I want to search for...
Permit #2025040093
Permit Details
Status: COED
| Parcel Id: 07-11-31-7013-00140-0400 |
| CONDITIONED SPACE: 1809 sqft |
| GARAGE: 406 sqft |
| OPENED PORCH (WITH ROOF) : 33 sqft |
| Total Square Footage: 2248 sqft |
| Block: 00140 |
| Subdivision: - |
| Job Phone: 239-571-5325 |
| Location Address: 94 BRITTANY LN |
| Type: BR - BUILDING RESIDENTIAL -SINGLE FAMILY |
| Issue Date: 04/10/2025 |
| NOC: RECORDED |
| Applicant name: RYAN SCOTT DAVIS |
| Owner: SYNERGY HOMES, LLC |
|
Address 581 NW MERCANTILE PL PORT ST LUCIE, FL 34986 |
|
Address STE 106 PORT ST LUCIE, FL 34986 |
| Lot: 0400 |
| Contracted Stated Job Value: ¤200,000.00 |
| Job Description: SINGLE FAMILY RESIDENCE |
| Type: CN |
Contractor
SYNERGY HOMES, LLC
| Status | Location Address | State License Number |
| ACTIVE |
1 HARGROVE GRADE, SUITE B1 PALM COAST, FL 32137 |
CBC1254289 (Exp: 08/31/2026) |
Sub Contractors
HEATH EDWARD SANFORD
| Status | Location Address | State License Number | Phone |
| ACTIVE |
126 EAST END RD SAN MATEO, FL 32187 |
CFC1429896 (Exp: 08/31/2026) | 386-871-8823 |
WILLIAM FRANK DUDLEY JR.
| Status | Location Address | State License Number | Phone |
| ACTIVE |
P.O. BOX 978 Bunnell, FL 32110 |
EC0003177 (Exp: 08/31/2026) | (386)437-3068 |
MICHAEL FRANK MORELLO
| Status | Location Address | State License Number | Phone | Fax |
| ACTIVE |
2 HARGROVE GRADE PALM COAST, FL 32164 |
CAC1819466 (Exp: 08/31/2026) | 386-445-5023 | 386-446-4614 |
TERRY BRICE DICKERSON
| Status | Location Address | State License Number | Phone |
| ACTIVE |
4300 ST JOHN'S PARKWAY ALPHARETTA, GA 30009 |
CCC1326209 (Exp: 08/31/2026) | 407-548-6733 |
Inspection History
| Type | Request Date | Result | Inspector |
| U -UTILITY RESIDENTIAL FINAL | 08/22/2025 | FINAL APPROVED | BWRIGHT |
| ROW - FINAL APRON (AFTER POUR) | 08/21/2025 | APPROVED | EMADISON |
| Note: AT THE TIME OF THE INSPECTION, ALL MINIMUM CITY REQUIREMENTS WERE MET. NIETHER THE INSPECTOR NOR THE CITY IS RESPONSIBLE IF, FOR WHATEVER REASON, SITE CONDITIONS CHANGE OVER TIME AFTER THE INSPECTION. IT IS THE BUILDER'S RESPONSIBILITY TO ENSURE THAT NOTHING CHANGES AFTER THIS INSPECTION IS APPROVED | |||
| ROW- FINAL SURVEY/GRADING CERTIFICATION | 08/21/2025 | APPROVED | EMADISON |
| ROW FIELD SURVEY /GRADING CERTIFICATION | 08/21/2025 | APPROVED | EMADISON |
| Note: AT THE TIME OF THE INSPECTION, ALL MINIMUM CITY REQUIREMENTS WERE MET. NIETHER THE INSPECTOR NOR THE CITY IS RESPONSIBLE IF, FOR WHATEVER REASON, SITE CONDITIONS CHANGE OVER TIME AFTER THE INSPECTION. IT IS THE BUILDER'S RESPONSIBILITY TO ENSURE THAT NOTHING CHANGES AFTER THIS INSPECTION IS APPROVED | |||
| ROW - STORMWATER FINAL | 08/21/2025 | APPROVED | EMADISON |
| Note: AT THE TIME OF THE INSPECTION, ALL MINIMUM CITY REQUIREMENTS WERE MET. NIETHER THE INSPECTOR NOR THE CITY IS RESPONSIBLE IF, FOR WHATEVER REASON, SITE CONDITIONS CHANGE OVER TIME AFTER THE INSPECTION. IT IS THE BUILDER'S RESPONSIBILITY TO ENSURE THAT NOTHING CHANGES AFTER THIS INSPECTION IS APPROVED | |||
| BLD - BUILDING FINAL | 08/21/2025 | CANCELLED BY APPLICANT | WEB |
