I want to search for...

Permit #2025031352

Permit Details

Status: COED

Parcel Id: 06-12-31-5180-00000-0380
CONDITIONED SPACE: 2355 sqft
GARAGE: 424 sqft
OPENED PORCH (WITH ROOF) : 160 sqft
Total Square Footage: 2939 sqft
Subdivision: 2322 - RETREAT AT TOWN CENTER PHASE 1
Job Phone: 904-669-7000
Location Address: 42 MAHOGANY WAY
Type: BR - BUILDING RESIDENTIAL -SINGLE FAMILY
Issue Date: 04/30/2025
NOC: RECORDED
Applicant name: PAUL GILBERT AXTELL
Owner: TOLL SOUTHEAST LP CO INC

Address

1140 VIRGINIA DRIVE

FORT WASHINGTON, PA 19034

Lot: 38
Contracted Stated Job Value: ¤432,028.00
Job Description: SINGLE FAMILY HOME
Type: CN

Contractor

TOLL BROS INC
Status Location Address State License Number Phone
ACTIVE

40 EVEREST LN, STE 5

ST JOHNS, FL 32259

CGC60445 (Exp: 08/31/2026) 904-217-3852

Sub Contractors

JAMES F QUINN III
Status Location Address State License Number Phone
ACTIVE

3210 SW 40TH BLVD STE F

GAINESVILLE, FL 32608

EC13010994 (Exp: 08/31/2026) 352-378-9274
PAUL ERIC FORSTER
Status Location Address State License Number Phone
ACTIVE

6114 GOODMAN RD

JACKSONVILLE, FL 32244

CFC1429261 (Exp: 08/31/2026) 904-647-1820
DUSTIN L ESTEP
Status Location Address State License Number Phone Fax
ACTIVE

2041 N HIAWASSEE RD

APOPKA, FL 32703

CCC1330971 (Exp: 08/31/2026) 407-702-0206 352-988-6629
BRETT CHRISTIAN GIBSON
Status Location Address State License Number Phone
ACTIVE

250 SEGOVIA RD

ST AUGUSTINE, FL 32086

CAC1818423 (Exp: 08/31/2026) 904-229-8131
HARLEY M BRYAN
Status Location Address State License Number Phone
ACTIVE

