Permit #2025031222

Permit Details

Status: COED

Parcel Id: 07-11-31-7035-00070-0380
GARAGE: 437 sqft
OPENED PORCH (WITH ROOF) : 182 sqft
OPENED PORCH (WITH ROOF) : 89 sqft
CONDITIONED SPACE: 1754 sqft
Total Square Footage: 2462 sqft
Block: 00070
Subdivision: -
Job Phone: 407-476-8195
Location Address: 31 BURNING VIEW LN
Type: BR - BUILDING RESIDENTIAL -SINGLE FAMILY
Issue Date: 09/25/2025
NOC: RECORDED
Applicant name: CARLETTE RENE WITTE
Owner: INB BFS LLC

Address

3670 MAGUIRE BOULEVARD

ORLANDO, FL 32803

Address

SUITE 220

ORLANDO, FL 32803

Lot: 0380
Contracted Stated Job Value: ¤165,000.00
Job Description: single family residence
Type: CN

Contractor

INNOVATIVE NATIONWIDE BUILDERS INC
Status Location Address State License Number Phone
ACTIVE

3670 MAGUIRE BLVD #220

,

CRC1330026 (Exp: 08/31/2026) 855-694-6634

Sub Contractors

TERRY BRICE DICKERSON
Status Location Address State License Number Phone
ACTIVE

4300 ST JOHN'S PARKWAY

ALPHARETTA, GA 30009

CCC1326209 (Exp: 08/31/2026) 407-548-6733
JOSEPH C WRIGHT
Status Location Address Mailing Address State License Number Phone Fax
ACTIVE

15 HARGROVE LANE

PALM COAST, FL 32137

UNIT 3 D

PALM COAST, FL 32137

EC13003278 (Exp: 08/31/2026) 386-447-9644 386-447-9633
HEATH EDWARD SANFORD
Status Location Address State License Number Phone
ACTIVE

126 EAST END RD

SAN MATEO, FL 32187

CFC1429896 (Exp: 08/31/2026) 386-871-8823
JASON LEE JAMES
Status Location Address State License Number Phone
ACTIVE

