max breaker of 30 amps not 40. *** NOTES ADDED BY RMARTIN 6/14/2024 11:19:50 AM *** 6/7/2024 - PREVIOUS INSPECTION NOTES *** NOTES ADDED BY JMUNSON 6/7/2024 9:38:20 AM *** Pump calls for a max breaker of 30 amps not 40. 5/15/2024 - PREVIOUS INSPECTION NOTES 5/15/24 Power release and email sent to FPL @ 10am , once meter is set call in for final 5/13/2024 - PREVIOUS INSPECTION NOTES 5/13/234 Make all repairs before calling in re-inspection 3/27/2024 - PREVIOUS INSPECTION NOTES 3/27/24 1. No approved plans on site FBC 107.3.1 2. Breakers are required to be labeled NEC 210.5 3. Ground wire must be protected NEC 250.64 4. Liquid tight can not be in areas subjust to physical damaage NEC 356.12 5. Connection made for ground wire to ground rods are not approved per manufacturer specs 3/21/2024 - PREVIOUS INSPECTION NOTES NEED TO HAVE SCH. 80 PVC WHERE SUBJECT TO PHYSICAL DAMAGE NEC 300.5, NEED TO UN-COVER GROUND RODS TO BE INSPECTED, NEED TO PROVIDE SITE STICKS FOR SERVICE CONDUIT DEPTH, NEED APPROVED PLANS ON SITE, GROUNDING CONDUCTOR NEEDS TO BE PROTECTED/SLEEVED NEC 250.64

Review History

Department Status Date In Date Out
ELEC COMPLETE 02/02/2024 02/05/2024
Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM
ELEC HOLD 02/01/2024 02/01/2024
Note: Held By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM 1. Need to apply for a commercial electrical permit. 2. You always need to submit a electrical riser diagram that includes all wire sizes, breaker sizes and GFCI protection.

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
ADJUSTMENT 10% (¤13.50) 03/27/2025
ADMINISTRATIVE - COMMERCIAL ¤75.00 03/27/2025
INSPECTION- ELECTRICAL ¤60.00 03/27/2025
SURCHARGE FS 533.721 ¤2.00 03/27/2025
SURCHARGE - FS 468.631 ¤2.00 03/27/2025
Fees Total Due: ¤0.00 Total Paid: ¤125.50