Permit #2025100246
Permit Details
Status: FINAL
| Parcel Id: 07-11-31-7024-00080-0160 |
| Total Square Footage: 2475 sqft |
| Block: 00080 |
| Subdivision: 7024 - |
| Job Phone: (386)672-1950 |
| Location Address: 25 PRINCESS DOLORES LN |
| Type: ME - MECHANICAL |
| Issue Date: 10/08/2025 |
| NOC: Unknown |
| Applicant name: RICHARD LEE VONBROCKEN |
| Owner: DELUCA THOMAS & PATRICIA J H&W |
|
Address 16 CAMEO DR MONROE TOWNSHIP, NJ 08831 |
| Lot: 0160 |
| Contracted Stated Job Value: ¤8,475.00 |
| Job Description: HVAC CHANGEOUT |
| Type: CN |
Contractor
VON-AIRE INC.
| Status | Location Address | State License Number | Phone | Fax |
| INACTIVE |
1738 STATE AVE HOLLY HILL, FL 32117 |
CAC035516 (Exp: 08/31/2026) | (386)672-1950 | (386)672-1952 |
Inspection History
| Type | Request Date | Result | Inspector |
| HVAC FINAL | 10/27/2025 | FINAL APPROVED | RSIMS |
| Note: *** NOTES ADDED BY RSIMS 10/27/2025 12:10:37 PM *** 10/17/2025 - PREVIOUS INSPECTION NOTES 10/17/25: A Virtual inspection will be available IF requested at the time of scheduling the re-inspection. If requesting a Virtual Re-inspection, please schedule the re-inspection for the same day that the deficiencies will be corrected and a FaceTime or Google Meet live virtual inspection can be completed. (Pictures are not approved). 1). AHU breaker is too small (Min.-45.1 amp / Max.-50 amp -- 45 amp installed). NEC 440.4 2). 1 of 3 locking caps is not locking. Left cap on ODU. FBCR M1411.8 3). Ceiling needs to be sealed where new linest and return duct enter attic space. FBC-R302.11 | |||
| HVAC FINAL | 10/17/2025 | Disapproved -FEE REQUIRED | RSIMS |
| Note: *** NOTES ADDED BY RSIMS 10/17/2025 1:44:58 PM *** 10/17/25: A Virtual inspection will be available IF requested at the time of scheduling the re-inspection. If requesting a Virtual Re-inspection, please schedule the re-inspection for the same day that the deficiencies will be corrected and a FaceTime or Google Meet live virtual inspection can be completed. (Pictures are not approved). 1). AHU breaker is too small (Min.-45.1 amp / Max.-50 amp -- 45 amp installed). NEC 440.4 2). 1 of 3 locking caps is not locking. Left cap on ODU. FBCR M1411.8 3). Ceiling needs to be sealed where new linest and return duct enter attic space. FBC-R302.11 |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| REINSPECTION RESIDENTIAL | ¤40.00 | 10/24/2025 |
| SURCHARGE FS 533.721 | ¤2.00 | 10/08/2025 |
| SURCHARGE - FS 468.631 | ¤2.00 | 10/08/2025 |
| ADMINISTRATIVE RESIDENTIAL | ¤30.00 | 10/08/2025 |
| INSPECTION - MECHANICAL | ¤60.00 | 10/08/2025 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤134.00 |