I want to search for...
Permit #2025080351
Permit Details
Status: FINAL
| Parcel Id: 07-11-31-7034-00620-0030 |
| Block: 00620 |
| Subdivision: 7034 - |
| Job Phone: (386)437-3068 |
| Location Address: 28 ELLSWORTH DR |
| Type: GEN - GENERATOR |
| Issue Date: 08/18/2025 |
| NOC: RECORDED |
| Applicant name: WILLIAM FRANK DUDLEY JR. |
| Owner: FRIED MARGARET E & EDWARD M H&W LIFE ESTATE |
|
Address 28 ELLSWORTH DRIVE PALM COAST, FL 32164 |
| Lot: 0030 |
| Contracted Stated Job Value: ¤13,650.00 |
| Job Description: 24KW GENERATOR AND TRANSFER SWITCH |
| Type: CN |
Contractor
PALMETTO ELECTRIC CO.
| Status | Location Address | State License Number | Phone |
| ACTIVE |
P.O. BOX 978 Bunnell, FL 32110 |
EC0003177 (Exp: 08/31/2026) | (386)437-3068 |
Inspection History
| Type | Request Date | Result | Inspector |
| ELECTRIC FINAL | 12/11/2025 | FINAL APPROVED | BTAYLOR |
| Note: 12/4/2025 - PREVIOUS INSPECTION NOTES Please fix items before next inspection Items front previous inspection not attended Missing bond wire front gas raiser to main metter panel ( noted on previous inspection ) 11/25/2025 - PREVIOUS INSPECTION NOTES CHECK FOR BOND WIRE. MARK GIBSON 11/25/25: Tech needs to be onsite for a run test inspection. Please coordinate with assigned inspector on the day of the re-schedule. | |||
| ELECTRIC FINAL | 12/04/2025 | Disapproved -FEE REQUIRED | CVANSTRAHLEN |
| Note: *** NOTES ADDED BY CVANSTRAHLEN 12/4/2025 11:50:38 AM *** NEC 250-GROUNDING Please fix items before next inspection Items front previous inspection not attended Missing bond wire front gas raiser to main metter panel ( noted on previous inspection ) 11/25/2025 - PREVIOUS INSPECTION NOTES CHECK FOR BOND WIRE. MARK GIBSON 11/25/25: Tech needs to be onsite for a run test inspection. Please coordinate with assigned inspector on the day of the re-schedule. | |||
| ELECTRIC FINAL | 11/25/2025 | Disapproved -FEE REQUIRED | RSIMS |
| Note: *** NOTES ADDED BY RSIMS 11/25/2025 12:38:03 PM *** CHECK FOR BOND WIRE. MARK GIBSON 11/25/25: Tech needs to be onsite for a run test inspection. Please coordinate with assigned inspector on the day of the re-schedule. |
Review History
| Department | Status | Date In | Date Out |
| ZON | COMPLETE | 08/15/2025 | 08/15/2025 |
| Note: Released By: CINDY CHIRI-GONCALVES - (386)986-4737 - CGONCALVES@PALMCOASTGOV.COM | |||
| GAS | COMPLETE | 08/15/2025 | 08/18/2025 |
| Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM | |||
| ELEC | COMPLETE | 08/11/2025 | 08/13/2025 |
| Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM | |||
| GAS | HOLD | 08/11/2025 | 08/12/2025 |
| Note: Held By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM Provide note on plans that generator exhaust must be minimum 10ft from any opening into the building per FBC Residential 2023 8Th edition M1905.2.5. If using the exception to 5ft, carbon monoxide detectors will be inspected on generator final. | |||
| ZON | HOLD | 08/11/2025 | 08/11/2025 |
| Note: Held By: TRACEY DOAK - (386)986-3751 - TDOAK@PALMCOASTGOV.COM Land Development Code Chapter 4 states: 4.01.04. Generators, permanently installed. The following standards shall apply to all permanently installed generators: A.Generators are prohibited in the required front and street side yard and prohibited in front of the front building line of the principal structure. |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| REINSPECTION RESIDENTIAL | ¤40.00 | 12/04/2025 |
| REINSPECTION RESIDENTIAL | ¤40.00 | 12/01/2025 |
| SURCHARGE FS 533.721 | ¤2.00 | 08/18/2025 |
| SURCHARGE - FS 468.631 | ¤2.00 | 08/18/2025 |
| SITE PLAN 15 | ¤15.00 | 08/18/2025 |
| ADJUSTMENT 10% | (¤12.25) | 08/18/2025 |
| ADMINISTRATIVE RESIDENTIAL | ¤30.00 | 08/18/2025 |
| INSPECTION - RESIDENTIAL | ¤60.00 | 08/18/2025 |
| PLAN REVIEW - MISC 32.50 | ¤32.50 | 08/18/2025 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤209.25 |