| Note: 8/20/2025 - PREVIOUS INSPECTION NOTES Please fix items before next inspection #1-FBC[A] 110.5-ACCESS FOR INSPECTION - SPECIAL INSTRUCTIONS ( front door lock , code lock box , not notes for inspector ) #2-removed porta potty before final inspection | |||
| BLD - BUILDING FINAL | 08/21/2025 | FINAL APPROVED | MKRASKI |
| BLD - BUILDING FINAL | 08/20/2025 | Disapproved -FEE REQUIRED | CVANSTRAHLEN |
| Note: Please fix items before next inspection #1-FBC[A] 110.5-ACCESS FOR INSPECTION - SPECIAL INSTRUCTIONS ( front door lock , code lock box , not notes for inspector ) #2-removed porta potty before final inspection | |||
| ROW- PRE-APRON (PRE-POUR) | 08/01/2025 | APPROVED | PFLANAGAN |
| Note: IT'S YOUR RESPONSIBILITY TO CHECK THE CULVERT ELEVATIONS BEFORE POURING CONCRETE. ALL CONCRETE NEEDS TO BE A MINIMUM OF 3000PSI WITH FIBER OR WITH METAL MESH IN THE CONCRETE TO MEET ALL CITY'S STANDARDS. At the time of the inspection all minimum city requirements were met. It is the builders and the homowners responsibility to ensure that nothing changes after this Inspection is approved. It will not be on the city if any changes after this inspection. ------------------------------------------------------------------------ 7/29/2025 - PREVIOUS INSPECTION NOTES CANCELLED BY TEXT FROM GRAYSON AT 7:40AM | |||
| ROW- PRE-APRON (PRE-POUR) | 07/29/2025 | CANCELLED BY APPLICANT | PFLANAGAN |
| Note: CANCELLED BY TEXT FROM GRAYSON AT 7:40AM | |||
| ELECTRIC - EARLY POWER | 07/29/2025 | APPROVED - AS NOTED | JSTEWART |
| Note: Authorize release of email to FPL. 7/28/2025 - PREVIOUS INSPECTION NOTES Safe off romex for switch under kitchen sink (No caps, or covered holding box). NEC 110.27 Safe off Receptacle under kitchen sink (loose with conductors outside of the outlet). NEC 110.27 | |||
| ELECTRIC - EARLY POWER | 07/28/2025 | Disapproved - NO FEE | JSTEWART |
| Note: Safe off romex for switch under kitchen sink (No caps, or covered holding box). NEC 110.27 Safe off Receptacle under kitchen sink (loose with conductors outside of the outlet). NEC 110.27 | |||
| INSULATION | 07/11/2025 | APPROVED | FWILLIS |
| LATH/BRICK/ WATER BARRIER | 07/09/2025 | APPROVED | FWILLIS |
| ALL ROUGH | 07/09/2025 | APPROVED | JSTEWART |
| ROOF SHEATHING / BRACES/TIES/DOWN CELL | 06/27/2025 | APPROVED | FWILLIS |
| Note: 6/25/2025 - PREVIOUS INSPECTION NOTES 6/25/25: Roof Sheathing and Truss Engineering approved. 1). Portable toilet needs to be moved out from the neighboring swale and onto site property. FBC 3303.5 2). Silt fence needs to be repaired and maintained throughout build process. FBC 3307.1 3). Left side of house: remove any dirt that has been pushed to neighboring property beyond property markers. FBC 3307.1 | |||
| ROOF VALLEY & METAL | 06/25/2025 | APPROVED | RSIMS |
| Note: *** NOTES ADDED BY RSIMS 6/25/2025 11:10:14 AM *** 6/25/25: Roof sheathing approved during inspection 2460. | |||
| WALL SHEATHING | 06/25/2025 | APPROVED | RSIMS |
| ROOF SHEATHING / BRACES/TIES/DOWN CELL | 06/25/2025 | Disapproved - NO FEE | RSIMS |