217 N WESTMONTE DR SUITE 1007

ALTAMONTE SPRINGS, FL 32714

CAC1820196 (Exp: 08/31/2026) 407-404-4000

Inspection History

Type Request Date Result Inspector
BLD - BUILDING FINAL 05/26/2026 FINAL APPROVED HCAMACHO
Note: 5/20/2026 - PREVIOUS INSPECTION NOTES 5/20/26 1. No paperwork on site for inspection FBC(A) 107.3.1 2. Multiple windows need adjustment. Will not line up properly to lock 3. Back right bedroom, right wall outlet; top of receptacle not working 4. Seal up top, front wall, above garage door. Can see daylight FBC 402.5.1.1 5. Kitchen outlets have no power NEC 210.8
BLD - BUILDING FINAL 05/20/2026 Disapproved -FEE REQUIRED MCONTRYMAN
Note: 5/20/26 1. No paperwork on site for inspection FBC(A) 107.3.1 2. Multiple windows need adjustment. Will not line up properly to lock 3. Back right bedroom, right wall outlet; top of receptacle not working 4. Seal up top, front wall, above garage door. Can see daylight FBC 402.5.1.1 5. Kitchen outlets have no power NEC 210.8
U -UTILITY RESIDENTIAL FINAL 05/20/2026 APPROVED TLOWE
Note: Inspector Notes from Inspection 9035 NO/CC NO IRR
ROW - FINAL APRON (AFTER POUR) 05/18/2026 APPROVED TPOLACEK
Note: AT THE TIME OF THE INSPECTION, ALL MINIMUM CITY REQUIREMENTS WERE MET. NIETHER THE INSPECTOR NOR THE CITY IS RESPONSIBLE IF, FOR WHATEVER REASON, SITE CONDITIONS CHANGE OVER TIME AFTER THE INSPECTION. IT IS THE BUILDER'S RESPONSIBILITY TO ENSURE THAT NOTHING CHANGES AFTER THIS INSPECTION IS APPROVED
ROW FIELD SURVEY /GRADING CERTIFICATION 05/18/2026 CANCELLED BY INSPECTOR TPOLACEK
Note: BASED ON THE ENGINEERS SIGNED AND SEALED LGDC MEETING THE COPC MINIMUM REQUIREMENTS AT THE TIME OF THIS INSPECTION, I AM APPROVING THIS DOCUMENT. Effective 03-25-26, the ROW Field Survey requirement is no longer in effect for Final Lot Grading and Drainage Certificates for new construction on subdivision and infill lots. All Final Lot Grading and Drainage Certificates for these projects will now be reviewed and approved only in the office. Field verification for the ROW-FIELD SURVEY will no longer be required as part of the standard approval process for these permit types
ROW - STORMWATER FINAL 05/18/2026 APPROVED TPOLACEK
Note: AT THE TIME OF THE INSPECTION, ALL MINIMUM CITY REQUIREMENTS WERE MET. NIETHER THE INSPECTOR NOR THE CITY IS RESPONSIBLE IF, FOR WHATEVER REASON, SITE CONDITIONS CHANGE OVER TIME AFTER THE INSPECTION. IT IS THE BUILDER'S RESPONSIBILITY TO ENSURE THAT NOTHING CHANGES AFTER THIS INSPECTION IS APPROVED
ROW- FINAL SURVEY/GRADING CERTIFICATION 05/14/2026 APPROVED EMADISON
Note:
ROW- FINAL SURVEY/GRADING CERTIFICATION 05/08/2026 Disapproved - NO FEE EMADISON
Note: ** 05/08/26 10 FT OFFSET SHOTS ARE REQUIRED ON ALL ADJACENT PROPERTIES YOU HAVE NO OFFSET SHOTS ** 3) The elevations on all adjacent properties at a minimum of 20-foot intervals on a 10-foot offset outside the property lines. Section 300.01 B(3) V-15
U-CROSS CONNECTION 05/07/2026 APPROVED - AS NOTED BVEIGA
Note: NO/CC NO IRR
ROW- PRE-APRON (PRE-POUR) 04/06/2026 APPROVED - AS NOTED EMADISON
Note: ** 04/06/26 READY TO POUR ** At the time of the inspection all minimum city requirements were met. It is the builder’s responsibility to ensure that nothing changes after this Inspection is approved. This includes but is not limited to, the Culvert Pipe Elevation from the time of the inspection approval to the concrete pour. **MAKE SURE THERE IS 3000 PSI CONCRETE REINFORCED WITH WWF 6X6.W1.4 MESH OR FIBERGLASS REINFORCED CONCRETE (FRC) DRAWING 300, E RESIDENTIAL CULVERT DETAIL _________________________________________________________________________________________________________________________ 4/2/2026 - PREVIOUS INSPECTION NOTES ** 04/02/26 CANCELLED VIA PHONE CALL FROM TYLER WITH INB SITE NOT READY FOR INSPECTION
