Permit #2025060698

Permit Details

Status: COED

Parcel Id: 03-12-31-1126-00000-2440
CONDITIONED SPACE: 2715 sqft
GARAGE: 614 sqft
OPENED PORCH (WITH ROOF) : 237 sqft
OPENED PORCH (WITH ROOF) : 208 sqft
Total Square Footage: 3774 sqft
Subdivision: 2344 - COLBERT LANDINGS PH 2
Job Phone: 813-917-1689
Location Address: 3 ARMENIA CT
Type: BR - BUILDING RESIDENTIAL -SINGLE FAMILY
Issue Date: 06/27/2025
NOC: RECORDED
Applicant name: SCOTT EVAN KEUNING
Owner: TAYLOR MORRISON OF FLORIDA INC

Address

1275 W GRANADA BLVD

ORMOND BEACH, FL 32174

Address

SUITE 3B

ORMOND BEACH, FL 32174

Lot: 244
Contracted Stated Job Value: ¤208,548.00
Job Description: Single Family Residence
Type: CN

Contractor

TAYLOR MORRISON OF FLORIDA INC
Status Location Address State License Number Phone
ACTIVE

7785 BAY MEADOWS WAY, SUITE 105

JACKSONVILLE, FL 32256

CBC1265083 (Exp: 08/31/2026) 813-917-1689

Sub Contractors

JOSEPH H STRADA JR
Status Location Address State License Number Phone
ACTIVE

3400 ST JOHNS PKWY

SANFORD, FL 32771

CAC043953 (Exp: 08/31/2026) 877-906-1113
JOSEPH HORATIO STRADA JR
Status Location Address State License Number Phone
ACTIVE

3400 ST JOHNS PARKWAY

SANFORD, FL 32771

EC13003715 (Exp: 08/31/2026) 877-906-1113
BENJAMIN MICHAEL RAY
Status Location Address Mailing Address State License Number Phone Fax
ACTIVE

6310 MABLETON PKWY

JACKSONVILLE, FL 32216

SUITE 1000

MABLETON, GA 30126

CFC1428415 (Exp: 08/31/2026) 904-861-5421 904-861-5426
CHASE RANDOLPH MASSEY
Status Location Address State License Number Phone
ACTIVE