5223 EDGEWOOD CT

ORMOND BEACH, FL 32174

LI26657 (Exp: 08/31/2028) 386-463-2700

Inspection History

Type Request Date Result Inspector
BLD - BUILDING FINAL 09/18/2025 FINAL APPROVED JSTEWART
Note: 9/12/2025 - PREVIOUS INSPECTION NOTES 9/12/25 1. Vent through soffit requires solid soffit 6' around it M1502.3 2. Upstairs tub/shower missing grout by door trim 3. Stair spindles need to be secured in place
BLD - BUILDING FINAL 09/12/2025 Disapproved - NO FEE MCONTRYMAN
Note: 9/12/25 1. Vent through soffit requires solid soffit 6' around it M1502.3 2. Upstairs tub/shower missing grout by door trim 3. Stair spindles need to be secured in place
U -UTILITY RESIDENTIAL FINAL 09/09/2025 FINAL APPROVED BWRIGHT
Note: Inspector Notes from Inspection 9035 reclaim irr-no cc
ROW - FINAL APRON (AFTER POUR) 09/05/2025 APPROVED FSLADISH
Note: 9/5/25 AT THE TIME OF THE INSPECTION, ALL MINIMUM CITY REQUIREMENTS WERE MET. IT IS THE BUILDER'S RESPONSIBILITY TO ENSURE THAT NOTHING CHANGES AFTER THIS INSPECTION IS APPROVED
ROW- FINAL SURVEY/GRADING CERTIFICATION 09/05/2025 APPROVED FSLADISH
ROW FIELD SURVEY /GRADING CERTIFICATION 09/05/2025 APPROVED FSLADISH
Note: 9/5/25 AT THE TIME OF THE INSPECTION, ALL MINIMUM CITY REQUIREMENTS WERE MET. IT IS THE BUILDER'S RESPONSIBILITY TO ENSURE THAT NOTHING CHANGES AFTER THIS INSPECTION IS APPROVED.
ROW - STORMWATER FINAL 09/05/2025 APPROVED FSLADISH
Note: 9/5/25 AT THE TIME OF THE INSPECTION, ALL MINIMUM CITY REQUIREMENTS WERE MET. IT IS THE BUILDER'S RESPONSIBILITY TO ENSURE THAT NOTHING CHANGES AFTER THIS INSPECTION IS APPROVED
U-CROSS CONNECTION 08/27/2025 APPROVED - AS NOTED LFITZGERALD
Note: reclaim irr-no cc
ROW- PRE-APRON (PRE-POUR) 08/20/2025 APPROVED FSLADISH
Note: 8/20/25 BUILDER REFER TO CONCRETE (FRC) DRAWING 300,E RESIDENTIAL CULVERT DETAIL BEFORE POURING. . IF FIBERGLASS OPTION IS USED, BUILDER REQUIRED TO USE 3000 PSI CONCRETE REINFORCED WITH WWF 6X6.W1.4 MESH OR FIBERGLASS REINFORCED DOCUMENTATION OF THE ( FRC) CONTAINING THE FIBERGLASS MUST BE ATTACHED TO THE PERMIT PRIOR TO REQUESTING AN AFTER-POUR INSPECTION. 8.b. IF MESH OPTION IS USED, IT SHALL BE IN PLACE AT THE TIME OF THE PRE-POUR AT THE TIME OF THE INSPECTION READY TO POUR, IF RAIN PLEASE, BUILDER SHOULD DOUBLE CHECK SITE FOR ANY STANDING WATER. ALSO VERIFY PIPE ELEVATION HAS NOT CHANGED. AT THE TIME OF THIS INSPECTION ALL MINIMUM COPC REQUIREMENTS ARE MET. BUILDER TO BE HELD RESPONSIBLE IF, FOR WHATEVER REASON, SITE CONDITIONS CHANGE OVER TIME AFTER THE INSPECTION. IT IS THE BUILDER'S RESPONSIBILITY TO ENSURE THAT NOTHING CHANGES AFTER THIS INSPECTION IS APPROVED.
ELECTRIC - EARLY POWER 08/15/2025 APPROVED MCONTRYMAN
Note: Inspector Notes from Inspection 2200 7/16/25 Okay to send email to FPL
WATER METER INSTALLATION REQUEST 07/31/2025 APPROVED CBOWERMASTER
ELECTRIC-TUG 07/16/2025 APPROVED - AS NOTED MCONTRYMAN
Note: 7/16/25 Okay to send email to FPL
INSULATION 07/10/2025 APPROVED MCONTRYMAN
Note: 7/9/2025 - PREVIOUS INSPECTION NOTES 7/9/25 1. Missing foam sealant around 2nd floor bedroom window FBCR 302.11
INSULATION 07/09/2025 Disapproved - NO FEE MCONTRYMAN
Note: 7/9/25 1. Missing foam sealant around 2nd floor bedroom window FBCR 302.11
GRAVITY SEWER TEST 07/07/2025 APPROVED - AS NOTED MGIBSON
Note: Inspector Notes from Inspection 2060 FBCR NEED ADDRESS POSTED FOR 9-1-1 THIS WAS A VIRTUAL INSPECTION
SEWER TIE IN 07/07/2025 APPROVED - AS NOTED MGIBSON
Note: Inspector Notes from Inspection 2060 FBCR NEED ADDRESS POSTED FOR 9-1-1 THIS WAS A VIRTUAL INSPECTION
LATH/BRICK/ WATER BARRIER 07/03/2025 APPROVED CVANSTRAHLEN
Note: Items from previous inspections will be check at insulation inspection Inspector Notes from Inspection 2420 Please fix items before next inspection #1-FBC [A]107.4-DUCT LAYOUT DOES NOT MATCH ENERGY CALCS ( please resummit e-cals for revision and approval second floor main flex is call for 14" instal is a 16" , first floor 2 plenum have different quantity of flex #2-FBCR 609.1-GAP AT WINDOW/DOOR REVEAL TOO LARGE > 1/4 " PER MANUFACTURERS SPECS ( front door , slidding door top , master bedroom window left side top and right side ) #3-Need pipe pvc support front bedroom 4" pipe #4-Smoke tetector combination on second floor , plans call for 2 CO Combination , instal is only 1