ROW- PRE-APRON (PRE-POUR) 04/02/2026 CANCELLED BY APPLICANT EMADISON
Note: ** 04/02/26 CANCELLED VIA PHONE CALL FROM TYLER WITH INB SITE NOT READY FOR INSPECTION
ELECTRIC - EARLY POWER 03/03/2026 APPROVED HCAMACHO
Note: Inspector Notes from Inspection 2200 Authorize release of email.
GRAVITY SEWER TEST 02/12/2026 APPROVED MCONTRYMAN
SEWER TIE IN 02/12/2026 APPROVED MCONTRYMAN
PEP TANK INSTALLATION REQUEST 02/05/2026 APPROVED CBOWERMASTER
INSULATION 02/04/2026 APPROVED JSTEWART
Note: 2/3/2026 - PREVIOUS INSPECTION NOTES Previous Note not rectified.....1. Header box built in laundry room needs to be fire foamed around ceiling edges and and vent pipe FBCR 302.11 (Vent pipe Penetration thru the top of soffit into attic requires the annular space to be sealed (fire foam). 2/2/2026 - PREVIOUS INSPECTION NOTES 2/2/26 1. Header box built in laundry room needs to be fire foamed around ceiling edges and and vent pipe FBCR 302.11 2. Missinf foam around AH ceiling penetrations FBCR 302.11 3. Unused opening missing fire foam on shared wall with master BR and Master closet FBCR 302.11 4. Empty cavity behing front entry door needs fire foamed around ceiling edges FBCR 302.11 Inspector Notes from Inspection 2420 1/22/26 1. Duct layout does not match what is installed. Please have revised and approved layout by next inspection FBC(A) 107.4 2. Twisted studs in front entry way, left side wall 3. Broken window in guest bath 1/20/2026 - PREVIOUS INSPECTION NOTES 1/20/26: INCOMPLETE INSPECTION due to missing documents, etc. 1). Missing Energy calcs and FPA sheet in permit box laying on the ground. FBC [A]107.3.1 2). No address. FBCR 319.1 3). Could not inspect windows due to stucco in progress. FBC [A]107.4 4). 5ft head pressure not holding. FBC-P2503.5.1 NOTE: A full inspection will be required.
INSULATION 02/03/2026 Disapproved -FEE REQUIRED JSTEWART
Note: Previous Note not rectified.....1. Header box built in laundry room needs to be fire foamed around ceiling edges and and vent pipe FBCR 302.11 (Vent pipe Penetration thru the top of soffit into attic requires the annular space to be sealed (fire foam). 2/2/2026 - PREVIOUS INSPECTION NOTES 2/2/26 1. Header box built in laundry room needs to be fire foamed around ceiling edges and and vent pipe FBCR 302.11 2. Missinf foam around AH ceiling penetrations FBCR 302.11 3. Unused opening missing fire foam on shared wall with master BR and Master closet FBCR 302.11 4. Empty cavity behing front entry door needs fire foamed around ceiling edges FBCR 302.11 Inspector Notes from Inspection 2420 1/22/26 1. Duct layout does not match what is installed. Please have revised and approved layout by next inspection FBC(A) 107.4 2. Twisted studs in front entry way, left side wall 3. Broken window in guest bath 1/20/2026 - PREVIOUS INSPECTION NOTES 1/20/26: INCOMPLETE INSPECTION due to missing documents, etc. 1). Missing Energy calcs and FPA sheet in permit box laying on the ground. FBC [A]107.3.1 2). No address. FBCR 319.1 3). Could not inspect windows due to stucco in progress. FBC [A]107.4 4). 5ft head pressure not holding. FBC-P2503.5.1 NOTE: A full inspection will be required.
INSULATION 02/02/2026 Disapproved - NO FEE MCONTRYMAN