10048 103RD ST

JACKSONVILLE, FL 32210

CCC1332486 (Exp: 08/31/2026) 904-248-1133

Inspection History

Type Request Date Result Inspector
ROW - STORMWATER FINAL 11/19/2025 APPROVED FSLADISH
Note: 11/19/25 REQUIRED SOD CORRECTION COMPLETED AT THE TIME OF THIS INSPECTION. AT THE TIME OF THIS INSPECTION ALL MINIMUM COPC REQUIREMENTS ARE MET. BUILDER TO BE HELD RESPONSIBLE IF, FOR WHATEVER REASON, SITE CONDITIONS CHANGE OVER TIME AFTER THE INSPECTION. IT IS THE BUILDER'S RESPONSIBILITY TO ENSURE THAT NOTHING CHANGES AFTER THIS INSPECTION IS APPROVED. _________________________________________________________________________________________________________________________ 11/14/2025 - PREVIOUS INSPECTION NOTES 11/14/25 AS PREVIOUSLY NOTED BUILDER WILL BE REQUIRED TO LAY SOD ON ENTIRE REAR BARE AREA AND MAY BE REQUIRED TO PIN IT BASED ON EROSION AND WASHOUT POTENTIAL. BUILDER IS RESPONSIBLE FOR ANY DETERIORATION OF REAR SLOPE. YOU ARE ALSO REQUIRED TO INSTALL SILT FENCE ON BOTH PROPERTY LINES BEFORE ROW FINAL PASSAGE. Inspector Notes from Inspection 9465 11/12/25 BASED ON GABES NOTES AND A CONVERSATION I JUST HAD WITH HIM THE REAR SLOPE IS ACCEPTABLE AT THE TIME OF THIS INSPECTION. BUILDER WILL BE REQUIRED TO LAY SOD ON ENTIRE REAR BARE AREA AND MAY BE REQUIRED TO PIN IT BASED ON EROSION AND WASHOUT POTENTIAL. BUILDER IS RESPONSIBLE FOR ANY DETERIORATION OF REAR SLOPE.
U -UTILITY RESIDENTIAL FINAL 11/14/2025 FINAL APPROVED BWRIGHT
BLD - BUILDING FINAL 11/14/2025 FINAL APPROVED BTAYLOR
Note: 11/12/2025 - PREVIOUS INSPECTION NOTES 1. Seal all openngs in garage - water heater lnes and bell transformer. 2. Outlets in garage back wall are not GFCI protected. 3. Outlet and ground by outside panel not secured to house.
U-CROSS CONNECTION 11/14/2025 APPROVED BWRIGHT
ROW - FINAL APRON (AFTER POUR) 11/14/2025 APPROVED FSLADISH
Note: 11/14/25 AT THE TIME OF THIS INSPECTION ALL MINIMUM COPC REQUIREMENTS ARE MET. BUILDER TO BE HELD RESPONSIBLE IF, FOR WHATEVER REASON, SITE CONDITIONS CHANGE OVER TIME AFTER THE INSPECTION. IT IS THE BUILDER'S RESPONSIBILITY TO ENSURE THAT NOTHING CHANGES AFTER THIS INSPECTION IS APPROVED. __________________________________________________________________________________________________________________________ Inspector Notes from Inspection 9465 11/12/25 BASED ON GABES NOTES AND A CONVERSATION I JUST HAD WITH HIM THE REAR SLOPE IS ACCEPTABLE AT THE TIME OF THIS INSPECTION. BUILDER WILL BE REQUIRED TO LAY SOD ON ENTIRE REAR BARE AREA AND MAY BE REQUIRED TO PIN IT BASED ON EROSION AND WASHOUT POTENTIAL. BUILDER IS RESPONSIBLE FOR ANY DETERIORATION OF REAR SLOPE.
ROW - STORMWATER FINAL 11/14/2025 Disapproved -FEE REQUIRED FSLADISH
