I want to search for...
Permit #2025091028
Permit Details
Status: COED
| Parcel Id: 07-11-31-7028-00020-0050 |
| Block: 00020 |
| Subdivision: 7028 - |
| Job Phone: 407-476-6212 |
| Location Address: 9 PHILOX LN |
| Type: SLRE - SOLAR ELECTRIC - PHOTOVOLTAIC |
| Issue Date: 10/23/2025 |
| NOC: RECORDED |
| Applicant name: FREDERICK C BRAUN |
| Owner: HOLMAN JERRY LEE JR & STEPHANIE RENEE H&W |
|
Address 9 PHILOX LN PALM COAST, FL 32164 |
| Lot: 0050 |
| Contracted Stated Job Value: ¤44,230.80 |
| Job Description: PV SOLAR PANEL INSTALLATION ROOF MOUNTED |
| Type: CN |
Contractor
PJWD ENERGY LLC
| Status | Location Address | State License Number | Phone |
| ACTIVE |
6752 CURTIS STREET ORLANDO, FL 32807 |
EC13012687 (Exp: 08/31/2026) | 407-476-6212 |
Inspection History
| Type | Request Date | Result | Inspector |
| SOLAR ELECTRIC FINAL | 12/19/2025 | FINAL APPROVED | RSIMS |
| Note: *** NOTES ADDED BY RSIMS 12/19/2025 2:57:43 PM *** 11/14/2025 - PREVIOUS INSPECTION NOTES 11/14/25: ATTEMPTED COMMUNICATION WITH CONTRACTOR MULTIPLE TIMES/WAYS. 1). Original TUG outlet (outlet below Main Panel noted previously) has now been removed by Solar contractor leaving an opening in the stucco. Outlet will need to be re-installed in original spot and in accordance with code requirements (will also need to be fully sealed around the perimeter of the outlet box). or stucco will need to be repaired to make water tight where outlet was removed. 11/12/2025 - PREVIOUS INSPECTION NOTES 11/12/25: PREVIOSLY LISTED ITEMS 1 AND 2 REMIAN UNRESOLVED. PREVIOUSLY LISTED ITEM 3 DOES NOT MEET CODE REQUIREMENTS. 1). Missing labels as required on plans. Marked on plans. FBC [A]107.4 >> STILL MISSING LABELS. SEE PLANS. 2). Breaker for GFCI has been moved so the new spot will need to be identified correctly as required. NEC 408.4 (A) >> BREAKER FOR TUG OUTLET BELOW PANEL HAS BEEN REMOVED AND A BLANK PUT IN ITS PLACE. RE-INSTALL BREAKER AND LABEL COPRRECTLY AS REQUIRED. 3). Surge protector is required at main panel. NEC-230.67(A)/(B) >> SURGE PROTECTOR NEEDS TO BE DIRECTLY AFTER THE MAIN BREAKER ON THE BUSS BAR. ALSO, NEEDS TO BE IDENTIFIED AS REQUIRED. NEC 408.4 (A) 11/6/2025 - PREVIOUS INSPECTION NOTES 11/6/25: A Virtual inspection will be available IF requested at the time of scheduling the re-inspection. If requesting a Virtual Re-inspection, please schedule the re-inspection for the same day that the deficiencies will be corrected and a FaceTime or Google Meet live virtual inspection can be completed. (Pictures are not approved). >>>>>> 1). Missing labels as required on plans. Marked on plans. FBC [A]107.4 2). Breaker for GFCI has been moved so the new spot will need to be identified correctly as required. NEC 408.4 (A) 3). Surge protector is required at main panel. NEC-230.67(A)/(B) _______________________________________________________________________________________________________________________ 11/4/2025 - PREVIOUS INSPECTION NOTES 11/4/25: No answer at the door after ringing video doorbell and knocking loudly twice. Dogs barking. Waited 5+ minutes. 1). Need access for inspection. FBC[A] 110.5 | |||
| SOLAR ELECTRIC FINAL | 11/14/2025 | Disapproved -FEE REQUIRED | RSIMS |