Note: 2/2/26 1. Header box built in laundry room needs to be fire foamed around ceiling edges and and vent pipe FBCR 302.11 2. Missinf foam around AH ceiling penetrations FBCR 302.11 3. Unused opening missing fire foam on shared wall with master BR and Master closet FBCR 302.11 4. Empty cavity behing front entry door needs fire foamed around ceiling edges FBCR 302.11 Inspector Notes from Inspection 2420 1/22/26 1. Duct layout does not match what is installed. Please have revised and approved layout by next inspection FBC(A) 107.4 2. Twisted studs in front entry way, left side wall 3. Broken window in guest bath 1/20/2026 - PREVIOUS INSPECTION NOTES 1/20/26: INCOMPLETE INSPECTION due to missing documents, etc. 1). Missing Energy calcs and FPA sheet in permit box laying on the ground. FBC [A]107.3.1 2). No address. FBCR 319.1 3). Could not inspect windows due to stucco in progress. FBC [A]107.4 4). 5ft head pressure not holding. FBC-P2503.5.1 NOTE: A full inspection will be required.
ALL ROUGH 01/22/2026 APPROVED - AS NOTED MCONTRYMAN
Note: 1/22/26 1. Duct layout does not match what is installed. Please have revised and approved layout by next inspection FBC(A) 107.4 2. Twisted studs in front entry way, left side wall 3. Broken window in guest bath 1/20/2026 - PREVIOUS INSPECTION NOTES 1/20/26: INCOMPLETE INSPECTION due to missing documents, etc. 1). Missing Energy calcs and FPA sheet in permit box laying on the ground. FBC [A]107.3.1 2). No address. FBCR 319.1 3). Could not inspect windows due to stucco in progress. FBC [A]107.4 4). 5ft head pressure not holding. FBC-P2503.5.1 NOTE: A full inspection will be required.
ALL ROUGH 01/20/2026 Disapproved -FEE REQUIRED RSIMS
Note: *** NOTES ADDED BY RSIMS 1/20/2026 1:33:43 PM *** 1/20/26: INCOMPLETE INSPECTION due to missing documents, etc. 1). Missing Energy calcs and FPA sheet in permit box laying on the ground. FBC [A]107.3.1 2). No address. FBCR 319.1 3). Could not inspect windows due to stucco in progress. FBC [A]107.4 4). 5ft head pressure not holding. FBC-P2503.5.1 NOTE: A full inspection will be required.
LATH/BRICK/ WATER BARRIER 01/16/2026 APPROVED JSTEWART
ELECTRIC-TUG 01/08/2026 APPROVED - AS NOTED JSTEWART
Note: Authorize release of email.
ROOF VALLEY & METAL 01/07/2026 APPROVED MCONTRYMAN
WALL SHEATHING 12/30/2025 APPROVED JSTEWART
ROOF SHEATHING / BRACES/TIES/DOWN CELL 12/30/2025 APPROVED JSTEWART
ROOF SHEATHING 12/30/2025 CANCELLED BY INSPECTOR JSTEWART
Note: Not needed.
TIE BEAM / LINTEL 12/16/2025 APPROVED JSTEWART
MONOLITHIC SLAB 12/05/2025 Disapproved -FEE REQUIRED JSTEWART
Note: Previous Notes not fully rectified........all column support pads reinforcement require 3" from soil (bottom,top,sides) FBC R404.1.3.3.7.4 12/4/2025 - PREVIOUS INSPECTION NOTES footing reinforcement thru out does not meet the required MIN 3" clearence from soil. Spots where reinforcement is laying directly on soil. FBC R404.1.3.3.7.4
MONOLITHIC SLAB 12/05/2025 APPROVED JSTEWART
Note: 12/5/2025 - PREVIOUS INSPECTION NOTES Previous Notes not fully rectified........all column support pads reinforcement require 3" from soil (bottom,top,sides) FBC R404.1.3.3.7.4 12/4/2025 - PREVIOUS INSPECTION NOTES footing reinforcement thru out does not meet the required MIN 3" clearence from soil. Spots where reinforcement is laying directly on soil. FBC R404.1.3.3.7.4
MONOLITHIC SLAB 12/04/2025 Disapproved - NO FEE JSTEWART
Note: footing reinforcement thru out does not meet the required MIN 3" clearence from soil. Spots where reinforcement is laying directly on soil. FBC R404.1.3.3.7.4
FORMBOARD SURVEY (OFFICE USE ONLY) 11/21/2025 APPROVED RRICKS
PLUMBING 1ST ROUGH UNDERGROUND 11/20/2025 APPROVED MGIBSON
GEOTECHNICAL REPORT APPROVAL (OFFICE USE) 11/13/2025 APPROVED PKNAPIK
WATER METER INSTALLATION REQUEST 10/22/2025 APPROVED CBOWERMASTER