Note: 11/14/25 AS PREVIOUSLY NOTED BUILDER WILL BE REQUIRED TO LAY SOD ON ENTIRE REAR BARE AREA AND MAY BE REQUIRED TO PIN IT BASED ON EROSION AND WASHOUT POTENTIAL. BUILDER IS RESPONSIBLE FOR ANY DETERIORATION OF REAR SLOPE. YOU ARE ALSO REQUIRED TO INSTALL SILT FENCE ON BOTH PROPERTY LINES BEFORE ROW FINAL PASSAGE. FRONT CURB AND GUTTER NEEDS TO BE CLEANED AND TRASH PICKED UP. Inspector Notes from Inspection 9465 11/12/25 BASED ON GABES NOTES AND A CONVERSATION I JUST HAD WITH HIM THE REAR SLOPE IS ACCEPTABLE AT THE TIME OF THIS INSPECTION. BUILDER WILL BE REQUIRED TO LAY SOD ON ENTIRE REAR BARE AREA AND MAY BE REQUIRED TO PIN IT BASED ON EROSION AND WASHOUT POTENTIAL. BUILDER IS RESPONSIBLE FOR ANY DETERIORATION OF REAR SLOPE.
BLD - BUILDING FINAL 11/12/2025 Disapproved - NO FEE PKNAPIK
Note: 1. Seal all openngs in garage - water heater lnes and bell transformer. 2. Outlets in garage back wall are not GFCI protected. 3. Outlet and ground by outside panel not secured to house.
ROW- FINAL SURVEY/GRADING CERTIFICATION 11/12/2025 APPROVED FSLADISH
Note: 11/12/25 BASED ON GABES NOTES AND A CONVERSATION I JUST HAD WITH HIM THE REAR SLOPE IS ACCEPTABLE. SURVEY MEETS MINIMUM COPC REQUIREMENTS AT THE TIME OF THIS INSPECTION. Note to inspector: Gabriel and I met with Bobby out in the field. There will be deviations from the approved grading plan in the back yard to allow for a less agreesive slope to the woodline. The shall be two 4:1 slopes shedding the water to the back and to the common area of the home to the street. If there are any questions call Rodney and Gabriel.
ROW FIELD SURVEY /GRADING CERTIFICATION 11/12/2025 APPROVED - AS NOTED FSLADISH
Note: 11/12/25 BASED ON GABES NOTES AND A CONVERSATION I JUST HAD WITH HIM THE REAR SLOPE IS ACCEPTABLE AT THE TIME OF THIS INSPECTION. BUILDER WILL BE REQUIRED TO LAY SOD ON ENTIRE REAR BARE AREA AND MAY BE REQUIRED TO PIN IT BASED ON EROSION AND WASHOUT POTENTIAL. BUILDER IS RESPONSIBLE FOR ANY DETERIORATION OF REAR SLOPE.
ELECTRIC - EARLY POWER 10/17/2025 APPROVED - AS NOTED BTAYLOR
Note: 10-17-25 1. Emailed FPL at 9:06. 10/16/2025 - PREVIOUS INSPECTION NOTES 10-16-25 1. Double outlet on island is not safed off. Inspector Notes from Inspection 2200 8-11-25 1. Emailed FPL at 10:22.
ELECTRIC - EARLY POWER 10/16/2025 Disapproved - NO FEE BTAYLOR
Note: 10-16-25 1. Double outlet on island is not safed off. Inspector Notes from Inspection 2200 8-11-25 1. Emailed FPL at 10:22.
ROW- PRE-APRON (PRE-POUR) 09/23/2025 APPROVED FSLADISH
Note: 9/23/25 BUILDER REFER TO CONCRETE (FRC) DRAWING 300,E RESIDENTIAL CULVERT DETAIL BEFORE POURING. . IF FIBERGLASS OPTION IS USED, BUILDER REQUIRED TO USE 3000 PSI CONCRETE REINFORCED WITH WWF 6X6.W1.4 MESH OR FIBERGLASS REINFORCED DOCUMENTATION OF THE ( FRC) CONTAINING THE FIBERGLASS MUST BE ATTACHED TO THE PERMIT PRIOR TO REQUESTING AN AFTER-POUR INSPECTION. 8.b. IF MESH OPTION IS USED, IT SHALL BE IN PLACE AT THE TIME OF THE PRE-POUR AT THE TIME OF THE INSPECTION READY TO POUR, IF RAIN PLEASE, BUILDER SHOULD DOUBLE CHECK SITE FOR ANY STANDING WATER. ALSO VERIFY PIPE ELEVATION HAS NOT CHANGED. NO EXPANSION JOINTS ALLOWED
GRAVITY SEWER TEST 09/17/2025 APPROVED - AS NOTED MGIBSON
Note: THIS WAS A VIRTUAL INSPECTION
SEWER TIE IN 09/17/2025 APPROVED - AS NOTED MGIBSON
Note: Inspector Notes from Inspection 2075 THIS WAS A VIRTUAL INSPECTION THIS WAS A VIRTUAL INSPECTION
INSULATION 09/12/2025 APPROVED MCONTRYMAN
