Permit #2025041360
Permit Details
Status: COED
| Parcel Id: 06-12-31-5825-00010-0200 |
| Total Square Footage: 4345 sqft |
| Block: 00010 |
| Subdivision: 582500 - |
| Job Phone: 386-451-6532 |
| Location Address: 145 CITY PL BLDG 1 |
| Type: CIA - COMMERCIAL INTERIOR EXTERIOR ALTERATION |
| Issue Date: 06/05/2025 |
| NOC: RECORDED |
| Applicant name: LEONARD MARINACCIO III |
| Owner: CITY CENTRE OF PALM COAST INC |
|
Address 145 CITY PL PALM COAST, FL 32164 |
|
Address STE 301 PALM COAST, FL 32164 |
| Lot: 0200 |
| Contracted Stated Job Value: ¤325,000.00 |
| Job Description: BLDG 1 UNIT 200 INTERIOR OFFICE BUILD OUT |
| Type: CN |
Contractor
BOMAR CONSTRUCTION, INC.
| Status | Location Address | State License Number | Phone | Fax |
| ACTIVE |
27 SOUTH ORCHARD STREET ORMOND BEACH, FL 32174 |
CGC1517931 (Exp: 08/31/2026) | 386-677-8736 | 386-677-7726 |
Sub Contractors
PAUL NOEL BIELEFELDT
| Status | Location Address | State License Number | Phone | Fax |
| ACTIVE |
320 Aragon Street Holly Hill, FL 32117 |
EC0001646 (Exp: 08/31/2026) | (386) 677-0447 | 386-673-9868 |
STEVEN K LONGFRITZ
| Status | Location Address | Mailing Address | State License Number | Phone | Fax |
| ACTIVE |
D G MEYER INC DAYTONA, FL 32114 |
345 MADISON AVE DAYTONA, FL 32114 |
CMC1250907 (Exp: 08/31/2026) | 386-253-7774 | 386-255-9411 |
Inspection History
| Type | Request Date | Result | Inspector |
| BUILDING FINAL | 08/21/2025 | FINAL APPROVED | FWILLIS |
| U - UTILITY COMMERCIAL FINAL | 08/21/2025 | FINAL APPROVED | LFITZGERALD |
| HVAC FINAL | 08/20/2025 | FINAL APPROVED | CPISCITELLI |
| Note: | |||
| PLUMBING FINAL | 08/18/2025 | APPROVED | MGIBSON |
| FIRE FINAL | 08/18/2025 | APPROVED | RMARTIN |
| ELECTRIC FINAL | 08/18/2025 | APPROVED | RMARTIN |
| Note: 8/13/2025 - PREVIOUS INSPECTION NOTES 8/13/25 Need to lable RTU per electrical panel schedule, need gfci protection by sink NEC 210.8 b 5, Need to have correct panel schedule installed and labled, RTU Mini split is 20A, Larger condenser is 20A, AHU above ceiling is a 30A 8/1/2025 - PREVIOUS INSPECTION NOTES Inspector Notes from Inspection 3190 walls only There are other inspections that have to be completed before you can call in final inspections. | |||
| ELECTRIC FINAL | 08/13/2025 | Disapproved - NO FEE | RMARTIN |
| Note: 8/13/25 Need to lable RTU per electrical panel schedule, need gfci protection by sink NEC 210.8 b 5, Need to have correct panel schedule installed and labled, RTU Mini split is 20A, Larger condenser is 20A, AHU above ceiling is a 30A 8/1/2025 - PREVIOUS INSPECTION NOTES Inspector Notes from Inspection 3190 walls only There are other inspections that have to be completed before you can call in final inspections. | |||
| ABOVE CEILING | 08/08/2025 | APPROVED | RMARTIN |
| Note: New inspection due to canceled inspection 8/1/2025 - PREVIOUS INSPECTION NOTES HVAC rough not fully approved. This needs to be scheduled and approved prior to above ceiling inspection. | |||
| ABOVE CEILING | 08/07/2025 | CANCELLED BY APPLICANT | WEB |
| Note: 8/1/2025 - PREVIOUS INSPECTION NOTES HVAC rough not fully approved. This needs to be scheduled and approved prior to above ceiling inspection. | |||
| HVAC ROUGH | 08/04/2025 | APPROVED - AS NOTED | CPISCITELLI |
| Note: 1. Drain lines need to be insulated. C403.2.10 2. Need to see balancing dampers in the return ducts. I only see the supply dampers. 608.1 3. Need to have barb fitting and connector at connection of minisplit drain line to PVC. 314.2.2 4. Need to see fresh air connection at the termination. Unable to locate due to all the ceiling tiles installed | |||
