Permit #2025041509
Permit Details
Status: FINAL
| Parcel Id: 07-11-31-7063-00620-0080 |
| Block: 00620 |
| Subdivision: - |
| Job Phone: 904-829-5038 |
| Location Address: 40 ZEPHYR LILY TRL |
| Type: GEN - GENERATOR |
| Issue Date: 05/12/2025 |
| NOC: RECORDED |
| Applicant name: NATHANAEL D MUNDELL |
| Owner: ROBERTS, JR, GEORGE |
|
Address 40 ZEPHYR LILLY TRAIL PALM COAST, FL 32137 |
| Lot: 0080 |
| Contracted Stated Job Value: ¤14,234.00 |
| Job Description: GENERATOR AND A 200 AMP AUTOMATIC TRANSFER SWITCH. |
| Type: CN |
Contractor
PURE ENERGY ELECTRICAL SERVICES LLC
| Status | Location Address | State License Number | Phone |
| ACTIVE |
840 RED FOX TRAIL ST AUGUSTINE, FL 32086 |
EC13010169 (Exp: 08/31/2026) | 904-829-5038 |
Inspection History
| Type | Request Date | Result | Inspector |
| ELECTRIC FINAL | 06/20/2025 | FINAL APPROVED | RMARTIN |
Review History
| Department | Status | Date In | Date Out |
| GAS | COMPLETE | 05/08/2025 | 05/12/2025 |
| Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM | |||
| GAS | HOLD | 05/05/2025 | 05/06/2025 |
| Note: Held By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM Provide note on plans that generator exhaust must be minimum 10ft from any opening into the building per FBC Residential 2023 8Th edition M1905.2.5. If using the exception to 5ft, carbon monoxide detectors will be inspected on generator final. | |||
| ELEC | COMPLETE | 05/05/2025 | 05/08/2025 |
| Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM | |||
| ELEC | HOLD | 04/29/2025 | 05/05/2025 |
| Note: Held By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM 1. Load calcs need to have correct NEC code year. | |||
| GAS | HOLD | 04/29/2025 | 05/01/2025 |
| Note: Held By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM Provide note on plans that generator exhaust must be minimum 10ft from any opening into the building per FBC Residential 2023 8Th edition M1905.2.5. If using the exception to 5ft, carbon monoxide detectors will be inspected on generator final. | |||
| ZON | COMPLETE | 04/29/2025 | 04/29/2025 |
| Note: Released By: TRACEY DOAK - (386)986-3751 - TDOAK@PALMCOASTGOV.COM |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| ADJUSTMENT 10% | (¤12.25) | 05/12/2025 |
| ADMINISTRATIVE RESIDENTIAL | ¤30.00 | 05/12/2025 |
| INSPECTION - RESIDENTIAL | ¤60.00 | 05/12/2025 |
| PLAN REVIEW - MISC 32.50 | ¤32.50 | 05/12/2025 |
| SURCHARGE FS 533.721 | ¤2.00 | 05/12/2025 |
| SURCHARGE - FS 468.631 | ¤2.00 | 05/12/2025 |
| SITE PLAN 15 | ¤15.00 | 05/12/2025 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤129.25 |