| Note: *** NOTES ADDED BY RSIMS 11/14/2025 2:10:09 PM *** 11/14/25: ATTEMPTED COMMUNICATION WITH CONTRACTOR MULTIPLE TIMES/WAYS. 1). Original TUG outlet (outlet below Main Panel noted previously) has now been removed by Solar contractor leaving an opening in the stucco. Outlet will need to be re-installed in original spot and in accordance with code requirements (will also need to be fully sealed around the perimeter of the outlet box). or stucco will need to be repaired to make water tight where outlet was removed. 11/12/2025 - PREVIOUS INSPECTION NOTES 11/12/25: PREVIOSLY LISTED ITEMS 1 AND 2 REMIAN UNRESOLVED. PREVIOUSLY LISTED ITEM 3 DOES NOT MEET CODE REQUIREMENTS. 1). Missing labels as required on plans. Marked on plans. FBC [A]107.4 >> STILL MISSING LABELS. SEE PLANS. 2). Breaker for GFCI has been moved so the new spot will need to be identified correctly as required. NEC 408.4 (A) >> BREAKER FOR TUG OUTLET BELOW PANEL HAS BEEN REMOVED AND A BLANK PUT IN ITS PLACE. RE-INSTALL BREAKER AND LABEL COPRRECTLY AS REQUIRED. 3). Surge protector is required at main panel. NEC-230.67(A)/(B) >> SURGE PROTECTOR NEEDS TO BE DIRECTLY AFTER THE MAIN BREAKER ON THE BUSS BAR. ALSO, NEEDS TO BE IDENTIFIED AS REQUIRED. NEC 408.4 (A) 11/6/2025 - PREVIOUS INSPECTION NOTES 11/6/25: A Virtual inspection will be available IF requested at the time of scheduling the re-inspection. If requesting a Virtual Re-inspection, please schedule the re-inspection for the same day that the deficiencies will be corrected and a FaceTime or Google Meet live virtual inspection can be completed. (Pictures are not approved). >>>>>> 1). Missing labels as required on plans. Marked on plans. FBC [A]107.4 2). Breaker for GFCI has been moved so the new spot will need to be identified correctly as required. NEC 408.4 (A) 3). Surge protector is required at main panel. NEC-230.67(A)/(B) _______________________________________________________________________________________________________________________ 11/4/2025 - PREVIOUS INSPECTION NOTES 11/4/25: No answer at the door after ringing video doorbell and knocking loudly twice. Dogs barking. Waited 5+ minutes. 1). Need access for inspection. FBC[A] 110.5 | |||
| SOLAR ELECTRIC FINAL | 11/12/2025 | Disapproved -FEE REQUIRED | RSIMS |
| Note: *** NOTES ADDED BY RSIMS 11/12/2025 2:00:42 PM *** 11/12/25: PREVIOSLY LISTED ITEMS 1 AND 2 REMIAN UNRESOLVED. PREVIOUSLY LISTED ITEM 3 DOES NOT MEET CODE REQUIREMENTS. 1). Missing labels as required on plans. Marked on plans. FBC [A]107.4 >> STILL MISSING LABELS. SEE PLANS. 2). Breaker for GFCI has been moved so the new spot will need to be identified correctly as required. NEC 408.4 (A) >> BREAKER FOR TUG OUTLET BELOW PANEL HAS BEEN REMOVED AND A BLANK PUT IN ITS PLACE. RE-INSTALL BREAKER AND LABEL COPRRECTLY AS REQUIRED. 