I want to search for...
Permit #2025061011
Permit Details
Status: FINAL
| Parcel Id: 07-11-31-7081-00170-0040 |
| Block: 00170 |
| Subdivision: 7081 - |
| Job Phone: 904-885-0891 |
| Location Address: 129 BLARE DR |
| Type: EL - ELECTRICAL |
| Issue Date: 06/23/2025 |
| NOC: Unknown |
| Applicant name: DANIEL JOSEPH SCHWARZKOPF |
| Owner: WILLACY HEADLEY G & ANNETTE (LIFE ESTATE) |
|
Address 129 BLARE DR PALM COAST, FL 32137 |
| Lot: 0040 |
| Contracted Stated Job Value: ¤2,200.00 |
| Job Description: Remove and replace one meter can |
| Type: CN |
Contractor
ANCHOR ELECTRIC OF FLORIDA, INC.
| Status | Location Address | State License Number | Phone |
| ACTIVE |
4601 E MOODY BLVD D6 PALM COAST, FL 32164 |
EC13010351 (Exp: 08/31/2026) | 386-313-6211 |
Inspection History
| Type | Request Date | Result | Inspector |
| ELECTRIC FINAL | 07/22/2025 | APPROVED | CVANSTRAHLEN |
| Note: | |||
| ELECTRIC FINAL | 07/21/2025 | Disapproved - NO FEE | MKRASKI |
| Note: 1. Protect ground rods from physical damage NEC 250.53(A)(4) 2. Protect ground wire from physical damage NEC 250.64(A)(2) 3. Breaker for AHU circuit is undersized per heater sticker on unit NEC 440.4 4. Can not locate 2nd ground rod per plans (ground rods must also be 5/8'') NEC 250.52(5)(B) |
Review History
| Department | Status | Date In | Date Out |
| ELEC | COMPLETE | 06/23/2025 | 06/23/2025 |
| Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| ADJUSTMENT 10% | (¤12.25) | 06/23/2025 |
| ADMINISTRATIVE RESIDENTIAL | ¤30.00 | 06/23/2025 |
| INSPECTION- ELECTRICAL | ¤60.00 | 06/23/2025 |
| PLAN REVIEW - MISC 32.50 | ¤32.50 | 06/23/2025 |
| SURCHARGE FS 533.721 | ¤2.00 | 06/23/2025 |
| SURCHARGE - FS 468.631 | ¤2.00 | 06/23/2025 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤114.25 |