I want to search for...

Permit #2025090867

Permit Details

Status: INSPECT

Parcel Id: 19-12-31-2676-00000-0300
GARAGE: 426 sqft
CONDITIONED SPACE: 2193 sqft
OPENED PORCH (WITH ROOF) : 30 sqft
OPENED PORCH (WITH ROOF) : 120 sqft
Total Square Footage: 2769 sqft
Subdivision: 2364 - FLAGLER VILLAGE PHASE 2
Job Phone: 317-488-7593
Location Address: 76 WANDERING CREEK WAY
Type: BR - BUILDING RESIDENTIAL -SINGLE FAMILY
Issue Date: 04/13/2026
NOC: RECORDED
Applicant name: STEVEN THOMAS HARDING
Owner: MERITAGE HOMES OF FLORIDA INC

Address

13901 SUTTON PARK DR S

JACKSONVILLE, FL 32224

Address

SUITE C350

JACKSONVILLE, FL 32224

Lot: 30
Contracted Stated Job Value: ¤160,372.00
Job Description: Single Family Residence
Type: CN

Contractor

MERITAGE HOMES OF FLORIDA INC
Status Location Address Mailing Address State License Number Phone
ACTIVE

13901 SUTTON PARK DR

JACKSONVILLE, FL 32224

SUITE C350

JACKSONVILLE, FL 32224

CBC1264443 (Exp: 08/31/2026) 317-488-7593

Sub Contractors

STEVEN THOMAS HARDING
Status Location Address Mailing Address State License Number Phone
ACTIVE

13901 SUTTON PARK DR

JACKSONVILLE, FL 32224

SUITE C350

JACKSONVILLE, FL 32224

CBC1264443 (Exp: 08/31/2026) 317-488-7593
JAMES M GREENSLADE
Status Location Address State License Number Phone Fax
ACTIVE

311 S BAY ST

BUNNELL, FL 32110

EC13006083 (Exp: 08/31/2026) 386-263-2960 386-263-2980
BENJAMIN MICHAEL RAY
Status Location Address Mailing Address State License Number Phone Fax
ACTIVE

6310 MABLETON PKWY

JACKSONVILLE, FL 32216

SUITE 1000

MABLETON, GA 30126

CFC1428415 (Exp: 08/31/2026) 904-861-5421 904-861-5426
TERRY BRICE DICKERSON
Status Location Address State License Number Phone
ACTIVE

4300 ST JOHN'S PARKWAY

ALPHARETTA, GA 30009

CCC1326209 (Exp: 08/31/2026) 407-548-6733
COREY MICHAEL TENNANT
Status Location Address State License Number Phone
ACTIVE

