Permit #2025041228

Permit Details

Status: EXPIRED

Parcel Id: 07-11-31-7028-00710-0050
Block: 00710
Subdivision: 7028 -
Job Phone: 904-641-0600
Location Address: 82 POINT OF WOODS DR
Type: ME - MECHANICAL
Issue Date: 04/23/2025
NOC: Unknown
Applicant name: EDWIN HALL MILLER JR
Owner: BOUTIN JEROME & GHISLAINE

Address

82 POINT OF WOODS DRIVE

PALM COAST, FL 32164

Lot: 0050
Contracted Stated Job Value: ¤13,871.00
Job Description: HVAC LIKE FOR LIKE TONNAGE
Type: CN

Contractor

SNYDER CO.
Status Location Address State License Number Phone
ACTIVE

83 ORANGE ST

ST AUGUSTINE, FL 32084

CAC1813307 (Exp: 08/31/2026) 904-641-0600

Inspection History

Type Request Date Result Inspector
HVAC FINAL 10/22/2025 Disapproved -FEE REQUIRED RSIMS
Note: *** NOTES ADDED BY RSIMS 10/22/2025 8:49:45 AM *** 10/22/25: Previously listed items 2 and 5 remain unresolved. Virtual inspection available again if requested. ** 2). Missing sticker at electrical panel indicating air handler is located in the attic as required. FBC-M1401.1 > FBCEC-R403.3.6. STICKER DOES NOT MEET REQUIREMENTS. SEE BELOW FOR ENTIRE CODE REQUIREMENTS! >>> M1401.1 Installation. Heating and cooling equipment and appliances shall be installed in accordance with the manufacturer’s instructions and the requirements of this code. Airhandling units installed in attics shall comply with the Florida Building Code, Energy Conservation Section R403.3.6. R403.3.6 Air-handling units. Air-handling units shall not be installed in the attic when a home is brought into code compliance by Section R402. Air-handling units shall be allowed in attics for compliance by Section R405 only if the following conditions are met: 1.The service panel of the equipment is located within 6 feet (1829 mm) of an attic access. 2.A device is installed to alert the owner or shut down the unit when the condensation drain is not working properly. 3.The attic access opening is of sufficient size to replace the air handler. 4.A notice is posted on the electric service panel indicating to the homeowner that the air handler is located in the attic. Said notice shall be in all capitals, in 16-point type, with the title and first paragraph in bold: NOTICE TO HOMEOWNER A PART OF YOUR AIR-CONDITIONING SYSTEM, THE AIR HANDLER, IS LOCATED IN THE ATTIC. FOR PROPER, EFFICIENT AND ECONOMIC OPERATION OF THE AIRCONDITIONING SYSTEM, YOU MUST ENSURE THAT REGULAR MAINTENANCE IS PERFORMED. YOUR AIR-CONDITIONING SYSTEM IS EQUIPPED WITH ONE OR BOTH OF THE FOLLOWING: (1) A DEVICE THAT WILL ALERT YOU WHEN THE CONDENSATION DRAIN IS NOT WORKING PROPERLY OR (2) A DEVICE THAT WILL SHUT DOWN THE SYSTEM WHEN THE CONDENSATION DRAIN IS NOT WORKING. TO LIMIT POTENTIAL DAMAGE TO YOUR HOME, AND TO AVOID DISRUPTION OF SERVICE, IT IS RECOMMENDED THAT YOU ENSURE PROPER WORKING ORDER OF THESE DEVICES BEFORE EACH SEASON OF PEAK OPERATION. 5). LFMC into disconnect needs to be secured to wall within 12" of enclosure. NEC 350.30(A) ________________________________________________________________________________________________________________________ 10/20/2025 - PREVIOUS INSPECTION NOTES 10/20/25: NO ANSWER AT THE DOOR FOR THE INSPECTION. RANG DOORBELL AND KNOCKED LOUDLY TWICE. CALLED HOME OWNER AND LEFT MESSAGE AT ABOUT 1310. 1). Need access for inspection. FBC[A] 110.5 9/26/2025 - PREVIOUS INSPECTION NOTES 9/26/25: 1). Breakers for both units are oversized. ( ODU = Min.-19amp > Max.- 30amp / 40amp installed) -- (AHU = Min.-45amp > Max.-45amp / 50amp installed). NEC 240.1 2). Missing sticker at electrical panel indicating air handler is located in the attic as required. FBCEC-R403.3.6 3). Missing AHRI document required to be on site for inspection. FBC [A]107.3.1 4). Condensing Unit needs to be 3in above finished grade per FBCR M1305.1.4.1 5). LFMC into disconnect needs to be secured to wall within 12" of enclosure. NEC 350.30(A)
HVAC FINAL 10/20/2025 Disapproved - NO FEE RSIMS
Note: *** NOTES ADDED BY RSIMS 10/20/2025 1:17:38 PM *** 10/20/25: NO ANSWER AT THE DOOR FOR THE INSPECTION. RANG DOORBELL AND KNOCKED LOUDLY TWICE. CALLED HOME OWNER AND LEFT MESSAGE AT ABOUT 1310. 1). Need access for inspection. FBC[A] 110.5 9/26/2025 - PREVIOUS INSPECTION NOTES 9/26/25: 1). Breakers for both units are oversized. ( ODU = Min.-19amp > Max.- 30amp / 40amp installed) -- (AHU = Min.-45amp > Max.-45amp / 50amp installed). NEC 240.1 2). Missing sticker at electrical panel indicating air handler is located in the attic as required. FBCEC-R403.3.6 3). Missing AHRI document required to be on site for inspection. FBC [A]107.3.1 4). Condensing Unit needs to be 3in above finished grade per FBCR M1305.1.4.1 5). LFMC into disconnect needs to be secured to wall within 12" of enclosure. NEC 350.30(A)