| Note: *** NOTES ADDED BY RSIMS 6/25/2025 11:13:55 AM *** 6/25/25: Roof Sheathing and Truss Engineering approved. 1). Portable toilet needs to be moved out from the neighboring swale and onto site property. FBC 3303.5 2). Silt fence needs to be repaired and maintained throughout build process. FBC 3307.1 3). Left side of house: remove any dirt that has been pushed to neighboring property beyond property markers. FBC 3307.1 | |||
| U-CROSS CONNECTION | 06/25/2025 | APPROVED | DHANEY |
| GRAVITY SEWER TEST | 06/24/2025 | APPROVED - AS NOTED | MGIBSON |
| Note: Inspector Notes from Inspection 2095 Inspector Notes from Inspection 2060 5/23/2025 - PREVIOUS INSPECTION NOTES WATER SERVICE NOT RAN, FBCR P-311.1 PROVIDE PORTABLE RESTROOM THIS WAS APPROVED ON 5/23/25. NOT PARTIAL Inspector Notes from Inspection 2060 5/23/2025 - PREVIOUS INSPECTION NOTES WATER SERVICE NOT RAN, FBCR P-311.1 PROVIDE PORTABLE RESTROOM THIS WAS APPROVED ON 5/23/25. NOT PARTIAL THISWAS A VIRTUAL INSPECTION THIS WAS A VIRTUAL INSPECTION | |||
| SEWER TIE IN | 06/24/2025 | APPROVED - AS NOTED | MGIBSON |
| Note: Inspector Notes from Inspection 2060 5/23/2025 - PREVIOUS INSPECTION NOTES WATER SERVICE NOT RAN, FBCR P-311.1 PROVIDE PORTABLE RESTROOM THIS WAS APPROVED ON 5/23/25. NOT PARTIAL Inspector Notes from Inspection 2060 5/23/2025 - PREVIOUS INSPECTION NOTES WATER SERVICE NOT RAN, FBCR P-311.1 PROVIDE PORTABLE RESTROOM THIS WAS APPROVED ON 5/23/25. NOT PARTIAL THISWAS A VIRTUAL INSPECTION | |||
| TIE BEAM / LINTEL | 06/18/2025 | APPROVED | FWILLIS |
| MONOLITHIC SLAB | 06/09/2025 | APPROVED | FWILLIS |
| Note: 6/5/2025 - PREVIOUS INSPECTION NOTES 6/5/25 - MISSING UFER GROUND NEC250.52(3). ALSO SEVERAL CAVE-INS AROUND REBAR, PLEASE CLEAR TO HAVE AT LEAST 3" COVERAGE AS PER FBC R404.1.3.3.7 5/29/2025 - PREVIOUS INSPECTION NOTES 1. Multiple wah outs in footings FBC R404.1.3.3.7.4 2. Remove debris and vegitation from footings FBC R318.6.2 | |||
| MONOLITHIC SLAB | 06/05/2025 | Disapproved -FEE REQUIRED | FWILLIS |
| Note: 6/5/25 - MISSING UFER GROUND NEC250.52(3). ALSO SEVERAL CAVE-INS AROUND REBAR, PLEASE CLEAR TO HAVE AT LEAST 3" COVERAGE AS PER FBC R404.1.3.3.7 5/29/2025 - PREVIOUS INSPECTION NOTES 1. Multiple wah outs in footings FBC R404.1.3.3.7.4 2. Remove debris and vegitation from footings FBC R318.6.2 | |||
| MONOLITHIC SLAB | 05/29/2025 | Disapproved - NO FEE | MKRASKI |
| Note: 1. Multiple wah outs in footings FBC R404.1.3.3.7.4 2. Remove debris and vegitation from footings FBC R318.6.2 | |||
| PLUMBING 1ST ROUGH UNDERGROUND | 05/28/2025 | APPROVED - AS NOTED | MGIBSON |
| Note: 5/23/2025 - PREVIOUS INSPECTION NOTES WATER SERVICE NOT RAN, FBCR P-311.1 PROVIDE PORTABLE RESTROOM THIS WAS APPROVED ON 5/23/25. NOT PARTIAL | |||
| PLUMBING 1ST ROUGH UNDERGROUND | 05/23/2025 | PARTIALLY APPROVED | MGIBSON |
| Note: WATER SERVICE NOT RAN, FBCR P-311.1 PROVIDE PORTABLE RESTROOM | |||
| FORMBOARD SURVEY (OFFICE USE ONLY) | 05/09/2025 | APPROVED | PFLANAGAN |
| GEOTECHNICAL REPORT APPROVAL (OFFICE USE) | 05/08/2025 | APPROVED | PKNAPIK |
| WATER METER INSTALLATION REQUEST | 04/28/2025 | APPROVED | CBOWERMASTER |
Review History
| Department | Status | Date In | Date Out |
| BLD | COMPLETE | 05/08/2025 | 05/08/2025 |
| Note: Released By: PETER KNAPIK - (386)986-3783 - PKNAPIK@PALMCOASTGOV.COM | |||