3370 AGRICULTURAL CNETER DR

ST AUGUSTINE, FL 32092

CAC1819063 (Exp: 08/31/2026) 904-829-8898

Inspection History

Type Request Date Result Inspector
ALL ROUGH 06/12/2026 Disapproved - NO FEE RSIMS
Note: 6/11/26 Main underground water service piping is installed from house to meter location but no pressure test has been applied. Trench will need to be opened for visual inspection with pressure test to be inspected by All Rough Inspection 2420 at the latest. FBC-P2503.7 Previously noted in item 1 below and on 6/8/26. 6/10/2026 - PREVIOUS INSPECTION NOTES 6/10/26: 1). Main water service still needs to be pressurized as previously noted. FBC-P2503.7 2). No 5ft head presure. FBC-P2503.5.1 3). No Water pressure. FBCR P2503.7 4). Breaker panel: wires need to be phased out. NEC 200.6(B) 5). Missing firestop in top plate penetrations on exterior walls. Studs marked FS. FBC-R302.11 6). Guest bathroom - right side: bathtub drain sleeve needs to be fully sealed with cement type product. FBCR 318 6/8/2026 - PREVIOUS INSPECTION NOTES 6/8/26: Cancelled by Applicant in person. Not fully ready. Note below is still in effect. Main underground water service piping is installed from house to meter location but no pressure test has been applied. Trench will need to be opened for visual inspection with pressure test to be inspected by All Rough Inspection 2420 at the latest.
ALL ROUGH 06/10/2026 Disapproved - NO FEE RSIMS
Note: 6/10/26: 1). Main water service still needs to be pressurized as previously noted. FBC-P2503.7 2). No 5ft head presure. FBC-P2503.5.1 3). No Water pressure. FBCR P2503.7 4). Breaker panel: wires need to be phased out. NEC 200.6(B) 5). Missing firestop in top plate penetrations on exterior walls. Studs marked FS. FBC-R302.11 6). Guest bathroom - right side: bathtub drain sleeve needs to be fully sealed with cement type product. FBCR 318 6/8/2026 - PREVIOUS INSPECTION NOTES 6/8/26: Cancelled by Applicant in person. Not fully ready. Note below is still in effect. Main underground water service piping is installed from house to meter location but no pressure test has been applied. Trench will need to be opened for visual inspection with pressure test to be inspected by All Rough Inspection 2420 at the latest.
ALL ROUGH 06/08/2026 CANCELLED BY APPLICANT RSIMS
Note: 6/8/26: Cancelled by Applicant in person. Not fully ready. Note below is still in effect. Main underground water service piping is installed from house to meter location but no pressure test has been applied. Trench will need to be opened for visual inspection with pressure test to be inspected by All Rough Inspection 2420 at the latest.
LATH/BRICK/ WATER BARRIER 06/03/2026 APPROVED RSIMS
GRAVITY SEWER TEST 06/03/2026 APPROVED RSIMS
Note: Inspector Notes from Inspection 2060 *** NOTES ADDED BY RSIMS 5/4/2026 1:21:06 PM *** 5/4/26: Main underground water service piping is installed from house to meter location but no pressure test has been applied. Trench will need to be opened for visual inspection with pressure test to be inspected by All Rough Inspection 2420 at the latest.
SEWER TIE IN 06/03/2026 APPROVED - AS NOTED RSIMS
Note: 6/3/26: See note from 5/4/26. Inspector Notes from Inspection 2060 *** NOTES ADDED BY RSIMS 5/4/2026 1:21:06 PM *** 5/4/26: Main underground water service piping is installed from house to meter location but no pressure test has been applied. Trench will need to be opened for visual inspection with pressure test to be inspected by All Rough Inspection 2420 at the latest.
ROOF SHEATHING / BRACES/TIES/DOWN CELL 06/03/2026 APPROVED RSIMS
Note: 5/28/2026 - PREVIOUS INSPECTION NOTES 5/28/26: Inspection 2465 Roof Sheathing. Inspected and approved.
ROOF SHEATHING 05/28/2026 APPROVED RSIMS
Note: *** NOTES ADDED BY RSIMS 5/28/2026 11:55:33 AM *** Inspected and approved
ROOF VALLEY & METAL 05/28/2026 APPROVED RSIMS
Note: Inspection 2465 - Roof Sheathing Inspection - Checked and approved prior to this inspection.
ELECTRIC-TUG 05/28/2026 APPROVED - AS NOTED RSIMS
Note: 5/28/26: FPL emailed > Approved for TUG.
ROOF SHEATHING / BRACES/TIES/DOWN CELL 05/28/2026 PARTIALLY APPROVED RSIMS
Note: 5/28/26: Inspection 2465 Roof Sheathing. Inspected and approved.
WATER METER INSTALLATION REQUEST 05/19/2026 APPROVED ISANDERSON
WALL SHEATHING 05/19/2026 APPROVED KSANDOE
MONOLITHIC SLAB 05/06/2026 APPROVED KSANDOE
PLUMBING 1ST ROUGH UNDERGROUND 05/04/2026 APPROVED - AS NOTED RSIMS
Note: *** NOTES ADDED BY RSIMS 5/4/2026 1:21:06 PM *** 5/4/26: Main underground water service piping is installed from house to meter location but no pressure test has been applied. Trench will need to be opened for visual inspection with pressure test to be inspected by All Rough Inspection 2420 at the latest.
FORMBOARD SURVEY (OFFICE USE ONLY) 04/29/2026 APPROVED PFLANAGAN
ELECTRIC - EARLY POWER
ALL ROUGH
Note: 6/12/2026 - PREVIOUS INSPECTION NOTES 6/11/26 Main underground water service piping is installed from house to meter location but no pressure test has been applied. Trench will need to be opened for visual inspection with pressure test to be inspected by All Rough Inspection 2420 at the latest. FBC-P2503.7 Previously noted in item 1 below and on 6/8/26. 6/10/2026 - PREVIOUS INSPECTION NOTES 6/10/26: 1). Main water service still needs to be pressurized as previously noted. FBC-P2503.7 2). No 5ft head presure. FBC-P2503.5.1 3). No Water pressure. FBCR P2503.7 4). Breaker panel: wires need to be phased out. NEC 200.6(B) 5). Missing firestop in top plate penetrations on exterior walls. Studs marked FS. FBC-R302.11 6). Guest bathroom - right side: bathtub drain sleeve needs to be fully sealed with cement type product. FBCR 318 6/8/2026 - PREVIOUS INSPECTION NOTES 6/8/26: Cancelled by Applicant in person. Not fully ready. Note below is still in effect. Main underground water service piping is installed from house to meter location but no pressure test has been applied. Trench will need to be opened for visual inspection with pressure test to be inspected by All Rough Inspection 2420 at the latest.
INSULATION
BLD - BUILDING FINAL
U-CROSS CONNECTION
ROW- PRE-APRON (PRE-POUR)
ROW - FINAL APRON (AFTER POUR)
ROW- FINAL SURVEY/GRADING CERTIFICATION
ROW - FINAL INSPECTION
U -UTILITY RESIDENTIAL FINAL