Note: 9/11/2025 - PREVIOUS INSPECTION NOTES 9-11-25 1. Bath fan isis missing cover for the connection. 9/10/2025 - PREVIOUS INSPECTION NOTES 9/10/25 Previous note not rectified 1. Master bath fan still not wired in 9/9/2025 - PREVIOUS INSPECTION NOTES 9-9-25 1. Bath fans are not wired in. Inspector Notes from Inspection 2420 9-3-25 1. Hole in top of electrical panel needs steel plug. 2. All of the bathroom fans are not wired in. Check at insulation.
INSULATION 09/11/2025 Disapproved - NO FEE BTAYLOR
Note: 9-11-25 1. Bath fan isis missing cover for the connection. 9/10/2025 - PREVIOUS INSPECTION NOTES 9/10/25 Previous note not rectified 1. Master bath fan still not wired in 9/9/2025 - PREVIOUS INSPECTION NOTES 9-9-25 1. Bath fans are not wired in. Inspector Notes from Inspection 2420 9-3-25 1. Hole in top of electrical panel needs steel plug. 2. All of the bathroom fans are not wired in. Check at insulation.
INSULATION 09/10/2025 Disapproved -FEE REQUIRED MCONTRYMAN
Note: 9/10/25 Previous note not rectified 1. Master bath fan still not wired in 9/9/2025 - PREVIOUS INSPECTION NOTES 9-9-25 1. Bath fans are not wired in. Inspector Notes from Inspection 2420 9-3-25 1. Hole in top of electrical panel needs steel plug. 2. All of the bathroom fans are not wired in. Check at insulation.
INSULATION 09/09/2025 Disapproved - NO FEE BTAYLOR
Note: 9-9-25 1. Bath fans are not wired in. Inspector Notes from Inspection 2420 9-3-25 1. Hole in top of electrical panel needs steel plug. 2. All of the bathroom fans are not wired in. Check at insulation.
ALL ROUGH 09/03/2025 APPROVED - AS NOTED BTAYLOR
Note: 9-3-25 1. Hole in top of electrical panel needs steel plug. 2. All of the bathroom fans are not wired in. Check at insulation.
LATH/BRICK/ WATER BARRIER 08/13/2025 APPROVED BTAYLOR
Note: Inspector Notes from Inspection 2460 8-5-25 1. Truss A12 is not repaired properly. 2. Truss A04 engineering nails are all hanging out the side. 3. Truss A01 missing bearing blocks on both sides.
ROOF VALLEY & METAL 08/13/2025 APPROVED BTAYLOR
Note: Inspector Notes from Inspection 2460 8-5-25 1. Truss A12 is not repaired properly. 2. Truss A04 engineering nails are all hanging out the side. 3. Truss A01 missing bearing blocks on both sides.
ELECTRIC-TUG 08/11/2025 APPROVED - AS NOTED BTAYLOR
Note: 8-11-25 1. Emailed FPL at 10:22.
WALL SHEATHING 08/05/2025 APPROVED BTAYLOR
ROOF SHEATHING / BRACES/TIES/DOWN CELL 08/05/2025 APPROVED - AS NOTED BTAYLOR
Note: 8-5-25 1. Truss A12 is not repaired properly. 2. Truss A04 engineering nails are all hanging out the side. 3. Truss A01 missing bearing blocks on both sides.
MONOLITHIC SLAB 07/22/2025 APPROVED MCONTRYMAN
PLUMBING 1ST ROUGH UNDERGROUND 07/18/2025 APPROVED MGIBSON
Note: 7/17/2025 - PREVIOUS INSPECTION NOTES FBCR-P2503.5 HEAD TEST NOT HOLDING
PLUMBING 1ST ROUGH UNDERGROUND 07/17/2025 Disapproved -FEE REQUIRED MGIBSON
Note: FBCR-P2503.5 HEAD TEST NOT HOLDING
FORMBOARD SURVEY (OFFICE USE ONLY) 07/16/2025 APPROVED RRICKS
WATER METER INSTALLATION REQUEST 07/09/2025 APPROVED CBOWERMASTER

