Permit #2025060735
Permit Details
Status: FINAL
| Parcel Id: 07-11-31-7002-00060-0230 |
| Block: 00060 |
| Subdivision: 7002 - |
| Job Phone: 386-586-9144 |
| Location Address: 14 FERNHAM LN |
| Type: GEN - GENERATOR |
| Issue Date: 07/15/2025 |
| NOC: Unknown |
| Applicant name: JOHN EDWARD GAMBONE |
| Owner: PAYTAS WAYNE F & PATRICIA A PAYTAS H&W |
|
Address 14 FERNHAM LANE PALM COAST, FL 32137 |
| Lot: 0230 |
| Contracted Stated Job Value: ¤2,390.00 |
| Job Description: install customer supplied generator |
| Type: CN |
Contractor
BREAKERS ELECTRICAL CONSTRUCTION, INC
| Status | Location Address | Mailing Address | State License Number | Phone |
| ACTIVE |
15 HARGROVE LN PALM COAST, FL 32137 |
1G PALM COAST, FL 32137 |
EC13006037 (Exp: 08/31/2026) | 386-586-9144 |
Inspection History
| Type | Request Date | Result | Inspector |
| ELECTRIC FINAL | 09/17/2025 | FINAL APPROVED | HCAMACHO |
| Note: 8/27/2025 - PREVIOUS INSPECTION NOTES 1. A representative of electric contractor is required to be onsite for start up and inspection. (Please call Assigned inspector in the morning of scheduled inspection to determine time of Arrival.) 2. Please install a CO detector in the Master Bath/dressing room closest to the window that the Generator is within 10ft of the opening. ( Ceiling is conventional frame and hard to get above window, so a wall mount above french doors will be sufficient) this install is do to Bath/Dressing room has doors that make it a seperate space. M1905.2.5 Exhaust location. | |||
| ELECTRIC FINAL | 08/27/2025 | Disapproved - NO FEE | JSTEWART |
| Note: 1. A representative of electric contractor is required to be onsite for start up and inspection. (Please call Assigned inspector in the morning of scheduled inspection to determine time of Arrival.) 2. Please install a CO detector in the Master Bath/dressing room closest to the window that the Generator is within 10ft of the opening. ( Ceiling is conventional frame and hard to get above window, so a wall mount above french doors will be sufficient) this install is do to Bath/Dressing room has doors that make it a seperate space. M1905.2.5 Exhaust location. | |||
| GAS FINAL | 08/27/2025 | FINAL APPROVED | JSTEWART |
| GAS ROUGH | 08/20/2025 | APPROVED | HCAMACHO |
Review History
| Department | Status | Date In | Date Out |
| GAS | COMPLETE | 07/15/2025 | 07/15/2025 |
| Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM | |||
| ELEC | COMPLETE | 06/23/2025 | 06/26/2025 |
| Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM | |||
| GAS | HOLD | 06/23/2025 | 06/25/2025 |
| Note: Held By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM Provide note on plans that generator exhaust must be minimum 10ft from any opening into the building per FBC Residential 2023 8Th edition M1905.2.5. If using the exception to 5ft, carbon monoxide detectors will be inspected on generator final. (Second Request) | |||
| ELEC | HOLD | 06/17/2025 | 06/23/2025 |
| Note: Held By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM 1. #3 copper is not rated for the 110 amp breaker in the 26 KW generator. NEC 2020 310.16 | |||
| GAS | HOLD | 06/17/2025 | 06/23/2025 |
| Note: Held By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM Provide note on plans that generator exhaust must be minimum 10ft from any opening into the building per FBC Residential 2023 8Th edition M1905.2.5. If using the exception to 5ft, carbon monoxide detectors will be inspected on generator final. | |||
| ZON | COMPLETE | 06/17/2025 | 06/17/2025 |
| Note: Released By: CINDY CHIRI-GONCALVES - (386)986-4737 - CGONCALVES@PALMCOASTGOV.COM | |||
| PLFM | COMPLETE | 06/17/2025 | 06/18/2025 |
| Note: Released By: JORDAN MYERS, C.F.M - (386)986-4789 - JMYERS@PALMCOASTGOV.COM According to the Site Plan submitted 6/17/25 and FEMA FIRMs, the generator will not fall inside the SFHA. No elevation certificate will be required. |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| ADJUSTMENT 10% | (¤12.25) | 07/15/2025 |
| ADMINISTRATIVE RESIDENTIAL | ¤30.00 | 07/15/2025 |
| INSPECTION - RESIDENTIAL | ¤60.00 | 07/15/2025 |
| PLAN REVIEW - MISC 32.50 | ¤32.50 | 07/15/2025 |
| SURCHARGE FS 533.721 | ¤2.00 | 07/15/2025 |
| SURCHARGE - FS 468.631 | ¤2.00 | 07/15/2025 |
| SITE PLAN 15 | ¤15.00 | 07/15/2025 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤129.25 |