Review History

Department Status Date In Date Out
BLD CANCEL 05/18/2026 05/20/2026
MECH COMPLETE 05/18/2026 05/20/2026
Note: Released By: PATRICK BUCKLEY - (386)986-3786 - PBUCKLEY@PALMCOASTGOV.COM
BLD COMPLETE 05/12/2026 05/14/2026
Note: Released By: PETER KNAPIK - (386)986-3783 - PKNAPIK@PALMCOASTGOV.COM
SW1 COMPLETE 04/29/2026 04/29/2026
Note: Released By: PARREN FLANAGAN - (386)986-2392 - PFLANAGAN@PALMCOASTGOV.COM
ZON COMPLETE 04/29/2026 04/29/2026
Note: Released By: SCOTT THOMAS - (386)986-3780 - STHOMAS@PALMCOASTGOV.COM
SW1 COMPLETE 11/17/2025 11/24/2025
Note: Released By: RODNEY RICKS - (386)986-4726 - RRICKS@PALMCOASTGOV.COM
BLD COMPLETE 09/22/2025 09/26/2025
Note: Released By: PETER KNAPIK - (386)986-3783 - PKNAPIK@PALMCOASTGOV.COM
CUSVC COMPLETE 09/22/2025 10/01/2025
Note: Released By: MICHELLE MCPARTLAND - -
ELEC COMPLETE 09/22/2025 09/29/2025
Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM
ENGIN1 COMPLETE 09/22/2025 09/22/2025
Note: Released By: LEVI SALYERDS - (386)986-2575 - LSALYERDS@PALMCOASTGOV.COM
GAS CANCEL 09/22/2025 09/24/2025
LOCATE COMPLETE 09/22/2025 09/26/2025
Note: Released By: CANDACE BOWERMASTER - - CBOWERMASTER@PALMCOASTGOV.COM
MECH COMPLETE 09/22/2025 09/24/2025
Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM
SW1 HOLD 09/22/2025 09/24/2025
Note: Held By: RODNEY RICKS - (386)986-4726 - RRICKS@PALMCOASTGOV.COM Grading comments: Per technical manual sections 200.02A.1.c.2-7 the following changes are required: - Existing and proposed elevations shall be on a 20' grid with 10' shots beyond property lines. - Road Centerline and edge pf pavement shall also be on a 20' grid. These elevations shall be expressed to the nearest 0.01. - Please ensure there is a 5% drop in the first 10' of home's foundation. - Please provide the FFE for the lanai, porch and sidewalk. These shall slope a minimum of 2% away from the home's foundation. Please feel free to call or email if there are any questions or concerns. I've attached the SW Informational packet and Example Grading Plans for your reference.
ZON COMPLETE 09/22/2025 09/23/2025
Note: Released By: SCOTT THOMAS - (386)986-3780 - STHOMAS@PALMCOASTGOV.COM
URB COMPLETE 09/22/2025 09/25/2025
Note: Released By: JOHN BEAUDET - (386)986-2456 - JBEAUDET@PALMCOASTGOV.COM

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
PLAN REVIEW - REVISION ¤32.50 05/18/2026
CONTRACTOR CHANGE ¤20.00 04/13/2026
FC IMPACT FEE EMS ¤62.00 04/13/2026
IMPACT FEE FIRE ¤434.51 04/13/2026
FC IMPACT FEE LAW ENFORCEMENT ¤218.00 04/13/2026
FC IMPACT FEE LIBRARY ¤268.00 04/13/2026
IMPACT FEE PARKS ¤1,828.01 04/13/2026
IMPACT FEE TRANSPORTATION ¤3,502.00 04/13/2026
WATER METER W/OUT TAP ¤965.03 04/13/2026
RECLAIM WATER PERMIT INSPECTIO ¤40.00 04/13/2026
SURCHARGE FS 533.721 ¤13.14 04/13/2026
SURCHARGE - FS 468.631 ¤19.71 04/13/2026
SW ENG - FOUNDATION SURVEY ¤20.00 04/13/2026
SW ENG INSPECTION 80 ¤80.00 04/13/2026
SW ENG PRE APRON ¤30.00 04/13/2026
SW ENG - REVIEW 20 ¤20.00 04/13/2026
WASTEWATER PERM INSPECTION ¤80.00 04/13/2026
WASTEWATER PERM REVIEW ¤25.00 04/13/2026
SEWER CAPITAL FACILITY ¤3,789.22 04/13/2026
WATER CAPITAL FACILITY FEE ¤3,271.91 04/13/2026
WATER PERMIT REVIEW ¤25.00 04/13/2026
SITE PLAN 30 ¤30.00 04/13/2026
WATER-METER ¤874.47 04/13/2026
WATER- TURN ON ¤50.00 04/13/2026
ADJUSTMENT 10% (¤145.97) 04/13/2026
ADMINISTRATIVE RESIDENTIAL ¤30.00 04/13/2026
INSPECTION - RESIDENTIAL ¤1,113.75 04/13/2026
PLAN REVIEW - RESIDENTIAL ¤315.90 04/13/2026
Fees Total Due: ¤0.00 Total Paid: ¤17,012.18