| HVAC FINAL | 08/01/2025 | CANCELLED BY APPLICANT | WEB |
| ELECTRIC FINAL | 08/01/2025 | Disapproved - NO FEE | JMUNSON |
| Note: Inspector Notes from Inspection 3190 walls only There are other inspections that have to be completed before you can call in final inspections. | |||
| ABOVE CEILING | 08/01/2025 | CANCELLED BY APPLICANT | CPISCITELLI |
| Note: HVAC rough not fully approved. This needs to be scheduled and approved prior to above ceiling inspection. | |||
| INSULATION | 07/09/2025 | APPROVED | FWILLIS |
| FRAMING | 07/02/2025 | APPROVED | FWILLIS |
| ELECTRIC 2ND ROUGH | 07/02/2025 | APPROVED - AS NOTED | RMARTIN |
| Note: walls only | |||
| HVAC ROUGH | 07/02/2025 | PARTIALLY APPROVED | CPISCITELLI |
| Note: Inspected metal duct seams to be able to wrap. Inspected fire damper in entry. |
Review History
| Department | Status | Date In | Date Out |
| MECH | COMPLETE | 05/21/2025 | 05/30/2025 |
| Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM | |||
| BLD | COMPLETE | 05/21/2025 | 05/30/2025 |
| Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM | |||
| BLD | HOLD | 04/25/2025 | 05/08/2025 |
| Note: Held By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM COMMENTS BELOW PER THE 2023 FLORIDA BUILDING CODE (FBC), FLORIDA BUILDING CODE-EXISTING BUILDING, FLORIDA BUILDING CODE-ACCESSIBILITY (FBCA), FLORIDA STATUTES (F.S.), FLORIDA ADMINISTRATIVE CODE (F.A.C.) AND AUTHORITY HAVING JURISDICTION (A.H.J.). Provide level of alteration per Chapter 6 FBC Exiting Building 2023 | |||
| DSD | COMPLETE | 04/25/2025 | 04/25/2025 |
| Note: Released By: JACQUELINE GONZALEZ - (386)986-3751 - JGONZALEZ@PALMCOASTGOV.COM | |||
| ELEC | COMPLETE | 04/25/2025 | 04/29/2025 |
| Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM | |||
| FI1 | COMPLETE | 04/25/2025 | 04/29/2025 |
| Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM | |||
| MECH | HOLD | 04/25/2025 | 05/08/2025 |
| Note: Held By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM ALL COMMENTS BELOW PER THE 2023 FLORIDA BUILDING CODE-BUILDING, FLORIDA BUILDING CODE-EXISTING BUILDING, FLORIDA BUILDING CODE-MECHANICAL AND FLORIDA BUILDING CODE -ENERGY CONSERVATION. RESUBMITTED PLAN PAGES NEED TO BE CLOUDED AND MUST HAVE A REPONSE LETTER FROM THE ENGINEER SIGNED AND SEALED 1. Provide Heat load Calculation per C403.2.1 FBC Energy Conservation 2023 2. Provide note on plans for means of balancing for all supply, return, fresh air and exhaust per Section 608 FBC Mechanical 2023 | |||
| PLUM | COMPLETE | 04/25/2025 | 05/05/2025 |
| Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM | |||
| UD1 | COMPLETE | 04/25/2025 | 05/05/2025 |
| Note: Released By: GREG DEGLER - (386)986-2384 - GDEGLER@PALMCOASTGOV.COM | |||
| UD2 | COMPLETE | 04/25/2025 | 04/29/2025 |
| Note: Released By: DAN LEMONCELLO - - 1) no grease trap required when no kitchen plans |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| ADJUSTMENT 10% | (¤280.50) | 06/05/2025 |
| ADMINISTRATIVE - COMMERCIAL | ¤75.00 | 06/05/2025 |
| INSPECTION COMMERCIAL | ¤2,275.00 | 06/05/2025 |
| INSPECTION - FIRE COMMERCIAL | ¤81.25 | 06/05/2025 |
| PLAN REVIEW - COMMERCIAL | ¤373.75 | 06/05/2025 |
| SURCHARGE FS 533.721 | ¤25.25 | 06/05/2025 |
| SURCHARGE - FS 468.631 | ¤37.87 | 06/05/2025 |
| SITE PLAN 30 | ¤30.00 | 06/05/2025 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤2,617.62 |