ALL ROUGH 07/02/2025 APPROVED - AS NOTED CVANSTRAHLEN
Note: Please fix items before next inspection #1-FBC [A]107.4-DUCT LAYOUT DOES NOT MATCH ENERGY CALCS ( please resummit e-cals for revision and approval second floor main flex is call for 14" instal is a 16" , first floor 2 plenum have different quantity of flex #2-FBCR 609.1-GAP AT WINDOW/DOOR REVEAL TOO LARGE > 1/4 " PER MANUFACTURERS SPECS ( front door , slidding door top , master bedroom window left side top and right side ) #3-Need pipe pvc support front bedroom 4" pipe #4-Smoke tetector combination on second floor , plans call for 2 CO Combination , instal is only 1
LATH/BRICK/ WATER BARRIER 07/01/2025 Disapproved - NO FEE CVANSTRAHLEN
Note: Please fix items before next inspection #1- all penetrations need to be seal on exterior walls , mark with red market ( circle ), drainer , AC wires and pipe , electrical wire , low voltage wire , etc Items from previous inspection still need to be check Inspector Notes from Inspection 2460 6/23/25 1. Truss KO2, marked on plans, still needs repair 6/9/2025 - PREVIOUS INSPECTION NOTES 6/9/25 All below areas are highlighted on the plans 1. Truss' FG01, FG02, FG03, A01 and K02 all need engineers letter of proper repair, and repair completed, before proceeding 2. Missing 2nd engineering on truss FG03 3. Missing screws for lvl on stairway per 9/S02 on page S1.2 4. Missing (3) 2x6 post by truss FGO3 per plans FBC(A) 107.4 5. Missing HUC2-10 hanger for porch beam. What is installed in not correct 6. Missing SDWC15600's on garage header per detail 7/S02 6/5/2025 - PREVIOUS INSPECTION NOTES 6/5/25 No stairs installed to go to second floor. Please schedule inspection once this is completed
ROOF SHEATHING / BRACES/TIES/DOWN CELL 06/23/2025 APPROVED - AS NOTED MCONTRYMAN
Note: 6/23/25 1. Truss KO2, marked on plans, still needs repair 6/9/2025 - PREVIOUS INSPECTION NOTES 6/9/25 All below areas are highlighted on the plans 1. Truss' FG01, FG02, FG03, A01 and K02 all need engineers letter of proper repair, and repair completed, before proceeding 2. Missing 2nd engineering on truss FG03 3. Missing screws for lvl on stairway per 9/S02 on page S1.2 4. Missing (3) 2x6 post by truss FGO3 per plans FBC(A) 107.4 5. Missing HUC2-10 hanger for porch beam. What is installed in not correct 6. Missing SDWC15600's on garage header per detail 7/S02 6/5/2025 - PREVIOUS INSPECTION NOTES 6/5/25 No stairs installed to go to second floor. Please schedule inspection once this is completed
ROOF VALLEY & METAL 06/16/2025 APPROVED MKRASKI
FORMBOARD SURVEY (OFFICE USE ONLY) 06/11/2025 APPROVED RRICKS
ROOF SHEATHING / BRACES/TIES/DOWN CELL 06/09/2025 Disapproved -FEE REQUIRED MCONTRYMAN
Note: 6/9/25 All below areas are highlighted on the plans 1. Truss' FG01, FG02, FG03, A01 and K02 all need engineers letter of proper repair, and repair completed, before proceeding 2. Missing 2nd engineering on truss FG03 3. Missing screws for lvl on stairway per 9/S02 on page S1.2 4. Missing (3) 2x6 post by truss FGO3 per plans FBC(A) 107.4 5. Missing HUC2-10 hanger for porch beam. What is installed in not correct 6. Missing SDWC15600's on garage header per detail 7/S02 6/5/2025 - PREVIOUS INSPECTION NOTES 6/5/25 No stairs installed to go to second floor. Please schedule inspection once this is completed
ROOF SHEATHING / BRACES/TIES/DOWN CELL 06/05/2025 Disapproved - NO FEE MCONTRYMAN
Note: 6/5/25 No stairs installed to go to second floor. Please schedule inspection once this is completed
WALL SHEATHING 06/04/2025 APPROVED MCONTRYMAN
MONOLITHIC SLAB 05/07/2025 APPROVED MCONTRYMAN
PLUMBING 1ST ROUGH UNDERGROUND 05/05/2025 APPROVED - AS NOTED MGIBSON
Note: FBCR NEED ADDRESS POSTED FOR 9-1-1