Review History

Department Status Date In Date Out
SW1 HOLD 11/20/2025 11/20/2025
Note: Held By: RODNEY RICKS - (386)986-4726 - RRICKS@PALMCOASTGOV.COM The dimension along the front of the property 17.35 does not match the approved grading plan.
ZON COMPLETE 11/20/2025 11/20/2025
Note: Released By: ALISHA MOBLEY - (386)986-3751 - AMOBLEY@PALMCOASTGOV.COM
SW1 COMPLETE 11/20/2025 11/21/2025
Note: Released By: RODNEY RICKS - (386)986-4726 - RRICKS@PALMCOASTGOV.COM
ENGIN1 COMPLETE 11/20/2025 11/21/2025
Note: Released By: LEVI SALYERDS - (386)986-2575 - LSALYERDS@PALMCOASTGOV.COM
ZON COMPLETE 11/20/2025 11/21/2025
Note: Released By: CINDY CHIRI-GONCALVES - (386)986-4737 - CGONCALVES@PALMCOASTGOV.COM Had to reject submitted site plan and re up load the revised site plan in order to stamp it
BLD COMPLETE 11/13/2025 11/13/2025
Note: Released By: PETER KNAPIK - (386)986-3783 - PKNAPIK@PALMCOASTGOV.COM
MECH COMPLETE 10/21/2025 10/22/2025
Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM
MECH HOLD 10/08/2025 10/09/2025
Note: Held By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM Design location on the energy calcs and heatload need to be Daytona Beach
MECH COMPLETE 04/02/2025 04/04/2025
Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM
SW1 COMPLETE 04/01/2025 04/01/2025
Note: Released By: RODNEY RICKS - - RRICKS@PALMCOASTGOV.COM
SWALE COMPLETE 03/28/2025 04/16/2025
Note: Released By: LEVI SALYERDS - (386)986-2575 - LSALYERDS@PALMCOASTGOV.COM
BADMIN COMPLETE 03/27/2025 04/01/2025
Note: Released By: PETER KNAPIK - (386)986-3783 - PKNAPIK@PALMCOASTGOV.COM
BLD COMPLETE 03/27/2025 04/01/2025
Note: Released By: PETER KNAPIK - (386)986-3783 - PKNAPIK@PALMCOASTGOV.COM
CUSVC COMPLETE 03/27/2025 03/28/2025
Note: Released By: REBECCA SANDERS - - RSANDERS@PALMCOASTGOV.COM
ELEC COMPLETE 03/27/2025 04/01/2025
Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM
ENGIN1 COMPLETE 03/27/2025 03/28/2025
Note: Released By: LEVI SALYERDS - (386)986-2575 - LSALYERDS@PALMCOASTGOV.COM
GAS CANCEL 03/27/2025 03/31/2025
LOCATE COMPLETE 03/27/2025 03/28/2025
Note: Released By: TONI CHURCHILL - - TCHURCHILL@PALMCOASTGOV.COM
MECH HOLD 03/27/2025 03/31/2025
Note: Held By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM Energy calcs and state card from wrong address
SW1 HOLD 03/27/2025 03/31/2025
Note: Held By: RODNEY RICKS - - RRICKS@PALMCOASTGOV.COM Per COPC Technical Manual, there shall be a minimum of 0.3' fall from the top of the swale to the toe of slope along the property lines.
ZON COMPLETE 03/27/2025 03/27/2025
Note: Released By: ALISHA MOBLEY - (386)986-3751 - AMOBLEY@PALMCOASTGOV.COM

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
REINSPECTION RESIDENTIAL ¤40.00 05/20/2026
PLAN REVIEW - REVISION ¤32.50 04/10/2026
REINSPECTION RESIDENTIAL ¤40.00 04/10/2026
REINSPECTION RESIDENTIAL ¤40.00 04/10/2026
REINSPECTION RESIDENTIAL ¤40.00 04/10/2026
CONTRACTOR CHANGE ¤20.00 04/10/2026
FC IMPACT FEE EMS ¤62.00 09/25/2025
IMPACT FEE FIRE ¤434.51 09/25/2025
FC IMPACT FEE LAW ENFORCEMENT ¤218.00 09/25/2025
FC IMPACT FEE LIBRARY ¤268.00 09/25/2025
IMPACT FEE PARKS ¤1,828.01 09/25/2025
IMPACT FEE SCHOOL ¤5,450.00 09/25/2025
IMPACT FEE TRANSPORTATION ¤1,916.00 09/25/2025
WATER -IRRIGATION INSPECTION ¤25.00 09/25/2025
SURCHARGE FS 533.721 ¤11.07 09/25/2025
SURCHARGE - FS 468.631 ¤16.61 09/25/2025
SW ENG - FOUNDATION SURVEY ¤20.00 09/25/2025
SW ENG INSPECTION 80 ¤80.00 09/25/2025
SW ENG PRE APRON ¤30.00 09/25/2025
SW ENG - REVIEW 20 ¤20.00 09/25/2025
SW ENG RES REVIEW 200 ¤200.00 09/25/2025
SEWER CREDIT (¤2,465.75) 09/25/2025
SEWER INSPECTION ¤25.00 09/25/2025
SEWER CAPITAL FACILITY ¤6,120.52 09/25/2025
WATER CAPITAL FACILITY FEE ¤4,351.14 09/25/2025
SITE PLAN 30 ¤30.00 09/25/2025
WATER- TURN ON ¤25.00 09/25/2025
ADJUSTMENT 10% (¤123.02) 09/25/2025
ADMINISTRATIVE RESIDENTIAL ¤30.00 09/25/2025
INSPECTION - RESIDENTIAL ¤935.00 09/25/2025
PLAN REVIEW - RESIDENTIAL ¤265.20 09/25/2025
CONNECTION FEES ¤1,187.26 09/25/2025
Fees Total Due: ¤0.00 Total Paid: ¤21,172.05