HVAC FINAL 09/26/2025 Disapproved -FEE REQUIRED RSIMS
Note: *** NOTES ADDED BY RSIMS 9/26/2025 11:43:22 AM *** Added on 9/26/25: 5). LFMC into disconnect needs to be secured to wall within 12" of enclosure. NEC 350.30(A) *** NOTES ADDED BY RSIMS 9/26/2025 11:38:26 AM *** 9/26/25: 1). Breakers for both units are oversized. ( ODU = Min.-19amp > Max.- 30amp / 40amp installed) -- (AHU = Min.-45amp > Max.-45amp / 50amp installed). NEC 240.1 2). Missing sticker at electrical panel indicating air handler is located in the attic as required. FBCEC-R403.3.6 3). Missing AHRI document required to be on site for inspection. FBC [A]107.3.1 4). Condensing Unit needs to be 3in above finished grade per FBCR M1305.1.4.1
HVAC FINAL
Note: 10/22/2025 - PREVIOUS INSPECTION NOTES 10/22/25: Previously listed items 2 and 5 remain unresolved. Virtual inspection available again if requested. ** 2). Missing sticker at electrical panel indicating air handler is located in the attic as required. FBC-M1401.1 > FBCEC-R403.3.6. STICKER DOES NOT MEET REQUIREMENTS. SEE BELOW FOR ENTIRE CODE REQUIREMENTS! >>> M1401.1 Installation. Heating and cooling equipment and appliances shall be installed in accordance with the manufacturer’s instructions and the requirements of this code. Airhandling units installed in attics shall comply with the Florida Building Code, Energy Conservation Section R403.3.6. R403.3.6 Air-handling units. Air-handling units shall not be installed in the attic when a home is brought into code compliance by Section R402. Air-handling units shall be allowed in attics for compliance by Section R405 only if the following conditions are met: 1.The service panel of the equipment is located within 6 feet (1829 mm) of an attic access. 2.A device is installed to alert the owner or shut down the unit when the condensation drain is not working properly. 3.The attic access opening is of sufficient size to replace the air handler. 4.A notice is posted on the electric service panel indicating to the homeowner that the air handler is located in the attic. Said notice shall be in all capitals, in 16-point type, with the title and first paragraph in bold: NOTICE TO HOMEOWNER A PART OF YOUR AIR-CONDITIONING SYSTEM, THE AIR HANDLER, IS LOCATED IN THE ATTIC. FOR PROPER, EFFICIENT AND ECONOMIC OPERATION OF THE AIRCONDITIONING SYSTEM, YOU MUST ENSURE THAT REGULAR MAINTENANCE IS PERFORMED. YOUR AIR-CONDITIONING SYSTEM IS EQUIPPED WITH ONE OR BOTH OF THE FOLLOWING: (1) A DEVICE THAT WILL ALERT YOU WHEN THE CONDENSATION DRAIN IS NOT WORKING PROPERLY OR (2) A DEVICE THAT WILL SHUT DOWN THE SYSTEM WHEN THE CONDENSATION DRAIN IS NOT WORKING. TO LIMIT POTENTIAL DAMAGE TO YOUR HOME, AND TO AVOID DISRUPTION OF SERVICE, IT IS RECOMMENDED THAT YOU ENSURE PROPER WORKING ORDER OF THESE DEVICES BEFORE EACH SEASON OF PEAK OPERATION. 5). LFMC into disconnect needs to be secured to wall within 12" of enclosure. NEC 350.30(A) ________________________________________________________________________________________________________________________ 10/20/2025 - PREVIOUS INSPECTION NOTES 10/20/25: NO ANSWER AT THE DOOR FOR THE INSPECTION. RANG DOORBELL AND KNOCKED LOUDLY TWICE. CALLED HOME OWNER AND LEFT MESSAGE AT ABOUT 1310. 1). Need access for inspection. FBC[A] 110.5 9/26/2025 - PREVIOUS INSPECTION NOTES 9/26/25: 1). Breakers for both units are oversized. ( ODU = Min.-19amp > Max.- 30amp / 40amp installed) -- (AHU = Min.-45amp > Max.-45amp / 50amp installed). NEC 240.1 2). Missing sticker at electrical panel indicating air handler is located in the attic as required. FBCEC-R403.3.6 3). Missing AHRI document required to be on site for inspection. FBC [A]107.3.1 4). Condensing Unit needs to be 3in above finished grade per FBCR M1305.1.4.1 5). LFMC into disconnect needs to be secured to wall within 12" of enclosure. NEC 350.30(A)

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
REINSPECTION RESIDENTIAL ¤40.00 10/16/2025
ADJUSTMENT 10% (¤9.00) 04/23/2025
ADMINISTRATIVE RESIDENTIAL ¤30.00 04/23/2025
INSPECTION - MECHANICAL ¤60.00 04/23/2025
SURCHARGE FS 533.721 ¤2.00 04/23/2025
SURCHARGE - FS 468.631 ¤2.00 04/23/2025
REINSPECTION RESIDENTIAL ¤40.00
Fees Total Due: ¤40.00 Total Paid: ¤125.00