3). Surge protector is required at main panel. NEC-230.67(A)/(B) >> SURGE PROTECTOR NEEDS TO BE DIRECTLY AFTER THE MAIN BREAKER ON THE BUSS BAR. ALSO, NEEDS TO BE IDENTIFIED AS REQUIRED. NEC 408.4 (A) 11/6/2025 - PREVIOUS INSPECTION NOTES 11/6/25: A Virtual inspection will be available IF requested at the time of scheduling the re-inspection. If requesting a Virtual Re-inspection, please schedule the re-inspection for the same day that the deficiencies will be corrected and a FaceTime or Google Meet live virtual inspection can be completed. (Pictures are not approved). >>>>>> 1). Missing labels as required on plans. Marked on plans. FBC [A]107.4 2). Breaker for GFCI has been moved so the new spot will need to be identified correctly as required. NEC 408.4 (A) 3). Surge protector is required at main panel. NEC-230.67(A)/(B) _______________________________________________________________________________________________________________________ 11/4/2025 - PREVIOUS INSPECTION NOTES 11/4/25: No answer at the door after ringing video doorbell and knocking loudly twice. Dogs barking. Waited 5+ minutes. 1). Need access for inspection. FBC[A] 110.5 | |||
| SOLAR ELECTRIC FINAL | 11/06/2025 | Disapproved -FEE REQUIRED | RSIMS |
| Note: *** NOTES ADDED BY RSIMS 11/6/2025 10:00:27 AM *** 11/6/25: A Virtual inspection will be available IF requested at the time of scheduling the re-inspection. If requesting a Virtual Re-inspection, please schedule the re-inspection for the same day that the deficiencies will be corrected and a FaceTime or Google Meet live virtual inspection can be completed. (Pictures are not approved). >>>>>> 1). Missing labels as required on plans. Marked on plans. FBC [A]107.4 2). Breaker for GFCI has been moved so the new spot will need to be identified correctly as required. NEC 408.4 (A) 3). Surge protector is required at main panel. NEC-230.67(A)/(B) _______________________________________________________________________________________________________________________ 11/4/2025 - PREVIOUS INSPECTION NOTES 11/4/25: No answer at the door after ringing video doorbell and knocking loudly twice. Dogs barking. Waited 5+ minutes. 1). Need access for inspection. FBC[A] 110.5 | |||
| SOLAR ELECTRIC FINAL | 11/04/2025 | Disapproved - NO FEE | RSIMS |
| Note: *** NOTES ADDED BY RSIMS 11/4/2025 1:25:25 PM *** 11/4/25: No answer at the door after ringing video doorbell and knocking loudly twice. Dogs barking. Waited 5+ minutes. 1). Need access for inspection. FBC[A] 110.5 |
Review History
| Department | Status | Date In | Date Out |
| BLD | COMPLETE | 10/23/2025 | 10/23/2025 |
| Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM | |||
| BLD | HOLD | 09/25/2025 | 09/25/2025 |
| Note: Held By: PETER KNAPIK - (386)986-3783 - PKNAPIK@PALMCOASTGOV.COM Provide Engineer's structural calculations and certification letter for the adequte support of existing roof framing for the proposed solar panel loads as per FBCR 324.4, with digital signature of an engineer of record as per F.S. 471.025 and F.A.C. 61G15-23.001. | |||
| ELEC | COMPLETE | 09/25/2025 | 09/25/2025 |
| Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| REINSPECTION RESIDENTIAL | ¤40.00 | 12/18/2025 |
| REINSPECTION RESIDENTIAL | ¤40.00 | 11/12/2025 |
| REINSPECTION RESIDENTIAL | ¤40.00 | 11/06/2025 |
| SURCHARGE FS 533.721 | ¤2.00 | 10/23/2025 |
| SURCHARGE - FS 468.631 | ¤2.95 | 10/23/2025 |
| ADJUSTMENT 10% | (¤21.88) | 10/23/2025 |
| ADMINISTRATIVE RESIDENTIAL | ¤30.00 | 10/23/2025 |
| INSPECTION - RESIDENTIAL | ¤123.75 | 10/23/2025 |
| SOLAR PLAN REVIEW | ¤65.00 | 10/23/2025 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤321.82 |