Permit #2025070327
Permit Details
Status: FINAL
| Parcel Id: 07-11-31-7057-00690-0060 |
| Block: 00690 |
| Subdivision: 7057 - |
| Job Phone: 386-586-9144 |
| Location Address: 154 ULYSSES TRL |
| Type: GEN - GENERATOR |
| Issue Date: 07/25/2025 |
| NOC: Unknown |
| Applicant name: JOHN EDWARD GAMBONE |
| Owner: GALKA DAVID & MELODY H&W |
|
Address 154 ULYSSES TRAIL PALM COAST, FL 32164 |
| Lot: 0060 |
| Contracted Stated Job Value: ¤2,322.00 |
| Job Description: install customer 24kw |
| Type: CN |
Contractor
BREAKERS ELECTRICAL CONSTRUCTION, INC
| Status | Location Address | Mailing Address | State License Number | Phone |
| ACTIVE |
15 HARGROVE LN PALM COAST, FL 32137 |
1G PALM COAST, FL 32137 |
EC13006037 (Exp: 08/31/2026) | 386-586-9144 |
Inspection History
| Type | Request Date | Result | Inspector |
| ELECTRIC FINAL | 08/26/2025 | FINAL APPROVED | BTAYLOR |
| ELECTRIC FINAL | 08/22/2025 | CANCELLED BY APPLICANT | WEB |
Review History
| Department | Status | Date In | Date Out |
| GAS | COMPLETE | 07/24/2025 | 07/25/2025 |
| Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM | |||
| GAS | HOLD | 07/23/2025 | 07/24/2025 |
| Note: Held By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM 1. Provide note on plans that generator exhaust must be minimum 10ft from any opening into the building per FBC Residential 2023 8Th edition M1905.2.5. If using the exception to 5ft, carbon monoxide detectors will be inspected on generator final. (Third Request) | |||
| ZON | HOLD | 07/23/2025 | 07/23/2025 |
| Note: Held By: ALISHA MOBLEY - (386)986-3751 - AMOBLEY@PALMCOASTGOV.COM Please turn in original document. What you submitted is not an original it is a copy. We must have original with wet signature. When you come in to drop this one off let staff know that you need to complete the one you previously dropped off that was not approved. You will need to complete the form. Fill in blanks and add wife to the top line of the original. We cannot accept these documents until they are approved first. | |||
| ZON | COMPLETE | 07/23/2025 | 07/23/2025 |
| Note: Released By: ALISHA MOBLEY - (386)986-3751 - AMOBLEY@PALMCOASTGOV.COM | |||
| ZON | HOLD | 07/17/2025 | 07/17/2025 |
| Note: Held By: ALISHA MOBLEY - (386)986-3751 - AMOBLEY@PALMCOASTGOV.COM Please complete form .Blanks should state generator All owners on the deed must sign. Wife must be added on the top and she must sign and her signature must be notarized as well. | |||
| SW1 | COMPLETE | 07/15/2025 | 07/23/2025 |
| Note: Released By: GABRIEL BERTOLA - (386)986-7660 - GBERTOLA@PALMCOASTGOV.COM | |||
| ZON | HOLD | 07/15/2025 | 07/15/2025 |
| Note: Held By: ALISHA MOBLEY - (386)986-3751 - AMOBLEY@PALMCOASTGOV.COM Generator located in 5ft utility easement. A 2ft easement encroachment must be signed by all owners on deed and notarized. Once electronic copy is approved we will ask for original. Adding stormwater review for approval of the encroachment. | |||
| GAS | HOLD | 07/15/2025 | 07/16/2025 |
| Note: Held By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM 1. Provide note on plans that generator exhaust must be minimum 10ft from any opening into the building per FBC Residential 2023 8Th edition M1905.2.5. If using the exception to 5ft, carbon monoxide detectors will be inspected on generator final. 2. No gas permit applied for (Second Request) | |||
| ELEC | COMPLETE | 07/15/2025 | 07/21/2025 |
| Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM | |||
| ELEC | COMPLETE | 07/09/2025 | 07/10/2025 |
| Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM | |||
| GAS | HOLD | 07/09/2025 | 07/10/2025 |
| Note: Held By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM 1. Provide note on plans that generator exhaust must be minimum 10ft from any opening into the building per FBC Residential 2023 8Th edition M1905.2.5. If using the exception to 5ft, carbon monoxide detectors will be inspected on generator final. 2. No gas permit applied for | |||
| ZON | HOLD | 07/09/2025 | 07/09/2025 |
| Note: Held By: ALISHA MOBLEY - (386)986-3751 - AMOBLEY@PALMCOASTGOV.COM Please show setback from generator to property line on site plan. Must meet a 5ft setback to not be located in the 5ft utility easement |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| ADJUSTMENT 10% | (¤12.25) | 07/25/2025 |
| ADMINISTRATIVE RESIDENTIAL | ¤30.00 | 07/25/2025 |
| INSPECTION - RESIDENTIAL | ¤60.00 | 07/25/2025 |
| PLAN REVIEW - MISC 32.50 | ¤32.50 | 07/25/2025 |
| RECORDING FEE REIMBURSE DOC | ¤44.00 | 07/25/2025 |
| SURCHARGE FS 533.721 | ¤2.00 | 07/25/2025 |
| SURCHARGE - FS 468.631 | ¤2.00 | 07/25/2025 |
| SITE PLAN 15 | ¤15.00 | 07/25/2025 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤173.25 |