I want to search for...
Permit #2025040908
Permit Details
Status: FINAL
| Parcel Id: 48-11-31-1710-00000-1000 |
| Block: 00000 |
| Subdivision: 1710 - |
| Job Phone: 386-793-1358 |
| Location Address: 30 BLUE OAK LN |
| Type: GEN - GENERATOR |
| Issue Date: 05/13/2025 |
| NOC: Unknown |
| Applicant name: JOSEPH PAUL BERNHARD |
| Owner: ROSS ANTHONY V & LEE H&W LIFE ESTATE |
|
Address 30 BLUE OAK LANE PALM COAST, FL 32137 |
| Lot: 1000 |
| Contracted Stated Job Value: ¤2,490.00 |
| Job Description: Install 24kw generator with 2-150amp transfer switches. Gas permit seperate. |
| Type: CN |
Contractor
PALM COAST ELECTRIC, INC
| Status | Location Address | State License Number | Phone |
| ACTIVE |
3 INDUSTRY DRIVE #8 PALM COAST, FL 32164 |
EC13008263 (Exp: 08/31/2026) | 386-793-1358 |
Inspection History
| Type | Request Date | Result | Inspector |
| ELECTRIC FINAL | 09/12/2025 | FINAL APPROVED | HCAMACHO |
| Note: Inspector Notes from Inspection 2150 Final inspection and start up complete, can not add final untill after elevation cert has been approved | |||
| ELEVATION CERTIFICATE-FINAL APPROVAL | 09/09/2025 | APPROVED | JMYERS |
| ELECTRIC UNDERGROUND | 07/17/2025 | CANCELLED BY INSPECTOR | MKRASKI |
| Note: Not needed | |||
| ELECTRIC UNDERGROUND | 07/17/2025 | APPROVED - AS NOTED | MKRASKI |
| Note: Final inspection and start up complete, can not add final untill after elevation cert has been approved | |||
| ELECTRIC UNDERGROUND | 06/20/2025 | CANCELLED BY APPLICANT | WEB |
Review History
| Department | Status | Date In | Date Out |
| PLFM | COMPLETE | 09/05/2025 | 09/09/2025 |
| Note: Released By: JORDAN MYERS, C.F.M - (386)986-4789 - JMYERS@PALMCOASTGOV.COM The Final elevation certificate has been approved. | |||
| PLFM | HOLD | 08/04/2025 | 08/05/2025 |
| Note: Held By: JORDAN MYERS, C.F.M - (386)986-4789 - JMYERS@PALMCOASTGOV.COM An old elevation certificate for the home was submitted. A new elevation certificate done for the generator is required. | |||
| GAS | COMPLETE | 04/22/2025 | 04/24/2025 |
| Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM | |||
| ELEC | COMPLETE | 04/16/2025 | 04/21/2025 |
| Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM | |||
| GAS | HOLD | 04/16/2025 | 04/22/2025 |
| Note: Held By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM Provide note on plans that generator exhaust must be minimum 10ft from any opening into the building per FBC Residential 2023 8Th edition M1905.2.5. If using the exception to 5ft, carbon monoxide detectors will be inspected on generator final. | |||
| ZON | COMPLETE | 04/16/2025 | 04/16/2025 |
| Note: Released By: ALISHA MOBLEY - (386)986-3751 - AMOBLEY@PALMCOASTGOV.COM | |||
| PLFM | INFORMATION | 04/16/2025 | 04/17/2025 |
| Note: Marked INFORMATION By: JORDAN MYERS, C.F.M - (386)986-4789 - JMYERS@PALMCOASTGOV.COM Property lies in a Special Flood Hazard Area. A Final elevation certificate will be required for the generator to ensure that it is at least 1' above the Base Flood Elevation. |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| ADJUSTMENT 10% | (¤12.25) | 05/13/2025 |
| ADMINISTRATIVE RESIDENTIAL | ¤30.00 | 05/13/2025 |
| INSPECTION - RESIDENTIAL | ¤60.00 | 05/13/2025 |
| PLAN REVIEW - MISC 32.50 | ¤32.50 | 05/13/2025 |
| SURCHARGE FS 533.721 | ¤2.00 | 05/13/2025 |
| SURCHARGE - FS 468.631 | ¤2.00 | 05/13/2025 |
| SITE PLAN 15 | ¤15.00 | 05/13/2025 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤129.25 |