Permit #2025041228
Permit Details
Status: EXPIRED
| Parcel Id: 07-11-31-7028-00710-0050 |
| Block: 00710 |
| Subdivision: 7028 - |
| Job Phone: 904-641-0600 |
| Location Address: 82 POINT OF WOODS DR |
| Type: ME - MECHANICAL |
| Issue Date: 04/23/2025 |
| NOC: Unknown |
| Applicant name: EDWIN HALL MILLER JR |
| Owner: BOUTIN JEROME & GHISLAINE |
|
Address 82 POINT OF WOODS DRIVE PALM COAST, FL 32164 |
| Lot: 0050 |
| Contracted Stated Job Value: ¤13,871.00 |
| Job Description: HVAC LIKE FOR LIKE TONNAGE |
| Type: CN |
Contractor
SNYDER CO.
| Status | Location Address | State License Number | Phone |
| ACTIVE |
83 ORANGE ST ST AUGUSTINE, FL 32084 |
CAC1813307 (Exp: 08/31/2026) | 904-641-0600 |
Inspection History
| Type | Request Date | Result | Inspector |
| HVAC FINAL | 10/22/2025 | Disapproved -FEE REQUIRED | RSIMS |
| Note: *** NOTES ADDED BY RSIMS 10/22/2025 8:49:45 AM *** 10/22/25: Previously listed items 2 and 5 remain unresolved. Virtual inspection available again if requested. ** 2). Missing sticker at electrical panel indicating air handler is located in the attic as required. FBC-M1401.1 > FBCEC-R403.3.6. STICKER DOES NOT MEET REQUIREMENTS. SEE BELOW FOR ENTIRE CODE REQUIREMENTS! >>> M1401.1 Installation. Heating and cooling equipment and appliances shall be installed in accordance with the manufacturer’s instructions and the requirements of this code. Airhandling units installed in attics shall comply with the Florida Building Code, Energy Conservation Section R403.3.6. R403.3.6 Air-handling units. Air-handling units shall not be installed in the attic when a home is brought into code compliance by Section R402. Air-handling units shall be allowed in attics for compliance by Section R405 only if the following conditions are met: 1.The service panel of the equipment is located within 6 feet (1829 mm) of an attic access. 2.A device is installed to alert the owner or shut down the unit when the condensation drain is not working properly. 3.The attic access opening is of sufficient size to replace the air handler. 4.A notice is posted on the electric service panel indicating to the homeowner that the air handler is located in the attic. Said notice shall be in all capitals, in 16-point type, with the title and first paragraph in bold: NOTICE TO HOMEOWNER A PART OF YOUR AIR-CONDITIONING SYSTEM, THE AIR HANDLER, IS LOCATED IN THE ATTIC. FOR PROPER, EFFICIENT AND ECONOMIC OPERATION OF THE AIRCONDITIONING SYSTEM, YOU MUST ENSURE THAT REGULAR MAINTENANCE IS PERFORMED. YOUR AIR-CONDITIONING SYSTEM IS EQUIPPED WITH ONE OR BOTH OF THE FOLLOWING: (1) A DEVICE THAT WILL ALERT YOU WHEN THE CONDENSATION DRAIN IS NOT WORKING PROPERLY OR (2) A DEVICE THAT WILL SHUT DOWN THE SYSTEM WHEN THE CONDENSATION DRAIN IS NOT WORKING. TO LIMIT POTENTIAL DAMAGE TO YOUR HOME, AND TO AVOID DISRUPTION OF SERVICE, IT IS RECOMMENDED THAT YOU ENSURE PROPER WORKING ORDER OF THESE DEVICES BEFORE EACH SEASON OF PEAK OPERATION. 5). LFMC into disconnect needs to be secured to wall within 12" of enclosure. NEC 350.30(A) ________________________________________________________________________________________________________________________ 10/20/2025 - PREVIOUS INSPECTION NOTES 10/20/25: NO ANSWER AT THE DOOR FOR THE INSPECTION. RANG DOORBELL AND KNOCKED LOUDLY TWICE. CALLED HOME OWNER AND LEFT MESSAGE AT ABOUT 1310. 1). Need access for inspection. FBC[A] 110.5 9/26/2025 - PREVIOUS INSPECTION NOTES 9/26/25: 1). Breakers for both units are oversized. ( ODU = Min.-19amp > Max.- 30amp / 40amp installed) -- (AHU = Min.-45amp > Max.-45amp / 50amp installed). NEC 240.1 2). Missing sticker at electrical panel indicating air handler is located in the attic as required. FBCEC-R403.3.6 3). Missing AHRI document required to be on site for inspection. FBC [A]107.3.1 4). Condensing Unit needs to be 3in above finished grade per FBCR M1305.1.4.1 5). LFMC into disconnect needs to be secured to wall within 12" of enclosure. NEC 350.30(A) | |||
| HVAC FINAL | 10/20/2025 | Disapproved - NO FEE | RSIMS |
| Note: *** NOTES ADDED BY RSIMS 10/20/2025 1:17:38 PM *** 10/20/25: NO ANSWER AT THE DOOR FOR THE INSPECTION. RANG DOORBELL AND KNOCKED LOUDLY TWICE. CALLED HOME OWNER AND LEFT MESSAGE AT ABOUT 1310. 1). Need access for inspection. FBC[A] 110.5 9/26/2025 - PREVIOUS INSPECTION NOTES 9/26/25: 1). Breakers for both units are oversized. ( ODU = Min.-19amp > Max.- 30amp / 40amp installed) -- (AHU = Min.-45amp > Max.-45amp / 50amp installed). NEC 240.1 2). Missing sticker at electrical panel indicating air handler is located in the attic as required. FBCEC-R403.3.6 3). Missing AHRI document required to be on site for inspection. FBC [A]107.3.1 4). Condensing Unit needs to be 3in above finished grade per FBCR M1305.1.4.1 5). LFMC into disconnect needs to be secured to wall within 12" of enclosure. NEC 350.30(A) | |||