Review History

Department Status Date In Date Out
BLD COMPLETE 09/02/2025 09/04/2025
Note: Released By: PETER KNAPIK - (386)986-3783 - PKNAPIK@PALMCOASTGOV.COM
SW1 COMPLETE 07/16/2025 07/16/2025
Note: Released By: RODNEY RICKS - (386)986-4726 - RRICKS@PALMCOASTGOV.COM
ZON COMPLETE 07/16/2025 07/16/2025
Note: Released By: LIBBY RAYBURN - - LRAYBURN@PALMCOASTGOV.COM
ZON COMPLETE 06/25/2025 06/25/2025
Note: Released By: ALISHA MOBLEY - (386)986-3751 - AMOBLEY@PALMCOASTGOV.COM
BADMIN COMPLETE 06/16/2025 06/23/2025
Note: Released By: PETER KNAPIK - (386)986-3783 - PKNAPIK@PALMCOASTGOV.COM
BLD COMPLETE 06/16/2025 06/23/2025
Note: Released By: PETER KNAPIK - (386)986-3783 - PKNAPIK@PALMCOASTGOV.COM
CUSVC COMPLETE 06/16/2025 06/24/2025
Note: Released By: MICHELLE MCPARTLAND - -
ELEC COMPLETE 06/16/2025 06/23/2025
Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM
ENGIN1 COMPLETE 06/16/2025 06/17/2025
Note: Released By: LEVI SALYERDS - (386)986-2575 - LSALYERDS@PALMCOASTGOV.COM
GAS CANCEL 06/16/2025 06/23/2025
LOCATE COMPLETE 06/16/2025 06/20/2025
Note: Released By: CANDACE BOWERMASTER - - CBOWERMASTER@PALMCOASTGOV.COM
MECH COMPLETE 06/16/2025 06/23/2025
Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM
SW1 COMPLETE 06/16/2025 06/18/2025
Note: Released By: RODNEY RICKS - (386)986-4726 - RRICKS@PALMCOASTGOV.COM Approved contingent on final survey depicting a clearly defined rear yard drainage swale moving stormwater to the front of the home.
ZON HOLD 06/16/2025 06/17/2025
Note: Held By: CINDY CHIRI-GONCALVES - (386)986-4737 - CGONCALVES@PALMCOASTGOV.COM Landscape plan please indicate irrigation as St Augstine grass requires it landscape plan does not match the home

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
RSI REINSPECTION 1 ¤35.00 11/18/2025
REINSPECTION RESIDENTIAL ¤40.00 11/10/2025
REINSPECTION RESIDENTIAL ¤40.00 11/10/2025
FC IMPACT FEE EMS ¤62.00 06/27/2025
IMPACT FEE FIRE ¤434.51 06/27/2025
FC IMPACT FEE LAW ENFORCEMENT ¤218.00 06/27/2025
FC IMPACT FEE LIBRARY ¤268.00 06/27/2025
IMPACT FEE PARKS ¤1,828.01 06/27/2025
IMPACT FEE TRANSPORTATION ¤3,502.00 06/27/2025
WATER METER W/OUT TAP ¤965.03 06/27/2025
SURCHARGE FS 533.721 ¤16.92 06/27/2025
SURCHARGE - FS 468.631 ¤25.38 06/27/2025
SW ENG - FOUNDATION SURVEY ¤20.00 06/27/2025
SW ENG INSPECTION 80 ¤80.00 06/27/2025
SW ENG PRE APRON ¤30.00 06/27/2025
SW ENG - REVIEW 20 ¤20.00 06/27/2025
SW ENG RES REVIEW 200 ¤200.00 06/27/2025
WASTEWATER PERM INSPECTION ¤80.00 06/27/2025
WASTEWATER PERM REVIEW ¤25.00 06/27/2025
SEWER CAPITAL FACILITY ¤3,613.92 06/27/2025
WATER CAPITAL FACILITY FEE ¤3,039.48 06/27/2025
WATER PERMIT INSPECTION ¤40.00 06/27/2025
WATER PERMIT REVIEW ¤25.00 06/27/2025
SITE PLAN 30 ¤30.00 06/27/2025
WATER-METER ¤965.03 06/27/2025
WATER- TURN ON ¤50.00 06/27/2025
WATER- TURN ON ¤50.00 06/27/2025
ADJUSTMENT 10% (¤187.97) 06/27/2025
ADMINISTRATIVE RESIDENTIAL ¤30.00 06/27/2025
INSPECTION - RESIDENTIAL ¤1,441.00 06/27/2025
PLAN REVIEW - RESIDENTIAL ¤408.72 06/27/2025
Fees Total Due: ¤0.00 Total Paid: ¤17,395.03