Review History

Department Status Date In Date Out
MECH COMPLETE 08/15/2025 08/18/2025
Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM
MECH COMPLETE 07/03/2025 07/03/2025
Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM
ENGIN1 COMPLETE 06/11/2025 06/11/2025
Note: Released By: RODNEY RICKS - (386)986-4726 - RRICKS@PALMCOASTGOV.COM
ZON COMPLETE 06/11/2025 06/11/2025
Note: Released By: ALISHA MOBLEY - (386)986-3751 - AMOBLEY@PALMCOASTGOV.COM
ENGIN1 COMPLETE 05/01/2025 05/02/2025
Note: Released By: LEVI SALYERDS - (386)986-2575 - LSALYERDS@PALMCOASTGOV.COM
SW1 COMPLETE 05/01/2025 05/06/2025
Note: Released By: PARREN FLANAGAN - (386)986-2392 - PFLANAGAN@PALMCOASTGOV.COM
ZON COMPLETE 05/01/2025 05/01/2025
Note: Released By: TRACEY DOAK - (386)986-3751 - TDOAK@PALMCOASTGOV.COM
ZON COMPLETE 04/28/2025 04/28/2025
Note: Released By: ALISHA MOBLEY - (386)986-3751 - AMOBLEY@PALMCOASTGOV.COM
BLD COMPLETE 04/28/2025 04/30/2025
Note: Released By: PETER KNAPIK - (386)986-3783 - PKNAPIK@PALMCOASTGOV.COM
MECH COMPLETE 04/28/2025 04/29/2025
Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM
BADMIN COMPLETE 03/31/2025 04/04/2025
Note: Released By: PETER KNAPIK - (386)986-3783 - PKNAPIK@PALMCOASTGOV.COM
BLD HOLD 03/31/2025 04/04/2025
Note: Held By: PETER KNAPIK - (386)986-3783 - PKNAPIK@PALMCOASTGOV.COM Please provide stair and hand rail details as per R311.7 through R311.7.8
CUSVC COMPLETE 03/31/2025 04/07/2025
Note: Released By: HALEIGH HAND - - HHAND@PALMCOASTGOV.COM
ELEC COMPLETE 03/31/2025 04/04/2025
Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM
ENGIN1 COMPLETE 03/31/2025 04/01/2025
Note: Released By: LEVI SALYERDS - (386)986-2575 - LSALYERDS@PALMCOASTGOV.COM
GAS COMPLETE 03/31/2025 04/01/2025
Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM
LOCATE COMPLETE 03/31/2025 04/02/2025
Note: Released By: CANDACE BOWERMASTER - - CBOWERMASTER@PALMCOASTGOV.COM
MECH COMPLETE 03/31/2025 04/02/2025
Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM
SW1 COMPLETE 03/31/2025 04/02/2025
Note: Released By: RODNEY RICKS - - RRICKS@PALMCOASTGOV.COM
ZON HOLD 03/31/2025 03/31/2025
Note: Held By: ALISHA MOBLEY - (386)986-3751 - AMOBLEY@PALMCOASTGOV.COM Pitched roofs. 1.All single-family and duplex buildings shall have a pitched roof covering a minimum of 65 percent of the overall floor area under the roof. 2.Pitched roofs shall have a minimum slope of 5:12 (five inches vertical rise for every 12 inches horizontal run) and shall have an overhang beyond the building wall; however, the overhang shall not encroach into an easement. 3.Flat roofed areas including, but not limited to, porches are permissible in the remaining 35 percent of floor area under roof. Please show that the 4/12 roofed area does not exceed the maximum 35% allowed for roof under 5/12
URB COMPLETE 03/31/2025 03/31/2025
Note: Released By: JOHN BEAUDET - (386)986-2456 - JBEAUDET@PALMCOASTGOV.COM

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
REINSPECTION RESIDENTIAL ¤40.00 06/09/2025
FC IMPACT FEE EMS ¤62.00 04/30/2025
IMPACT FEE FIRE ¤434.51 04/30/2025
FC IMPACT FEE LAW ENFORCEMENT ¤218.00 04/30/2025
FC IMPACT FEE LIBRARY ¤268.00 04/30/2025
IMPACT FEE PARKS ¤1,828.01 04/30/2025
IMPACT FEE SCHOOL ¤5,450.00 04/30/2025
IMPACT FEE TRANSPORTATION ¤3,502.00 04/30/2025
WATER METER W/OUT TAP ¤965.03 04/30/2025
SURCHARGE FS 533.721 ¤14.03 04/30/2025
SURCHARGE - FS 468.631 ¤21.04 04/30/2025
SW ENG - FOUNDATION SURVEY ¤20.00 04/30/2025
SW ENG INSPECTION 80 ¤80.00 04/30/2025
SW ENG PRE APRON ¤30.00 04/30/2025
SW ENG - REVIEW 20 ¤20.00 04/30/2025
SW ENG RES REVIEW 200 ¤200.00 04/30/2025
WATER PERMIT INSPECTION ¤40.00 04/30/2025
SITE PLAN 30 ¤30.00 04/30/2025
WATER-METER ¤874.47 04/30/2025
WATER- TURN ON ¤50.00 04/30/2025
ADJUSTMENT 10% (¤155.85) 04/30/2025
ADMINISTRATIVE RESIDENTIAL ¤30.00 04/30/2025
INSPECTION - RESIDENTIAL ¤1,190.75 04/30/2025
PLAN REVIEW - RESIDENTIAL ¤337.74 04/30/2025
Fees Total Due: ¤0.00 Total Paid: ¤15,549.73