| HVAC FINAL | 09/26/2025 | Disapproved -FEE REQUIRED | RSIMS |
| Note: *** NOTES ADDED BY RSIMS 9/26/2025 11:43:22 AM *** Added on 9/26/25: 5). LFMC into disconnect needs to be secured to wall within 12" of enclosure. NEC 350.30(A) *** NOTES ADDED BY RSIMS 9/26/2025 11:38:26 AM *** 9/26/25: 1). Breakers for both units are oversized. ( ODU = Min.-19amp > Max.- 30amp / 40amp installed) -- (AHU = Min.-45amp > Max.-45amp / 50amp installed). NEC 240.1 2). Missing sticker at electrical panel indicating air handler is located in the attic as required. FBCEC-R403.3.6 3). Missing AHRI document required to be on site for inspection. FBC [A]107.3.1 4). Condensing Unit needs to be 3in above finished grade per FBCR M1305.1.4.1 | |||
| HVAC FINAL | |||
| Note: 10/22/2025 - PREVIOUS INSPECTION NOTES 10/22/25: Previously listed items 2 and 5 remain unresolved. Virtual inspection available again if requested. ** 2). Missing sticker at electrical panel indicating air handler is located in the attic as required. FBC-M1401.1 > FBCEC-R403.3.6. STICKER DOES NOT MEET REQUIREMENTS. SEE BELOW FOR ENTIRE CODE REQUIREMENTS! >>> M1401.1 Installation. Heating and cooling equipment and appliances shall be installed in accordance with the manufacturer’s instructions and the requirements of this code. Airhandling units installed in attics shall comply with the Florida Building Code, Energy Conservation Section R403.3.6. R403.3.6 Air-handling units. Air-handling units shall not be installed in the attic when a home is brought into code compliance by Section R402. Air-handling units shall be allowed in attics for compliance by Section R405 only if the following conditions are met: 1.The service panel of the equipment is located within 6 feet (1829 mm) of an attic access. 2.A device is installed to alert the owner or shut down the unit when the condensation drain is not working properly. 3.The attic access opening is of sufficient size to replace the air handler. 4.A notice is posted on the electric service panel indicating to the homeowner that the air handler is located in the attic. Said notice shall be in all capitals, in 16-point type, with the title and first paragraph in bold: NOTICE TO HOMEOWNER A PART OF YOUR AIR-CONDITIONING SYSTEM, THE AIR HANDLER, IS LOCATED IN THE ATTIC. FOR PROPER, EFFICIENT AND ECONOMIC OPERATION OF THE AIRCONDITIONING SYSTEM, YOU MUST ENSURE THAT REGULAR MAINTENANCE IS PERFORMED. YOUR AIR-CONDITIONING SYSTEM IS EQUIPPED WITH ONE OR BOTH OF THE FOLLOWING: (1) A DEVICE THAT WILL ALERT YOU WHEN THE CONDENSATION DRAIN IS NOT WORKING PROPERLY OR (2) A DEVICE THAT WILL SHUT DOWN THE SYSTEM WHEN THE CONDENSATION DRAIN IS NOT WORKING. TO LIMIT POTENTIAL DAMAGE TO YOUR HOME, AND TO AVOID DISRUPTION OF SERVICE, IT IS RECOMMENDED THAT YOU ENSURE PROPER WORKING ORDER OF THESE DEVICES BEFORE EACH SEASON OF PEAK OPERATION. 5). LFMC into disconnect needs to be secured to wall within 12" of enclosure. NEC 350.30(A) ________________________________________________________________________________________________________________________ 10/20/2025 - PREVIOUS INSPECTION NOTES 10/20/25: NO ANSWER AT THE DOOR FOR THE INSPECTION. RANG DOORBELL AND KNOCKED LOUDLY TWICE. CALLED HOME OWNER AND LEFT MESSAGE AT ABOUT 1310. 1). Need access for inspection. FBC[A] 110.5 9/26/2025 - PREVIOUS INSPECTION NOTES 9/26/25: 1). Breakers for both units are oversized. ( ODU = Min.-19amp > Max.- 30amp / 40amp installed) -- (AHU = Min.-45amp > Max.-45amp / 50amp installed). NEC 240.1 2). Missing sticker at electrical panel indicating air handler is located in the attic as required. FBCEC-R403.3.6 3). Missing AHRI document required to be on site for inspection. FBC [A]107.3.1 4). Condensing Unit needs to be 3in above finished grade per FBCR M1305.1.4.1 5). LFMC into disconnect needs to be secured to wall within 12" of enclosure. NEC 350.30(A) |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| REINSPECTION RESIDENTIAL | ¤40.00 | 10/16/2025 |
| ADJUSTMENT 10% | (¤9.00) | 04/23/2025 |
| ADMINISTRATIVE RESIDENTIAL | ¤30.00 | 04/23/2025 |
| INSPECTION - MECHANICAL | ¤60.00 | 04/23/2025 |
| SURCHARGE FS 533.721 | ¤2.00 | 04/23/2025 |
| SURCHARGE - FS 468.631 | ¤2.00 | 04/23/2025 |
| REINSPECTION RESIDENTIAL | ¤40.00 | |
| Fees | Total Due: ¤40.00 | Total Paid: ¤125.00 |