| ENGIN1 | COMPLETE | 05/08/2025 | 05/08/2025 |
| Note: Released By: PARREN FLANAGAN - (386)986-2392 - PFLANAGAN@PALMCOASTGOV.COM | |||
| ZON | COMPLETE | 05/08/2025 | 05/08/2025 |
| Note: Released By: SCOTT THOMAS - (386)986-3780 - STHOMAS@PALMCOASTGOV.COM | |||
| BADMIN | COMPLETE | 04/02/2025 | 04/08/2025 |
| Note: Released By: PETER KNAPIK - (386)986-3783 - PKNAPIK@PALMCOASTGOV.COM | |||
| BLD | COMPLETE | 04/02/2025 | 04/08/2025 |
| Note: Released By: PETER KNAPIK - (386)986-3783 - PKNAPIK@PALMCOASTGOV.COM | |||
| CUSVC | COMPLETE | 04/02/2025 | 04/10/2025 |
| Note: Released By: HALEIGH HAND - - HHAND@PALMCOASTGOV.COM | |||
| ELEC | COMPLETE | 04/02/2025 | 04/07/2025 |
| Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM | |||
| ENGIN1 | COMPLETE | 04/02/2025 | 04/02/2025 |
| Note: Released By: LEVI SALYERDS - (386)986-2575 - LSALYERDS@PALMCOASTGOV.COM | |||
| GAS | CANCEL | 04/02/2025 | 04/04/2025 |
| LOCATE | COMPLETE | 04/02/2025 | 04/07/2025 |
| Note: Released By: CANDACE BOWERMASTER - - CBOWERMASTER@PALMCOASTGOV.COM | |||
| MECH | COMPLETE | 04/02/2025 | 04/04/2025 |
| Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM | |||
| SW1 | COMPLETE | 04/02/2025 | 04/09/2025 |
| Note: Released By: RODNEY RICKS - - RRICKS@PALMCOASTGOV.COM | |||
| ZON | COMPLETE | 04/02/2025 | 04/02/2025 |
| Note: Released By: ALISHA MOBLEY - (386)986-3751 - AMOBLEY@PALMCOASTGOV.COM | |||
| SWALE | COMPLETE | 04/02/2025 | 04/17/2025 |
| Note: Released By: LEVI SALYERDS - (386)986-2575 - LSALYERDS@PALMCOASTGOV.COM |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| REINSPECTION RESIDENTIAL | ¤40.00 | 08/22/2025 |
| REINSPECTION RESIDENTIAL | ¤40.00 | 08/22/2025 |
| FC IMPACT FEE EMS | ¤62.00 | 04/10/2025 |
| IMPACT FEE FIRE | ¤434.51 | 04/10/2025 |
| FC IMPACT FEE LAW ENFORCEMENT | ¤218.00 | 04/10/2025 |
| FC IMPACT FEE LIBRARY | ¤268.00 | 04/10/2025 |
| IMPACT FEE PARKS | ¤1,828.01 | 04/10/2025 |
| IMPACT FEE SCHOOL | ¤5,450.00 | 04/10/2025 |
| IMPACT FEE TRANSPORTATION | ¤1,916.00 | 04/10/2025 |
| WASTEWATER MAIN EXTENSION IMPA | ¤2,189.82 | 04/10/2025 |
| SURCHARGE FS 533.721 | ¤10.82 | 04/10/2025 |
| SURCHARGE - FS 468.631 | ¤16.23 | 04/10/2025 |
| SW ENG - FOUNDATION SURVEY | ¤20.00 | 04/10/2025 |
| SW ENG INSPECTION 80 | ¤80.00 | 04/10/2025 |
| SW ENG PRE APRON | ¤30.00 | 04/10/2025 |
| SW ENG - REVIEW 20 | ¤20.00 | 04/10/2025 |
| SW ENG RES REVIEW 200 | ¤200.00 | 04/10/2025 |
| WATER METER W/ TAP | ¤2,326.93 | 04/10/2025 |
| SEWER CREDIT | (¤1,146.15) | 04/10/2025 |
| WASTEWATER PERM INSPECTION | ¤40.00 | 04/10/2025 |
| SEWER CAPITAL FACILITY | ¤3,930.70 | 04/10/2025 |
| WATER CAPITAL FACILITY FEE | ¤3,496.74 | 04/10/2025 |
| WATER PERMIT REVIEW | ¤40.00 | 04/10/2025 |
| WATER MAIN EXTENSION IMPACT | ¤854.40 | 04/10/2025 |
| SITE PLAN 30 | ¤30.00 | 04/10/2025 |
| WATER- TURN ON | ¤50.00 | 04/10/2025 |
| ADJUSTMENT 10% | (¤120.20) | 04/10/2025 |
| ADMINISTRATIVE RESIDENTIAL | ¤30.00 | 04/10/2025 |
| INSPECTION - RESIDENTIAL | ¤913.00 | 04/10/2025 |
| PLAN REVIEW - RESIDENTIAL | ¤258.96 | 04/10/2025 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤23,527.77 |